PLN63 AL Ghail Industrial Zone-NFZ, Ras Al Khaimah, United Arab Emirates
Certificate No1790a to BS 6387:2013 (Category CWZ) EN 50200:2015 (PH120) IEC 60331-21:1999 EN 60754-1:2014 EN 60754-2:2014 EN 61034-2:2005+A2:2020 EN 60332-1-2:2004+A11:2016
Read RedBook section introduction
Fire Resistant Cable
| Product | Nominal csa of conductor (mm2) see note 1 | Core Construction | BS 6387 | EN 50200 | IEC 60331-21 see note 2 | EN 61034-2 | EN 60754-1 | EN 60754-2 | LPCB Ref. No. |
|---|---|---|---|---|---|---|---|---|---|
1.0 | 2, 3 & 4 | C,W,Z | PH120 | (180+15) minutes | >60% | <0.5% HCI | Complies | 1790a/01 |
See below for all products listed in this group.
Fire Resistant Cable
| Product | Nominal csa of conductor (mm2) see note 1 | Core Construction | BS 6387 | EN 50200 | IEC 60331-21 see note 2 | EN 61034-2 | EN 60754-1 | EN 60754-2 | LPCB Ref. No. |
|---|---|---|---|---|---|---|---|---|---|
1.0 | 2, 3 & 4 | C,W,Z | PH120 | (180+15) minutes | >60% | <0.5% HCI | Complies | 1790a/01 | |
2.5 | 2, 3 & 4 | C,W,Z | PH120 | (180+15) minutes | >60% | <0.5% HCI | Complies | 1790a/01 | |
1.5 | 2, 3 & 4 | C,W,Z | PH120 | (180+15) minutes | >60% | <0.5% HCI | Complies | 1790a/01 | |
4.0 | 2, 3 & 4 | C,W,Z | PH120 | (180+15) minutes | >60% | <0.5% HCI | Complies | 1790a/01 |
Uo/U 300/500V
Notes:
1. Solid and Stranded conductor only.
2. The MESC PYRO FP 200 cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 750oC, for a duration of 180 + 15 minutes cool down at voltage of 300/500V.
3. The MESC PYRO FP 200 cables listed also met the requirements of EN 60332-1-2:2004+A11:2016