Context Plus Limited

Progress House
Newby Road
Hazel Road
Stockport
SK7 5DA
United Kingdom

Tel: 01612572541
Email: contextplus@xportsales.com • Web: www.contextplus.co.uk


Certificate No 176b-(cl-2) to EN 54-2:1997 + A1:2006 EN 54-4:1997 + A1:2002 + A2:2006
Certificate No 176c-(cl-2) to EN 54-2:1997 + A1:2006 EN 54-4:1997 + A1:2002 + A2:2006 EN 12094-1:2003


Product Description LPCB
Ref. No.
XFP502/X/CON

2 Loop, 32 Zone Analogue Addressable Control and Indicating Equipment using Apollo Protocol, Metal Housing

Incorporating the following units:

SPF0501021        Switch mode power supply board

SPF0501425         XFP Apollo 2 loop,      Mainboard

SPF0501199        Display board (Keypad display)

Certified with the following options with requirements from EN54-2: 1997

7.8        Output to fire alarm device(s)

7.11        Delays to the actioning of outputs fire alarm devices and fire routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of each address point

10        Test condition

Notes:

1. Scope of approval does not include the operation of the network functionality.

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/02
XFP501/X/CON

1 Loop, 32 Zone Analogue Addressable Control and Indicating Equipment using Apollo Protocol, Metal Housing

Incorporating the following units

SPF0501021        Switch mode power supply board

SPF0501424        XFP Apollo 1 loop, Mainboard

SPF0501199        Display board (keypad display)

Certified with the following options with requirements from EN54-2: 1997

7.8        Output to fire alarm device(s)

7.11        Delays to the actioning of outputs fire alarm devices and fire routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of each address point

10        Test condition

Notes:

1.     Scope of approval does not include the operation of the network functionality.

2.     This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/04
XFP501E/X/CON

1 Loop, 16 Zone Analogue Addressable Control and Indicating Equipment using Apollo Protocol, Plastic Housing

Incorporating the following units:

SPF0702025        Switch mode power supply board

SPF0501116        XFP Apollo 1 loop, main motherboard

Certified with the following options with requirements from EN54-2: 1997

7.8        Output to fire alarm device(s)

7.11        Delays to the actioning of outputs fire alarm devices and fire routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of each address point

10        Test condition

Notes:

1.        Scope of approval does not include the operation of the network functionality.

2.         This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/06
CFP702-4/CON

Two Zone Conventional Control and Indicating Equipment

Incorporating the units:

SPF0702025        Switch mode power supply unit board

SPF0724871        2 Zone main control board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices(s)

7.11        Delays to outputs

10        Test condition

Notes:

1. Scope of approval does not include the operation of the network functionality.

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/07
CFP704-4/CON

Four Zone Conventional Control and Indicating Equipment

Incorporating the units:

SPF0702025        Switch mode power supply unit board

SPF0724873        4 Zone main control board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices(s)

7.11        Delays to outputs

10        Test condition

Notes:

1.        Scope of approval does not include the operation of the network functionality.

2.        This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/08
CFP708-4/CON

Eight Zone Conventional Control and Indicating Equipment

Incorporating the units:

SPF0702025        Switch mode power supply unit board

SPF0724875        8 Zone main control board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices(s)

7.11        Delays to outputs

10        Test condition

Notes:

1.         Scope of approval does not include the operation of the network functionality.

2.        This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/09
XFP501E/CA/CON

1 Loop 16 Zone Analogue Addressable Control and Indicating Equipment using CAST Protocol, Plastic Housing

Incorporating the following modules:

SPF0050127        1 Loop Main board

SPF0702025        Switch mode power supply board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of addressable points

10        Test condition

Notes:

1. Scope of approval does not include the operation of the network functionality.

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/26
XFP501/CA/CON

1 Loop 32 Zone Analogue Addressable Control and Indicating Equipment using CAST Protocol, Metal Housing

Incorporating the following modules:

SPF0050110        1 Loop Main board

SPF0501021        Switch mode power supply board

SPF0501199        Display Board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of addressable points

10        Test condition

Notes:

1. Scope of approval does not include the operation of the network functionality.

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/27
XFP502/CA/CON

2 Loop 32 Zone Analogue Addressable Control and Indicating Equipment using CAST Protocol, Metal Housing

Incorporating the following modules:

SPF0050210        2 Loop Main board

SPF0501021        Switch mode power supply board

SPF0501199        Display Board

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

9.5        Disablement of addressable points

10        Test condition

Notes:

1.        Scope of approval does not include the operation of the network functionality.

2.        This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/28
ZFP1/40/CA/CON

1 Loop Analogue Addressable Control and Indicating Equipment, 5A PSU, 40 Zone Indication, Standard Cabinet

Incorporating the following modular units:

RPF0000051        Main display PCB

RPF0999308        Loop 1 - 2 PCB
RPF0000025        Z47 - 40 LED Display

RPF0000060        Credit card Processor board

RPF0361020        5 Amp PSU module

Optional Modules:

RPF0000028        Z11 - 4-way relay PCB

RPF0000029     Z13 - 8 way I/O PCB

RPF0000024     Z48 - 40 LED Display with 5 key switches

Certified with the following options with requirements from EN 54-2:

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.13        Alarm counter

8.3        Fault signal from points

9.5         Disablement of each addressable point

10        Test Condition

Notes:

1.        Scope of approval does not include the operation of the network functionality.

2.        This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/32
ZFP2/40/CA/CON

2 Loop Analogue Addressable Control and Indicating Equipment, 5A PSU, 40 Zone Indication, Standard Cabinet

Incorporating the following modular units:

RPF0000051        Main display PCB

RPF0999308        Loop 1 - 2 PCB
RPF0000025        Z47 - 40 LED Display

RPF0000060        Credit card Processor board

RPF0361020        5 Amp PSU module

Optional Modules:

RPF0000028        Z11 - 4-way relay PCB

RPF0000029        Z13 - 8 way I/O PCB

RPF0000024        Z48 - 40 LED Display with 5 key switches

Certified with the following options with requirements from EN 54-2:

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.13        Alarm counter

8.3        Fault signal from points

9.5         Disablement of each addressable point

10        Test Condition

Notes:

1.        Scope of approval does not include the operation of the network functionality.

2.         This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/33
ZFP4/40/CA/CON

4 Loop Analogue Addressable Control and Indicating Equipment, 5A PSU, 40 zone indication, Standard Cabinet

Incorporating the following modular units:

RPF0000051        Main display PCB

RPF0999308        Loop 1 - 2 PCB

RPF0999307      Loop 3 - 4 expansion PCB

RPF0000025             Z47 - 40 LED Display

RPF0000060            Credit card Processor board

RPF0361020            5 Amp PSU module

Optional Modules:

RPF0000028        Z11 - 4-way Relay PCB

RPF0000029            Z13 - 8-way I/O PCB

RPF0000024             Z48 - 40 LED Display with 5 key switches

Certified with the following options with requirements from EN 54-2:

7.8        Output to fire alarm devices

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.13        Alarm counter

8.3        Fault signal from points

9.5        Disablement of each addressable point

10        Test Condition

Notes:

1. Scope of approval does not include the operation of the network functionality.

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

176b/34
EP203/CON

Conventional Three Zone 'Class A' Extinguisher Control Panel under Context Plus Brand

Incorporating the following units:

SPF0000203        Main extinguisher control

SPF0000212        External relay interface

SPF0003613        Power supply unit

SPF0000214        EP214 terminator

Incorporating as modular units:

EP210S        Remote Status Unit "Surface Mount" optional (See Note 1)

EP211                Economy Status Unit optional (See Note 1)

Certified with the following options with requirements from EN 12094-1:2003

4.17        Delay of extinguishing signal

4.18         Signal representing the flow of extinguishing agent

4.19         Monitoring of the status of components

4.20             Emergency hold device

4.21             Control of flooding time

4.23        Manual only mode

4.26        Triggering of equipment outside the system

4.27        Emergency abort device

4.30        Activation of alarm devices with different signals

Certified with the following options with requirements from EN 54-2:1997

7.8        Output to fire alarm device(s)

7.11         Delays to the auctioning of outputs fire alarm devices and fire routing equipment

7.13        Alarm counter

10        Test condition

Note:

        1)  Optional Remote Status Unit part No. EP210S & Economy Status Unit part No. EP211 are not certified meeting the requirements of the standards specified

        2)  Meets the requirements of EN12094-3:2003, Class A - i.e. operational temperature range of -5°C to +40°C.

176c/01

 

 


 