Certificate No 681ag-(cl-3) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681ag-(cl-1) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681au-(cl-1) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681ad-(cl-2) to EN 54-4:1997 + A1:2002 + A2:2006
Certificate No 681ad-(cl-1) to EN 54-4:1997 + A1:2002 + A2:2006
Certificate No 681an-(cl-1) to EN 54-2:1997 + A1:2006 & EN 54-4:1997 + A1:2002 + A2:2006

Certificate No 681af-(cl-2) to EN 54-2: 1997 + A1: 2006 &EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681ae-(cl-1) to EN 54-2:1997 + A1:2006 & EN 54-4:1997 + A1:2002 + A2:2006
Certificate No 681ac-(cl-2) to EN 54-4:1997 + A1:2002 + A2:2006
Certificate No 681au-(cl-2) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681bb-(cl-1) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006
Certificate No 681bb-(cl-2) to EN 54-2: 1997 + A1: 2006 & EN 54-4: 1997 + A1: 2002 + A2: 2006


Control and indicating equipment

Product Description LPCB
Ref. No.
Pro16xD

4-16 Loops Analogue Addressable Control & Indicating Equipment

Incorporating the following units:

ProR1DS        Profile Reduced User Interface

PFI800        PROFILE Panel Field Interface Board

PSC400        PROFILE Backplane 4 Slots

PPM800        Profile Panel Mounting Frame

PBB801        PROFILE 5A Power Unit [With BAQ140T24 PSU]

Incorporating the following optional modules:

PNI800        PROFILE Network Interface Slot Card

PCS800        PROFILE Ethernet Switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi-Mode

FB800        Fuse board (15 way)

PZ4x        PROFILE 40 Way Zonal Display

PZ8x        PROFILE 80 Way Zonal Display

TUD800        Triggering board for transmission unit

PLX800        PROFILE Loop Expansion Slot Card

PCH800        PROFILE Charger Slot Card

SM3        Serial Interface to FAT

SFK800        PROFILE Swiss Fire Brigade Interface

IOB800        Input/Output Expansion Board

FOM800        Fibre Optic Module

FBI800        Fire Brigade Interface

Incorporating the following mechanical parts:

PXB800        PROFILE Ancillary Expansion Box

PxD        Profile Extension Box For Pro32xD

Pro16xBB - Approved for use with the Pro16xD Control & Indicating Equipment

Incorporating the following units:

PFI800        PROFILE Panel Field Interface Board

PSC400        PROFILE Backplane 4 Slots

PPM800        Profile Panel Mounting Frame

PBB801        PROFILE 5A Power Unit [With BAQ140T24 PSU]

Incorporating the following optional modules:

PNI800        PROFILE Network Interface Slot Card

PCS800        PROFILE Ethernet Switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi-Mode

FB800        Fuse board (15 way)

TUD800        Triggering board for transmission unit

PLX800        PROFILE Loop Expansion Slot Card

PCH800        PROFILE Charger Slot Card

SM3        Serial Interface to FAT

SFK800        PROFILE Swiss Fire Brigade Interface

IOB800        Input/Output Expansion Board

FOM800        Fibre Optic Module

Incorporating the following mechanical parts:

PXB800        PROFILE Ancillary Expansion Box

PxD        Profile Extension Box For Pro32xD

Certified with the following options with requirements from EN54-2:

7.8        Output to fire alarm devices

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1        Outputs to fire controls for fire protection equipment - Output type A

7.10.2        Outputs to fire controls for fire protection equipment - Output type B

7.10.3        Outputs to fire controls for fire protection equipment - Output type C

7.10.4        Fault monitoring of fire controls for fire protection equipment

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

8.9        Output to fault warning routing equipment

9.5        Disablement of addressable points

10        Test condition

11        Output to standardised input/output interface

681ag/06
Pro32xD

4-32 Loops Analogue Addressable Control & Indicating Equipment

Incorporating the following units:

ProR1DS        Profile Reduced User Interface

PFI800        PROFILE Panel Field Interface Board

PSC800        PROFILE Backplane 6 Slots

PPM800        Profile Panel Mounting Frame

PBB801        PROFILE 5A Power Unit [With BAQ140T24 PSU]

Incorporating the following optional modules:

PNI800        PROFILE Network Interface Slot Card

PCS800        PROFILE Ethernet Switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi-Mode

