Search by Certificate Number

Morley-IAS by Honeywell, Pittway Tecnologica Srl

Via Caboto 19/3
Trieste
34147
Italy

Tel: +44 (0)1444 230300 • Fax: +44 (0)1444 230888
Email: sales@morleyias.co.uk • Web: www.morley-ias.co.uk


Certificate No 199ae-(cl-1) to EN54-17: 2005 & EN54-20: 2006


Aspirating Smoke Detectors

Product Description LPCB
Ref. No.
MI-FL2011EI-HS

Analogue Addressable Single Channel Loop-Based Aspirating Detector (F-INF-25 In line filter)

Notes:

1.        For compliance with Clause 5.10 of EN54-20: 2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeIQ software.

3.        The approval of the detector is conditional upon the following requirements:

  • Design including accessories used, installation and commissioning are performed in accordance with the Advanced Set-up and Control Guide (I56-3888-xxx)
199ae/01
MI-FL2012EI-HS

Analogue Addressable Loop-Based Single Channel Unit Common Chamber Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1.        This device has single channel capability with two high sensitivity smoke sensors in a common chamber.

2.        For compliance with Clause 5.10 of EN54-20: 2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

3.        The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeIQ software.

4.        The approval of the detector is conditional upon the following requirements:

  • Design including accessories used, installation and commissioning are performed in accordance with the Advanced Set-up and Control Guide (I56-3888-xxx).
199ae/02
MI-FL2022EI-HS

Analogue Addressable Dual Channel Loop-Based Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1.        For compliance with Clause 5.10 of EN54-20: 2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

2.        The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeIQ software.

3.        The approval of the detector is conditional upon the following requirements:

  • Design including accessories used, installation and commissioning are performed in accordance with the Advanced Set-up and Control Guide (I56-3888-xxx).
199ae/03

 

Accessories
    F-INF-25    In line filter
    

 


 

To read the Red Book section introduction click here.

 

< back to results page