Haci Ayvaz End. Mam. San. Ve Tic. A.S.

Ataturk Sanayi Bolgesi
Mustafa Inan Cd. No:44
Arnavutkoy
Istanbul
34555
Turkey

Tel: +90 212 771 0145
Email: ealtug@ayvaz.com • Web: www.ayvaz.com


Certificate No 331Av to EN 12094-4 & an LPCB schedule of requirements


Actuator Assemblies

Product

Description

LPCB
Ref. No.
AZ-71-120

Relay actuator

331Av/04
AZ-70-325-2

Nitrogen Actuator Assembly (Normally Open Pressure Switch Contacts)

331Av/04
AZ-70-325-4

Nitrogen Actuator Assembly (Normally Closed Pressure Switch Contacts)

331Av/04

 

Notes:
  
- The range of equipment is approved for use in conjunction with Ayvaz Equipment, Design & Service Manual P/N AZ-06-439 (Rev. 0 / October, 2018)
- The following equipment is suitable for use at storage temperatures from-20°C to 50°C
- Containers are superpressurised to 25bar at 21°C
- Maximum system working pressure at 50°C for HFC227ea is 34.6 bar; fill ratios 0.5 kg/l min. to 1.1 kg/l max.

 


 