Search by Certificate Number

Elite Security Products (ESP)

Unit 7, Target Park
Shawbank Road
Redditch
Birmingham
B98 8YN
United Kingdom

Tel: +44 (0)1527 515150
Email: info@espuk.com • Web: https://www.espuk.com/


Certificate No 331g-(cl-1) to EN 54-3:2001+ A1: 2002 + A2: 2006 EN 54-5:2000+ A1: 2002 EN 54-7: 2000 + A1: 2002 + A2: 2006 CEA 4021: 2003
Certificate No 331y-(cl-1) to EN 54-5:2000 + A1:2002,EN 54-7:2000+ A1: 2002 + A2: 2006, CEA 4021:2003
Certificate No 331z-(cl-1) to EN 54-3:2001 + A1: 2002 + A2:2006, EN 54-5:2000 +A1:2002, EN 54-7:2000 + A2: 2006, CEA 4021:2003


Product Description LPCB
Ref. No.
MAGDUOSHDSS

MAGDUO Flexipoint Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder & Strobe (45-0048-202-01 Base)

Notes:

1. Meets the requirements of EN 54-5:2000 at the following settings:

     HM1 Class A1 standard temperature rate of rise enhanced

     HM2 Class A1 standard temperature, fixed temperature

     HM3 Class C standard temperature, fixed temperature

2. Meets the requirements of EN 54-7:2000 at the following settings:

     SM1 Standard optical sensitivity with high thermal enhancement

     SM2 Standard optical sensitivity with normal thermal enhancement

3. Meets the requirements of EN 54-3: 2001 at the following tones -

     SP1   Continuous 970Hz

     SP2         Alternating tone at 800/970Hz

     SP3   Sweep Up 800-970Hz

4. The strobe function is not approved to EN 54-23:2010

331g/03
MAGDUOSHD

MAGDUO Flexipoint Conventional Optical Smoke and Heat Multisensor Detector (45-0048-202-01 Base)

Notes:

1. Meets the requirements of EN 54-5:2000 at the following settings:

    HM1 Class A1 standard temperature rate of rise enhanced

    HM2 Class A1 standard temperature, fixed temperature

    HM3 Class C standard temperature, fixed temperature

2. Meets the requirements of EN 54-7:2000 at the following settings:

    SM1 Standard optical sensitivity with high thermal enhancement

    SM2 Standard optical sensitivity with normal thermal enhancement

331y/01
MAGDUOSHDS

MAGDUO Flexipoint Conventional Optical Smoke and Heat Multisensor Detector with Type A Sounder (45-0048-202-01 Base)

Notes:

1. Meets the requirements of EN 54-5:2000 at the following settings:

     HM1 Class A1 standard temperature rate of rise enhanced

     HM2 Class A1 standard temperature, fixed temperature

     HM3 Class C standard temperature, fixed temperature

2. Meets the requirements of EN 54-7:2000 at the following settings:

     SM1 Standard optical sensitivity with high thermal enhancement

     SM2 Standard optical sensitivity with normal thermal enhancement

3. Meets the requirements of EN 54-3 :2001 at the following tones -

     SP1   Continuous 970Hz

     SP2         Alternating tone at 800/970Hz

     SP3   Sweep Up 800-970Hz

331z/01

 

    Bases:

45-0048-202-01 Standard Base
    

 


 