Certificate No 305e to EN 54-20: 2006
Certificate No 305d to EN 54-20: 2006
Certificate No 305g to EN 54-20: 2006


Aspirating Smoke Detectors

Product Description LPCB
Ref. No.
XCC-010 (XCC-01000-NF)

Xtralis Class C aspirating smoke detector

Notes:         

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming with the requirements of EN 54-4.

2. System design, installation and commissioning shall be performed in

accordance with the Xtralis Class C XCC-010 product guide (Document 14159).

3. The device is approved for sensitivity Class C.

4. The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

application guide (10856 or 17785).

5. When installing pipework systems containing in-line components, guidance

from the 18336 "Xtralis Open-flow In-Line Components" document shall be

sought and the recommendations followed.

6. XCC-01000-NF alternative model number intended for French market.

305e/01
VESDA VLF-250-xx (VLF-250-01NF*) high sensitivity aspirating smoke detector

Incorporating the following ancillary equipment:

-        VIC-010 VESDAnet network card

-        VIC-020 Multifunction control card

-        VIC-030 Multifunction control card

-        VRT-V00 Remote VLF display (with 7 relays)

-        VRT-W00 Remote VLF display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLF product guide (07208).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        xx denotes alternative language version where xx (range 00 to 99)

        designates the language of the product labels.

7.        Alternative model number with suffix* as indicated, intended for French

        market.

8.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/01
VESDA VLF-250-xx (VLF-250-01NF*) high sensitivity aspirating smoke detector

Incorporating the following ancillary equipment:

-        VIC-010 VESDAnet network card

-        VIC-020 Multifunction control card

-        VIC-030 Multifunction control card

-        VRT-V00 Remote VLF display (with 7 relays)

-        VRT-W00 Remote VLF display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLF product guide (07208).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        xx denotes alternative language version where xx (range 00 to 99)

        designates the language of the product labels.

7.        Alternative model number with suffix* as indicated, intended for French

        market.

8.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/06
VESDA VLF-500-xx (VLF-500-01NF*) high sensitivity aspirating smoke detector

Incorporating the following ancillary equipment:

-        VIC-010 VESDAnet network card

-        VIC-020 Multifunction control card

-        VIC-030 Multifunction control card

-        VRT-V00 Remote VLF display (with 7 relays)

-        VRT-W00 Remote VLF display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLF product guide (07209).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        xx denotes alternative language version where xx (range 00 to 99)

        designates the language of the product labels.

7.        Alternative model number with suffix* as indicated, intended for French

        market.

8.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/02
VESDA VLF-500-xx (VLF-500-01NF*) high sensitivity aspirating smoke detector

Incorporating the following ancillary equipment:

-        VIC-010 VESDAnet network card

-        VIC-020 Multifunction control card

-        VIC-030 Multifunction control card

-        VRT-V00 Remote VLF display (with 7 relays)

-        VRT-W00 Remote VLF display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLF product guide (07209).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        xx denotes alternative language version where xx (range 00 to 99)

        designates the language of the product labels.

7.        Alternative model number with suffix* as indicated, intended for French

        market.

8.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/07
VESDA VLC High sensitivity aspirating smoke detector

Approved configurations:

- VLC-500 (VLF-50000-NF*) VLC Relays only (RO) version

- VLC-505 (VLF-50500-NF*) VLC VESDAnet (VN) version

- VLC-400 (VLF-400-NF*) VLC Apollo (AP) version

- VLC-700 (801519.F0*) VLC Esser (EB) version

- VLC-800 (VLF-800-NF*) VLC Tyco (MX) version

Approved remote units with the VLC-505 VESDAnet (VN) version:

- VRT-J00 Remote VLC display (with 7 relays)

- VRT-K00 Remote VLC display (no relays)

- VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

         pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLC product guides

        (10280 [VLC-500 & VLC-505], 03494 [VLC-400], 09411 [VLC-700],

        09515 [VLC-800]).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

        application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/03
VESDA VLC High sensitivity aspirating smoke detector

Approved configurations:

- VLC-500 (VLF-50000-NF*) VLC Relays only (RO) version

- VLC-505 (VLF-50500-NF*) VLC VESDAnet (VN) version

- VLC-400 (VLF-400-NF*) VLC Apollo (AP) version

- VLC-700 (801519.F0*) VLC Esser (EB) version

- VLC-800 (VLF-800-NF*) VLC Tyco (MX) version

Approved remote units with the VLC-505 VESDAnet (VN) version:

- VRT-J00 Remote VLC display (with 7 relays)

- VRT-K00 Remote VLC display (no relays)

- VRT-500 Remote relay unit (with 7 relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

         pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLC product guides

        (10280 [VLC-500 & VLC-505], 03494 [VLC-400], 09411 [VLC-700],

        09515 [VLC-800]).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

        application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/08
VESDA VLP High sensitivity aspirating smoke detector

Approved Configurations:

VLP-012 (VLP-01200-NF*) VLP detector with Display & Programmer

VLP-002 (VLP-00200-NF*) VLP detector with Display

VLP-400 (VLP-00000-NF*) VLP detector with Fire/OK LEDs only

VLP-401 (VLP-00100-NF*) VLP detector with Programmer & Fire/OK LEDs

VLP-100 VLP detector with OEM cover

Approved remote units:

VRT-100 Remote Programmer

VRT-200 Remote VLP Display unit (with 7 relays)

VRT-300 VESDAnet socket

VRT-500 Remote Relay unit (with 7 relays)

VRT-600 Remote VLP Display unit (without relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole  configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLP product guide (10278).