FB800        Fuse board (15 way)

PZ4x        PROFILE 40 Way Zonal Display

PZ8x        PROFILE 80 Way Zonal Display

TUD800        Triggering board for transmission unit

PLX800        PROFILE Loop Expansion Slot Card

PCH800        PROFILE Charger Slot Card

SM3        Serial Interface to FAT

SFK800        PROFILE Swiss Fire Brigade Interface

IOB800        Input/Output Expansion Board

FOM800        Fibre Optic Module

FBI800        Fire Brigade Interface

Incorporating the following mechanical parts:

PXB800        PROFILE Ancillary Expansion Box

PxD        Profile Extension Box For Pro32xD


Pro32xBB  - Approved for use with the Pro32xD Control & Indicating Equipment

Incorporating the following units:

PFI800        PROFILE Panel Field Interface Board

PSC800        PROFILE Backplane 6 Slots

PPM800        Profile Panel Mounting Frame

PBB801        PROFILE 5A Power Unit [With BAQ140T24 PSU]

Incorporating the following optional modules:

PNI800        PROFILE Network Interface Slot Card

PCS800        PROFILE Ethernet Switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi-Mode

FB800        Fuse board (15 way)

PZ4x        PROFILE 40 Way Zonal Display

PZ8x        PROFILE 80 Way Zonal Display

TUD800        Triggering board for transmission unit

PLX800        PROFILE Loop Expansion Slot Card

PCH800        PROFILE Charger Slot Card

SM3        Serial Interface to FAT

SFK800        PROFILE Swiss Fire Brigade Interface

IOB800        Input/Output Expansion Board

FOM800        Fibre Optic Module

Incorporating the following mechanical parts:

PXB800        PROFILE Ancillary Expansion Box

PxD        Profile Extension Box For Pro32xD

Certified with the following options with requirements from EN54-2:

7.8        Output to fire alarm devices

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1        Outputs to fire controls for fire protection equipment - Output type A

7.10.2        Outputs to fire controls for fire protection equipment - Output type B

7.10.3        Outputs to fire controls for fire protection equipment - Output type C

7.10.4        Fault monitoring of fire controls for fire protection equipment

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal - Type A

7.12.2        Dependencies on more than one alarm signal - Type B

7.12.3        Dependencies on more than one alarm signal - Type C

7.13        Alarm counter

8.3        Fault signals from points

8.9        Output to fault warning routing equipment

9.5        Disablement of addressable points

10        Test condition

11        Output to standardised input/output interface

681ag/07
Pro215S

1-2 Loops Analogue Addressable Control & Indicating Equipment, Shallow Housing

Incorporating the following units:

PR1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PCS800        Profile Ethernet switch

FB800                Fuse Board

TUD800                Triggering Board for transmission unit

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12170        2x17Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/01
Pro215D

1-2 Loops Analogue Addressable Control & Indicating Equipment, Deep Housing

Incorporating the following units:

PR1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/02
Pro815D

4-8 Loops Analogue Addressable Control & Indicating Equipment

Incorporating the following units:

PR1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PLX800                Profile Loop Expansion Slot Card

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/04
Pro885D

4-8 Loops Analogue Addressable Control & Indicating Equipment

Incorporating the following units:

PR1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PZ8x                80way Zonal Display

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PLX800                Profile Loop Expansion Slot Card

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

PZ4x                40way Zonal Display

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/05
Pro815D-CH

4-8 Loops Analogue Addressable Control & Indicating Equipment

Incorporating the following units:

PR1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

SFK800                Swiss Fire Brigade Interface

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PLX800                Profile Loop Expansion Slot Card

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12260        2x26Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/06
557.200.530

PSU A17 Addressable 17Ah Power Supply Unit

Notes:

1)      The unit is not intended to supply power to Fire Alarm Control Panels

2)     The maximum lead length for the fault output connection is 3m

681ad/01
557.200.531

PSU A38 Addressable 38Ah Power Supply Unit

Notes:

1)      The unit is not intended to supply power to Fire Alarm Control Panels

2)      The maximum lead length for the fault output connection is 3m

681ad/02
557.200.732

PSU A17 Addressable 17Ah Power Supply Unit

Notes:

1)      The unit is not intended to supply power to Fire Alarm Control Panels

2)      The maximum lead length for the fault output connection is 3m

681ad/01
557.200.733

PSU A38 Addressable 38Ah Power Supply Unit

Notes:

1)      The unit is not intended to supply power to Fire Alarm Control Panels

2)      The maximum lead length for the fault output connection is 3m

681ad/02
MX4000

2-8 loop Analogue Addressable Control and Indicating Equipment

Notes:

1)The following product variants are approved -

Finished goods No.   557.200.003, MX4000 1-4 loop CIE, shallow housing

Finished goods No.   557.200.005, MX-BBX battery box, shallow housing

Finished goods No.   557.200.004, MX4000 1-8 loop CIE, deep housing

Finished goods No.   557.200.006, MX-DPBX battery box, deep housing (door                        access)

Finished goods No.   557.200.016, MX-DPBX battery box, deep housing (plain                        cover access)

Finished goods No.   557.200.009, MX4000 1-4 loop, flush housing

Finished goods No.   557.200.019, MX-BBX-F battery box, flush housing        

Incorporating as modular units:

OCM800          Operator Control Module

ODM800          Operator Display Module

CPU800          Main CPU module

FIM802          Field Interface Module "drives 1 or 2 loops"

PSU830          Power Supply Module

and as optional modular units:

XLM800          Expansion Loop Module  "drives 1 or 2 additional loops"

ANN840          40 + 40 LED Annunciator module

ANN880         80 LED Annunciator module

COM820          20 way Status Command Module

MPM800          Multi-Purpose Interface Module

IOB800          Input/Output Expansion Board

FB800            Fuse Board        

Certified with the following options with requirements from EN 54 Part 2:

7.8        Output to fire alarm devices

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1        Outputs to fire protection equipment (Type A)

7.10.2        Outputs to fire protection equipment (Type B)

7.10.3        Outputs to fire protection equipment (Type C)

7.10.4        Fault monitoring of fire protection equipment

7.11        Delays to outputs

7.12.1        Dependencies on more than one alarm signal (Type A dependency)

7.12.2        Dependencies on more than one alarm signal (Type B  dependency)

7.12.3        Dependencies on more than one alarm signal (Type C dependency)

7.13        Alarm counter

8.3        Fault signals from points

8.9         Output to fault warning routing equipment

9.5        Disablement of addressable points

10        Test condition

11         Standardized input/output interface  

681an/01
MXR

Repeater panel is approved for use with the MX4000 Control and Indicating

Notes:

1)The following product variants are approved -

Finished goods No.   557.200.013, MXR-PSU repeater

Finished goods No.   557.200.018, MXR-PSU-F repeater flush housing

Finished goods No.   557.200.012, MXR repeater

Finished goods No.   557.200.017, MXR-F repeater flush housing

Incorporating as modular units:

OCM800 (Operator Control Module)

ODM800 (Operator Display Module)

PSU830 (Power Supply Module)

and as optional modular units:

ANN840 (40 + 40 LED Annunciator)

ANN880 (80 LED Annunciator)

MPM800 (Multi Purpose Interface Module)

IOB800 (Input/Output Expansion Board)

FB800 (Fuse Board)

681an/R01
508.031.701

FIRECLASS Duo-CEL, 1 Zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605501, 1 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

681af/01
508.031.702

FIRECLASS Duo-CEL, 2 Zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605502, 2 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

681af/02
508.031.703

FIRECLASS Duo-CEL, 4 zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605503,  4 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

681af/03
508.031.005.xx

MZXC 4 zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605503,  4 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

Note:         xx indicates the language option

        Blank = Blank facia overlay

681af/03
508.031.704

FIRECLASS Duo-CEL, 8 Zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605504, 8 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

681af/04
508.031.006.xx

MZXC 8 Zone Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605504, 8 Zone Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

Note:         xx indicates the language option

        Blank = Blank facia overlay

681af/04
508.031.705

FIRECLASS Duo-CEL, Fire Alarm Repeater (Mains)

Incorporating as modular units:

C1694 - 2605505, Repeater Motherboard

BAQ-35T24 Power Supply

Note: Compatible with 508.031.703 & 508.031.704 panels only

681af/R01
508.031.016.xx

Fire Alarm Repeater (Mains)

Incorporating as modular units:

C1694 - 2605505, Repeater Motherboard

BAQ-35T24 Power Supply

Notes:         

1)  Compatible with 508.031.005.xx & 508.031.006.xx panels.

