8985 Town Center Parkway
Bradenton
FL 34202
USA
Certificate No 902c-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-23:2010
Certificate No 904h-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-23:2010
Product | Description | LPCB Ref. No. |
---|---|---|
G1x-HDVM-E | Genesis E-Version Temporal Sounder- Beacon Notes:
1. Approved with backboxes G1xB-MP and 27193-xx - Continuous 3200Hz (interrupted at 40Hz) - Temporal 3200Hz (interrupted at 40Hz); 2 pulses 0.5s on / 0.5s off, - 1 pulse 0.5s on / 1.5s off, repeat
3. The wall mounted VAD meets the requirements of EN 54-23:2010 for the following: @15cd (W-3.0-2.8 or W-2.5-3.3) @30cd (W-4.4-4.5) @75cd (W-6.0-7.5) @110cd (W-6.5-8.4) - Synchronization - Flash rate 1Hz 4. x denotes housing colours Blank = White housing R = Red housing F = White housing with Fire Marking RF = Red housing with Fire Marking |
902c/01 |
G1AVxx-E | Sounder Beacon
Notes: 1. Meets the requirements of EN 54-23 for the following: - Category (W-2.4-8.5) - Flash rate 1Hz - Synchronization
- Operating voltage range 16-33 VDC 2. Meets the requirements of EN 54-3 with Continuous and Temporal tones and operating voltages of 16-33 VDC 3. Certified for use with G1RB-E and G1WB-E back boxes 4. This is a Type A Indoor Device
xx = RF or RN or WF or WN RF is Red with Fire Marking RN is Red with No Fire Marking WF is White with Fire Marking WN is White with No Fire Marking |
904h/01 |
Bases: