Unit 31
Springvale Industrial Estate
Cwmbran
Gwent
NP44 5BD
United Kingdom
Tel: +44 (0)1633 865558
•
Fax: +44 (0)1633 866656
Email: fstinfo@fike.com
•
Web: www.fikesafetytechnology.co.uk
Certificate No 331f to EN 54-3: 2000 + A1: 2002 + A2: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006,
EN 54-17: 2005, EN 54-18: 2005 and CEA 4021:July 2003 (en)
Certificate No 331n to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006,
EN 54-17:2005, EN 54-18: 2005 and CEA 4021:July 2003 (en)
Certificate No 331g to EN 54-3: 2000 + A1: 2002 + A2: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006 and CEA 4021: July 2003 (en)
Certificate No 331p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006 and CEA 4021: July 2003 (en)
Multi-Sensor Detectors
Product | Description | LPCB Ref. No. |
---|---|---|
205-0001 | Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator and sounder. Notes: 1. Meets the requirements of EN 54-5:2000 at the following settings: HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature.
2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement.
3. Approved at the following tones - SP1 Continuous 970Hz SP2 Pulsed 970Hz 1s on 1s off SP3 Dual Tone 970Hz 0.25s , 800Hz 0.25s SP4* Sweep Up 800-970Hz over 1s SP5 Slow Whoop 500-1200Hz over 3s, 0.5s off SP6* Sweep Down 1200-500Hz over 1s SP7 Dual French 550Hz 0.1s, 440Hz 400ms * Not available if the I/O facility is used. |
331f/01 |
205-0012 | Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator and sounder/strobe. Notes: 1. Meets the requirements of EN 54-5:2000 at the following settings: HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature.
2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement.
3. Approved at the following tones - SP1 Continuous 970Hz SP2 Pulsed 970Hz 1s on 1s off SP3 Dual Tone 970Hz 0.25s , 800Hz 0.25s SP4* Sweep Up 800-970Hz over 1s SP5 Slow Whoop 500-1200Hz over 3s, 0.5s off SP6* Sweep Down 1200-500Hz over 1s SP7 Dual French 550Hz 0.1s, 440Hz 400ms * Not available if the I/O facility is used.
4. The strobe function is not approved. |
331f/02 |
205-0003 | Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator. Notes: 1. Meets the requirements of EN 54-5:2000 at the following settings: HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature.
2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement. |
331n/01 |
204-0001 | Twinflex Multipoint ASD Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder (45-0048-202-01 Base) Notes:
HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature HM3 Class C standard temperature, fixed temperature 2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement 3. Meets the requirements of EN 54-3: 2001 at the following tones - SP1 Continuous 970Hz SP2 Alternating tone at 800/970Hz SP3 Sweep Up 800-970Hz |
331g/02 |
204-0012 | Twinflex Multipoint ASD Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder & Strobe Notes: 1. Meets the requirements of EN 54-5:2000 at the following settings: HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature HM3 Class C standard temperature, fixed temperature 2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement 3. Meets the requirements of EN 54-3: 2001 at the following tones - SP1 Continuous 970Hz SP2 Alternating tone at 800/970Hz SP3 Sweep Up 800-970Hz 4. The strobe function is not approved to EN 54-23:2010 |
331g/03 |
204-0003 | Twinflex Multipoint ASDConventional Optical Smoke and Heat Multisensor Detector (45-0048-202-01 Base) Notes:
HM1 Class A1 standard temperature rate of rise enhanced HM2 Class A1 standard temperature, fixed temperature HM3 Class C standard temperature, fixed temperature 2. Meets the requirements of EN 54-7:2000 at the following settings: SM1 Standard optical sensitivity with high thermal enhancement SM2 Standard optical sensitivity with normal thermal enhancement |
331p/02 |
Bases