2)  Also compatible with 508.031.005.xx & 508.031.006.xx twin wire conventional panels on certificate 018r.

3)  xx indicates the language option

        Blank = Blank facia overlay

        EG = English facia overlay

681af/R01
508.031.706

FIRECLASS Duo-CEL, Fire Alarm Repeater (24 VDC).

Incorporating as a modular unit:

C1694 - 2605506, Repeater Motherboard        

Note: Compatible with 508.031.703 & 508.031.704 panels only.

681af/R02
508.031.004.xx

MZXC 2 Zone, Twin Wire Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605508, 2 Zone Twin Wire Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

                

Note:         xx indicates the language option

        EG = English facia overlay

681ae/01
508.031.005.xx

MZXC 4 Zone, Twin Wire Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605509, 4 Zone Twin Wire Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

                

Note:         xx indicates the language option

        EG = English facia overlay

681ae/02
508.031.006.xx

MZXC 8 Zone Twin Wire Conventional Control and Indicating Equipment

Incorporating as modular units:

C1694 - 2605510, 8 Zone Twin Wire Motherboard

BAQ-35T24 Power Supply

Certified with the following options from EN 54-2:

7.8         Output to fire alarm devices

7.9.1         Output to fire alarm routing equipment

7.12.1        Dependencies on more than one alarm signal - Type A

7.13        Alarm counter

10        Test condition

Note:         xx indicates the language option

        EG = English facia overlay

681ae/03
PSU A17

Addressable 17Ah Power Supply Unit

Notes:

1) The unit is not intended to supply power to

    Fire Alarm Control Panels

2) The maximum lead length for the fault output connection is 3m

681ac/01
PSU A38

Addressable 38Ah Power Supply Unit

Notes:

1) The unit is not intended to supply power to

    Fire Alarm Control Panels

2) The maximum lead length for the fault output connection is 3m

681ac/02
FC702S

1-2 Loops Analogue Addressable Control & Indicating Equipment, Shallow Housing (557.200.949)

Incorporating the following units:

FC1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PCS800        Profile Ethernet switch

FB800                Fuse Board

TUD800                Triggering Board for transmission unit

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12170        2x17Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/01
FC702D

1-2 Loops Analogue Addressable Control & Indicating Equipment, Deep Housing (557.200.950)

Incorporating the following units:

FC1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/02
FC718D

4-8 Loops Analogue Addressable Control & Indicating Equipment (557.200.952)

Incorporating the following units:

FC1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PLX800                Profile Loop Expansion Slot Card

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/04
FC708D

4-8 Loops Analogue Addressable Control & Indicating Equipment (557.200.951)

Incorporating the following units:

FC1DS                Profile User Interface

PFI800                Profile Panel Field Interface Board

PSC400        Profile Backplane 4 Slots

PZ8x                80way Zonal Display

PSU (BAQ140T24) Power Supply Unit        

        

Incorporating the following optional units:

ProR1DS        Profile Reduced User Interface

PNI800                Profile Network Interface Slot Card

FOM800        Fibre Optic Module

PLX800                Profile Loop Expansion Slot Card

PCS800        Profile Ethernet switch

POS800-S        Fibre Optic Switch Single Mode

POS800-M        Fibre Optic Switch Multi Mode

FB800                Fuse Board

CD5.241        DC-DC Converter (24V input and 24V output )

TUD800                Triggering Board for transmission unit

SM3                Serial Interface to FAT

IOB800                Input/ Output Expansion Board

PZ4x                40way Zonal Display

FBI800                Fire Brigade Interface

PS-12380        2x38Ah Batteries

Certified with the following options with requirements from EN54-2:

7.8 Output to fire alarm device(s)

7.9.1 Output to fire alarm routing equipment

7.9.2 Alarm confirmation input from fire alarm routing equipment

7.10.1 Output type A

7.10.2 Output type B

7.10.3 Output type C

7.10.4 Fault monitoring of fire protection equipment

7.11 Delays to outputs

7.12.1 Dependencies on more than one alarm signal - Type A

7.12.2 Dependencies on more than one alarm signal - Type B

7.12.3 Dependencies on more than one alarm signal - Type C

7.13 Alarm counter

8.3 Fault signals from points

8.9 Output to fault warning routing equipment

9.5 Disablement of each address point

10 Test condition

11 Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm systems requirements of EN54-13

