Search by Company Name

Mecon GmbH

Rontgenstrasse 105
Kerpen
50169
Germany

Tel: 0049 2237 6000611 • Fax: 0049 2237 6000620
Web: www.mecon.de


Certificate No 1385a to LPS 1045


Direct Reading Flow Meter

Product

Nominal Pipe Size to BS 1387 (mm)

Nominal Pipe Size to BS 3600 (mm)

Flow Range (l/min)

Connection Type

LPCB
Ref. No.
Turbo-Lux 3

50

50

75 - 375

Groove

1385a/01
Turbo-Lux 3

65

65

150 - 750

Groove

1385a/02
Turbo-Lux 3

80

80

220 - 1100

Groove

1385a/03
Turbo-Lux 3

80

80

300 - 1500

Groove

1385a/04
Turbo-Lux 3

100

100

380 - 1900

Groove

1385a/05
Turbo-Lux 3

100

100

460 - 2300

Groove

1385a/06
Turbo-Lux 3

100

100

600 - 3000

Groove

1385a/07
Turbo-Lux 3

100

100

680 - 3400

Groove

1385a/08
Turbo-Lux 3

150

150

760 - 3800

Groove

1385a/09
Turbo-Lux 3

150

150

1130 - 5650

Groove

1385a/10
Turbo-Lux 3

150

150

1500 - 7500

Groove

1385a/11
Turbo-Lux 3

150

150

1900 - 9500

Groove

1385a/12
Turbo-Lux 3

200

2200 - 11000

Groove

1385a/13
Turbo-Lux 3

200

3000 - 15000

Groove

1385a/14
Turbo-Lux 3

200

3800 - 19000

Groove

1385a/15
Turbo-Lux 3

200

4500 - 22500

Groove

1385a/16

 

Notes:
1)    These meters are provided with demountable measurement tubes (bypass meters) that are connected directly to the flow meter body. After measurements have been taken it is recommended that the measuring tube is either drained by inverting it or removed from the flow meter body. If removed the measurement tube must be drained and stored in the supplied packaging. The open orifice on the flow meter body must be sealed pressure tight with the cap supplied.
2)    These meters have been approved for installation with the measurement tube in the vertical position.
3)    Turbo-Lux 3 meters must be installed and maintained in accordance with manufacturers instruction's 'MECON GmbH 11/2016 OI_FO Turbo-Lux 3'

    

 


 