4.        Remote display, programmer and relay modules are also approved in a

        19 sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/04
VESDA VLP High sensitivity aspirating smoke detector

Approved Configurations:

VLP-012 (VLP-01200-NF*) VLP detector with Display & Programmer

VLP-002 (VLP-00200-NF*) VLP detector with Display

VLP-400 (VLP-00000-NF*) VLP detector with Fire/OK LEDs only

VLP-401 (VLP-00100-NF*) VLP detector with Programmer & Fire/OK LEDs

VLP-100 VLP detector with OEM cover

Approved remote units:

VRT-100 Remote Programmer

VRT-200 Remote VLP Display unit (with 7 relays)

VRT-300 VESDAnet socket

VRT-500 Remote Relay unit (with 7 relays)

VRT-600 Remote VLP Display unit (without relays)

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole  configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLP product guide (10278).

4.        Remote display, programmer and relay modules are also approved in a

        19 sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed.

305d/09
VESDA VLS High sensitivity aspirating smoke detector

Approved Configurations:

VLS-600 (VLS-20000-NF*) VLS with 7 relays and Fire/OK LEDs

VLS-204 (VLS-20400-NF*) VLS with 7 Relays and Display Module

VLS-214 (VLS-21400-NF*) VLS with 7 Relays, Display and Program Module

VLS-700 (VLS-30000-NF*) VLS with 12 relays and Fire/OK LEDs

VLS-304 (VLS-30400-NF*) VLS with 12 Relays and Display Module

VLS-314 (VLS-31400-NF*) VLS with 12 Relays, Display and Program Module

VLS-100 VLS with 7 Relays and OEM cover

VLS-500 VLS with 12 Relays and OEM cover

Approved Remote Units:

VRT-400 Remote Scanner Display with 7 relays

VRT-700 Remote Scanner Display with no relays

VRT-800 Remote Scanner Display with 12 relays

VRT-900 Remote Scanner Relays -12 relays

VRT-E00 Remote Scanner Relays - 7 relays

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLS product guide (10279).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed

305d/05
VESDA VLS High sensitivity aspirating smoke detector

Approved Configurations:

VLS-600 (VLS-20000-NF*) VLS with 7 relays and Fire/OK LEDs

VLS-204 (VLS-20400-NF*) VLS with 7 Relays and Display Module

VLS-214 (VLS-21400-NF*) VLS with 7 Relays, Display and Program Module

VLS-700 (VLS-30000-NF*) VLS with 12 relays and Fire/OK LEDs

VLS-304 (VLS-30400-NF*) VLS with 12 Relays and Display Module

VLS-314 (VLS-31400-NF*) VLS with 12 Relays, Display and Program Module

VLS-100 VLS with 7 Relays and OEM cover

VLS-500 VLS with 12 Relays and OEM cover

Approved Remote Units:

VRT-400 Remote Scanner Display with 7 relays

VRT-700 Remote Scanner Display with no relays

VRT-800 Remote Scanner Display with 12 relays

VRT-900 Remote Scanner Relays -12 relays

VRT-E00 Remote Scanner Relays - 7 relays

Notes:

1.        For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

        with power from a power supply conforming to the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C. The Class of any

        pipe/hole configuration and detector sensitivity must be determined using

        ASPIRE2.

3.        System design, installation and commissioning shall be performed in

        accordance with the VESDA VLS product guide (10279).

4.        Remote display, programmer and relay modules are also approved in a 19

        sub rack.

5.        The detector is also approved when used with in-line filter models,

        E700-FILASSY and VSP-850 in accordance with the appropriate

        VESDA application guide (10856 or 17785).

6.        Alternative model numbers with suffix* as indicated, intended for French

        market.

7.        When installing pipework systems containing in-line components, guidance

        from the 18336 "Xtralis Open-flow In-Line Components" document shall be

        sought and the recommendations followed

305d/10
XCC-010 (XCC-01000-NF)

Xtralis Class C aspirating smoke detector

Notes:         

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming with the requirements of EN 54-4.

2. System design, installation and commissioning shall be performed in

accordance with the Xtralis Class C XCC-010 product guide (Document 14159).

3. The device is approved for sensitivity Class C.

4. The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

application guide (10856 or 17785).

