Search by Certificate Number

Chemring Energetics Limited

Ardeer Site
Stevenston
Ayrshire
Scotland
KA20 3LN
United Kingdom

Tel: +44 (0)1294 487007 • Fax: +44 (0)1294 487230
Email: campbell.howie@chemringenergetics.co.uk • Web: www.chemringenergetics.co.uk


Certificate No 313a


Protractor ‘Metron’ Actuators

Product

Stroke (mm)

Work Outout J (minimum)

Resistance Range Ohms

Allfire Amps (50ms)

Nofire Amps (5 sec)

LPCB
Ref. No.
DR2001/C13

3.4

0.69

0.9 to 1.6

0.6

0.3

313a/01
DR2003/C1

3.4

1.18

0.9 to 1.6

0.6

0.3

313a/02
DR2003/C6

3.4

1.18

0.9 to 1.6

0.6

0.3

313a/02
DR2003/C35

3.4

1.18

0.9 to 1.6

0.6

0.3

313a/02
DR2004/C1

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/03
DR2005/C1

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2005/C2

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2005/C3

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2005/C6

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2005/C9

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2005/C35

9.5

3.43

0.9 to 1.6

0.6

0.3

313a/04
DR2006/C1

13.5

4.9

0.9 to 1.6

0.6

0.3

313a/05
DR2006/C2

13.5

4.9

0.9 to 1.6

0.6

0.3

313a/05
DR2014/C1

9.5

4.9

0.9 to 1.6

0.6

0.3

313a/06
DR2053

3.4

0.8

7 to 12

0.16

0.05

313a/07

 

Maximum monitoring current for all models is 0.01A.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page