Search by Company Name

Tyco Safety Products (Great Yarmouth)

Burlingham House
Hewett Road
Gapton Hall Industrial Estate
Great Yarmouth
Norfolk
NR31 0NN
United Kingdom

Tel: +44 (0) 1493 417600 • Fax: +44(0) 1493 417700
Email: macron-info@tycoint.com • Web: www.macron-safety.com


Certificate No 587b to LPS 1230


Tyco Safety Products Sapphire™

Product

Risk

Design

Concentration

Comments

LPCB
Ref. No.
Tyco Safety Products Sapphire™

Class A Standard (Solid fires e.g. paper, wood, plastics)

6.0%

Design concentration includes 30% safety factor

587b/01
Tyco Safety Products Sapphire™

Class A Cables (Solid fire risks including cables)

6.1%

Confirmation that minimum safety factor is adequate

587b/01
Tyco Safety Products Sapphire™

Class B (Liquid Fires e.g. heptane)

6.4%

Design concentration includes 30% safety factor

587b/01

 

Design concentration Class A Standard and Class B  = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables  System test concentration.  Where this value is lower than the Class A Standard value, the Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 208832 v2.
Extinguishing concentrations are as tested in BRE Test Report Number 208831 (ISO 14520-1 tests)
  
This system uses:

        Design, Installation, Maintenance and User Manual:                                                                TSP NovecTM  1230 Total Flooding Systems (Engineered & Pre-engineered) Design Manual Reference 14a-06T Issue 5                               
  
Software Programme:                                                                TSPNovec 1230 FlowCalc Version TSP3.60b  
        
  
  a)    This system is suitable for storage in environmental conditions from -20° to +50°.
b)    System pressure is specified as 25 bar @ 20°C

 


 

To read the Red Book section introduction click here.

 