5. When installing pipework systems containing in-line components, guidance

from the 18336 "Xtralis Open-flow In-Line Components" document shall be

sought and the recommendations followed.

6. XCC-01000-NF alternative model number intended for French market.

305e/02
VLI-880

    (VLI-88000-NF)   VESDA Laser Industrial aspirating smoke detector

Incorporating the following ancillary equipment:

-        VRT-Q00 Remote VLI display (with 7 relays)

-        VRT-T00 Remote VLI display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:         

1.For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming to the requirements of EN 54-4.

2.The device is approved for sensitivity Classes A, B and C.

The Class of any pipe/hole configuration and detector sensitivity must be

determined using ASPIRE2.

3.System design, installation and commissioning shall be performed in

accordance with the VESDA VLI product guide (18500).

4.Remote display, programmer and relay modules are also approved in a 19 sub rack.

5.The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA application guide

(10856 or 17785).

6. VLI-88000-NF is the alternative model number intended for French market.

7.When installing pipework systems containing in-line components, guidance from the 18336

"Xtralis Open-flow In-Line Components" document shall be sought and the recommendations followed.

305g/01
VLI-885

    (VLI-88500-NF) VESDA Laser Industrial aspirating smoke detector with VESDAnet card

Incorporating the following ancillary equipment:

-        VRT-Q00 Remote VLI display (with 7 relays)

-        VRT-T00 Remote VLI display (no relays)

-        VRT-500 Remote relay unit (with 7 relays)

Notes:         

1.For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming to the requirements of EN 54-4.

2.The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole

configuration and detector sensitivity must be determined using ASPIRE2.

3.System design, installation and commissioning shall be performed in

accordance with the VESDA VLI product guide (18500).

4.Remote display, programmer and relay modules are also approved in a 19 sub rack.

5.The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA application guide

(10856 or 17785).

6. VLI-88500-NF alternative model number intended for French market.

7 .When installing pipework systems containing in-line components, guidance from the 18336

"Xtralis Open-flow In-Line Components" document shall be sought and the recommendations followed.

305g/02
XCC-011 (XCC-01100-NF)

Xtralis Class C aspirating smoke detector

Notes:  

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming with the requirements of EN 54-4.

2. System design, installation and commissioning shall be performed in

accordance with the Xtralis Class C XCC-011 product guide (Document 19137).

3. The device is approved for sensitivity Class C.

4. The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

application guide (10856 or 17785).

5. When installing pipework systems containing in-line components, guidance

from the 18336 "Xtralis Open-flow In-Line Components" document shall be

sought and the recommendations followed.

6. XCC-01100-NF alternative model number intended for French market.

305e/03
XCC-011 (XCC-01100-NF)

Xtralis Class C aspirating smoke detector

Notes:  

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied

with power from a power supply conforming with the requirements of EN 54-4.

2. System design, installation and commissioning shall be performed in

accordance with the Xtralis Class C XCC-011 product guide (Document 19137).

3. The device is approved for sensitivity Class C.

4. The detector is also approved when used with in-line filter models,

E700-FILASSY and VSP-850 in accordance with the appropriate VESDA

application guide (10856 or 17785).

5. When installing pipework systems containing in-line components, guidance

from the 18336 "Xtralis Open-flow In-Line Components" document shall be

sought and the recommendations followed.

6. XCC-01100-NF alternative model number intended for French market.

305e/04
VLQ-100 (VLQ-10000-NF)

VESDA VLQ Aspirating Smoke Detector

Notes:

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming to the requirements of EN 54-4.

2. The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity is provided in the VESDA VLQ Product Guide (26104).

3. System design, installation and commissioning shall be performed in

accordance with the VESDA VLQ Product Guide (26104).

4. The detector is also approved when used with in-line filter model,

VSP-850 in accordance with the VESDA application guide (17785).

5.  The detector is also approved when used with the ECO gas detection module when fitted with the ECO-LQ Adaptor.

6. VLQ-10000-NF is the alternative model number intended for French market (Product Guide 26746).

7. When installing pipework systems containing in-line components, guidance from the 18336 "Xtralis Open-flow In-Line Components" document shall be sought and the recommendations followed.

305g/03
ILQ-100 (ILQ-10000-NF)

ICAM ILQ Aspirating Smoke Detector

Notes:

1. For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming to the requirements of EN 54-4.

2. The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity is provided in the ICAM ILQ Product Guide (26105).

3. System design, installation and commissioning shall be performed in

accordance with the ICAM ILQ Product Guide (26105).

4. The detector is also approved when used with in-line filter model,VSP-850 in accordance with the application guide (17785).

5.  The detector is also approved when used with the ECO gas detection module when fitted with the ECO-LQ Adaptor.

6. ILQ-10000-NF is the alternative model number intended for French market (Product Guide 26749).

7. When installing pipework systems containing in-line components, guidance from the 18336 "Xtralis Open-flow In-Line Components" document shall be sought and the recommendations followed.

305g/04

 