Search by Certificate Number

Fike Safety Technology Ltd

Unit 31
Springvale Industrial Estate
Cwmbran
Gwent
NP44 5BD
United Kingdom

Tel: +44 (0)1633 865558 • Fax: +44 (0)1633 866656
Email: fstinfo@fike.com • Web: www.fikesafetytechnology.co.uk


Certificate No 331f to EN 54-3: 2000 + A1: 2002 + A2: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006, EN 54-17: 2005, EN 54-18: 2005 and CEA 4021:July 2003 (en)
Certificate No 331n to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006, EN 54-17:2005, EN 54-18: 2005 and CEA 4021:July 2003 (en)
Certificate No 331g to EN 54-3: 2000 + A1: 2002 + A2: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006 and CEA 4021: July 2003 (en)
Certificate No 331p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006 and CEA 4021: July 2003 (en)


Multi-Sensor Detectors

Product Description LPCB
Ref. No.
205-0001

Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator and sounder.

Notes:

1.           Meets the requirements of EN 54-5:2000 at the following settings:

        HM1 Class A1 standard temperature rate of rise enhanced

        HM2 Class A1 standard temperature, fixed temperature.

2.           Meets the requirements of EN 54-7:2000 at the following settings:

        SM1 Standard optical sensitivity with high thermal enhancement

        SM2 Standard optical sensitivity with normal thermal enhancement.

3.        Approved at the following tones -

        SP1        Continuous 970Hz

        SP2        Pulsed 970Hz 1s on 1s off

        SP3        Dual Tone 970Hz 0.25s , 800Hz 0.25s

        SP4*        Sweep Up 800-970Hz over 1s

        SP5        Slow Whoop 500-1200Hz over 3s, 0.5s off

        SP6*        Sweep Down 1200-500Hz over 1s

        SP7        Dual French 550Hz 0.1s, 440Hz 400ms

        * Not available if the I/O facility is used.

331f/01
205-0012

Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator and sounder/strobe.

Notes:

1.           Meets the requirements of EN 54-5:2000 at the following settings:

        HM1 Class A1 standard temperature rate of rise enhanced

        HM2 Class A1 standard temperature, fixed temperature.

2.           Meets the requirements of EN 54-7:2000 at the following settings:

        SM1 Standard optical sensitivity with high thermal enhancement

        SM2 Standard optical sensitivity with normal thermal enhancement.

3.        Approved at the following tones -

        SP1        Continuous 970Hz

        SP2        Pulsed 970Hz 1s on 1s off

        SP3        Dual Tone 970Hz 0.25s , 800Hz 0.25s

        SP4*        Sweep Up 800-970Hz over 1s

        SP5        Slow Whoop 500-1200Hz over 3s, 0.5s off

        SP6*        Sweep Down 1200-500Hz over 1s

        SP7        Dual French 550Hz 0.1s, 440Hz 400ms

        * Not available if the I/O facility is used.

4.        The strobe function is not approved.

331f/02
205-0003

Sita analogue addressable optical smoke and heat multisensor detector with short circuit isolator.

Notes:

1.           Meets the requirements of EN 54-5:2000 at the following settings:

        HM1 Class A1 standard temperature rate of rise enhanced

        HM2 Class A1 standard temperature, fixed temperature.

2.        Meets the requirements of EN 54-7:2000 at the following settings:

        SM1 Standard optical sensitivity with high thermal enhancement

        SM2 Standard optical sensitivity with normal thermal enhancement.

331n/01
204-0001

Twinflex Multipoint ASD Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder (45-0048-202-01 Base)

Notes:

  1. Meets the requirements of EN 54-5:2000 at the following settings:

     HM1 Class A1 standard temperature rate of rise enhanced

     HM2 Class A1 standard temperature, fixed temperature

     HM3 Class C standard temperature, fixed temperature

2.  Meets the requirements of EN 54-7:2000 at the following settings:

     SM1 Standard optical sensitivity with high thermal enhancement

     SM2 Standard optical sensitivity with normal thermal enhancement

3.  Meets the requirements of EN 54-3: 2001 at the following tones -

     SP1   Continuous 970Hz

     SP2         Alternating tone at 800/970Hz

     SP3   Sweep Up 800-970Hz

331g/02
204-0012

Twinflex Multipoint ASD Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder & Strobe

Notes:

1.  Meets the requirements of EN 54-5:2000 at the following settings:

     HM1 Class A1 standard temperature rate of rise enhanced

     HM2 Class A1 standard temperature, fixed temperature

     HM3 Class C standard temperature, fixed temperature

2.  Meets the requirements of EN 54-7:2000 at the following settings:

     SM1 Standard optical sensitivity with high thermal enhancement

     SM2 Standard optical sensitivity with normal thermal enhancement

3.  Meets the requirements of EN 54-3: 2001 at the following tones -

     SP1   Continuous 970Hz

     SP2         Alternating tone at 800/970Hz

     SP3   Sweep Up 800-970Hz

4.  The strobe function is not approved to EN 54-23:2010

331g/03
204-0003

Twinflex Multipoint ASDConventional Optical Smoke and Heat Multisensor Detector (45-0048-202-01 Base)

Notes:

  1.   Meets the requirements of EN 54-5:2000 at the following settings:

      HM1 Class A1 standard temperature rate of rise enhanced

      HM2 Class A1 standard temperature, fixed temperature

      HM3 Class C standard temperature, fixed temperature

2.   Meets the requirements of EN 54-7:2000 at the following settings:

      SM1 Standard optical sensitivity with high thermal enhancement

      SM2 Standard optical sensitivity with normal thermal enhancement

331p/02

 

Bases
45-0048-202 ASD Base
45-0048-202-01 Standard Base
25-0065-202 Base extension
45-0306-202 Twinflex Multipoint Base
200-0014 Shallow Base

  
  


 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page