Search by Certificate Number

Macron Safety Systems (UK) Ltd

Burlingham House
Hewett Road
Gapton Hall Industrial Estate
Great Yarmouth
Norfolk
NR31 0NN
United Kingdom

Tel: +44 (0)1493 417600 • Fax: +44 (0)1493 417700
Email: infogy@tycoint.com • Web: www.macron-safety.com


Certificate No 587Bb to LPS 1230


Hygood Sapphire™

Product

Risk

Design

Concentration

Comments

LPCB
Ref. No.
Hygood Sapphire™

Class A Standard (Solid fires, e.g. paper, wood, plastics)

6.0%

Design concentration includes 30% safety factor

587Bb/01
Hygood Sapphire™

Class A Cables (Solid fire risks including cables)

6.1%

Confirmation that minimum safety factor is adequate

587Bb/01
Hygood Sapphire™

Class B (Liquid fires e.g. heptane)

6.4%

Design concentration includes 30% safety factor

587Bb/01

 

Design concentration Class A Standard and Class B  = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables  System test concentration.  Where this value is lower than the Class A Standard value, the Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 208832 v2.
Extinguishing concentrations are as tested in BRE Test Report Number 208831 (ISO 14520-1 tests)
  
This system uses:

        Design, Installation, Maintenance and User Manual: Hygood NovecTM  1230 Total Flooding Systems (Engineered & Pre-engineered) Design Manual Reference 14a-06H Issue 5                               
  
Software Programme:           Novec 1230 FlowCalc Version HYG3.60b  
        
  
a)    This system is suitable for storage in environmental conditions from -20° to +50°.
b)   System pressure is specified as 24.8 bar @ 20°C

 


 