Search by Company Name

Dubai Cable Company (Private) Limited, Trading as Ducab

Ducab-M1, Plot No. - 2D12,3D2,4D2,5D2
Sector - M41, Industrial City of Abu Dhabi-1
Mussafah
Abu Dhabi
United Arab Emirates

Tel: +9714 815 8888 • Fax: +9714 815 8433
Email: ducab@ducab.com • Web: www.ducab.com


Certificate No 782j to BS 7629-1:1997. This certificate is to a withdrawn version of the BS 7629-1:1997, Cables conforming to this version of the standard may not be suitable for use within the jurisdiction fo the European Union (EU). BS 5839-1:2013 Clause 26.2d, EN 50200:2006 Class PH120, EN 50200:2006 Annex E


Ducab Flam BICC 2a

Product

Nominal csa of  conductor (mm²)

Core Construction

(excluding drain wire and earth)

BS 7629-1

(see note 6)

EN 50200

EN 50200

Annex E

BS 5839-1

Clause 26.2

LPCB
Ref. No.
Ducab Flam BICC 2a

1.5(1)

2, 3 & 4

Complies(3)

Class PH120

30min(4)

Standard(5)

782j/01
Ducab Flam BICC 2a

2.5(1)

2, 3 & 4

Complies(3)

Class PH120

30min(4)

Standard(5)

782j/01
Ducab Flam BICC 2a

4.0(2)

2, 3 & 4

Complies(3)

Class PH120

30min(4)

Standard(5)

782j/01

 

Uo/U 300/500V
  
Notes:

    1.    Solid conductor only.
2.    Stranded conductor only.
3.    In meeting the requirements of BS 7629-1:1997, the Ducab Flam BICC 2a cables listed met the requirements of smoke density of EN 61034-2:2005, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the insulation, binder tape and outer covering when tested in accordance with EN 50267-2-1:1999.
4.    The duration of 30min when tested in accordance with EN 50200:2006 Annex E is achieved by 15min for the fire and mechanical shock phase and an additional 15min for the fire, mechanical shock and water phase.
5.    The Ducab Flam BICC 2a cables listed conform to BS 7629-1:1997, met Class PH120 when tested in accordance with EN 50200:2006 and met the 30min duration when tested in accordance with EN 50200:2006 Annex E and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2013.
6.    BS 7629-1:1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31st March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators.
    
    Certificate 782h covers cables certified in accordance with BS 7629-1:2008

 


 

To read the Red Book section introduction click here.

 

< back to results page