681au/05
Pro215S Lite

1-2 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing
Zettler Profile Lite (557.202.910)

        Zettler Profile Lite Red Housing (557.202.910.R)

Incorporating the following modules:

PFI801                  Field Interface

CUI                       Colour User Interface

BAW75T24        2.5 A PSU

Incorporating the following optional units:

PNI800                 Network Interface

FBI800                 Fire Brigade Interface

FB800                  Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2    Dependencies on more than one alarm signal -Type B

7.12.3    Dependencies on more than one alarm signal -Type C

7.13       Alarm counter

8.3         Fault signals from points

8.9         Output to fault warning routing equipment

9.5         Disablement of each address point

10          Test condition

11          Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

661bb/01
Pro415SLite

2-4 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        Zettler Profile Lite (557.202.911),

        Zettler Profile Lite Red Housing (557.202.910.R)

Incorporating the following modules:

PFI800        Field Interface

CUI                Colour User Interface

BAQ140T24        5 A PSU

Incorporating the following optional units:

PNI800                 Panel Network Interface

FBI800                  Fire Brigade Interface

FB800                Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10. 1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/02
Pro415D Lite

2-4 Loop Analogue Addressable Control and Indicating Equipment, Deep Housing

        Zettler Profile Lite (557.202.916)

Incorporating the following modules:

PFI800                Field Interface

CUI                 Colour User Interface

BAQ140T24        5 A PSU

Incorporating the following optional units:        

PNI800           Panel Network Interface

FBI800         Fire Brigade Interface

FB800        Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10. 1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/03
Pro215S-CH Lite Swiss

1-2 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        Zettler Profile Lite (557.202.912)

Incorporating the following modules:

PFI801              Field Interface

CUI                 Colour User Interface

SFK800               Swiss Interface                  

BAW75T24         2.5 A PSU

Incorporating the following optional units:

PNI800               Panel Network Interface

FBI800               Fire Brigade Interface

FB800                Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10. 1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/04
Pro415S-CH Lite Swiss

2-4 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        Zettler Profile Lite Swiss (557.202.913)

Incorporating the following modules:

PFI800              Field Interface

CUI           Colour User Interface

SFK800        Swiss Interface                                  

BAQ140T24        5 A PSU

Incorporating the following optional units:

PNI800                Panel Network Interface

FBI800        Fire Brigade Interface

FB800        Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10. 1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/05
P32AR LT

32 Zone AC Repeater, Zettler (557.202.914)

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

PMM800        Power Monitor Module

BAW75T24        Power Supply Unit, 2.5 A

Note: Approved for use with the Pro215S Lite, Pro415S Lite, Pro415D Lite,
P32AR LT, P32DR LT, P32AR-CH LT and P32DR-CH LT

681bb/R01
P32DR LT

32 Zone DC Repeater, Zettler (557.202.915)

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

Note: Approved for use with the Pro215S Lite, Pro415S Lite, Pro415D Lite,
P32AR LT, P32DR LT, P32AR-CH LT and P32DR-CH LT

681bb/R02
P32AR-CH LT

32 Zone AC Repeater, Zettler Swiss (557.202.922)

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

PMM800        Power Monitor Module

SFK800            Swiss Interface

BAW75T24        Power Supply Unit, 2.5


Note: Approved for use with the Pro215S Lite Swiss and Pro415S Lite Swiss

681bb/R03
P32DR-CH LT

32 Zone DC Repeater, Zettler Swiss (557.202.923)

Incorporating the following modules:

CUI-R         Repeater Colour User Interface

SFK800        Swiss Interface

Note: Approved for use with the Pro215S Lite Swiss and Pro415S Lite Swiss

681bb/R04
FC602S

1-2 Loop Analogue Addressable Control and Indicating Equipment, Shallow

Housing

        FireClass (557.200.650)

Incorporating the following modules:

PFI801-FC        Field Interface

CUI                       Colour User Interface

BAW75T24           2.5 A PSU

Incorporating the following optional modules:

PNI800        Panel Network Interface

FB800            Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3            Dependencies on more than one alarm signal -Type C

7.13       Alarm counter

8.3         Fault signals from points

8.9         Output to fault warning routing equipment

9.5         Disablement of each address point

10          Test condition

11          Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection

and alarm system requirements of EN54-13.

681bb/01
FC604S

2-4 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        FireClass (557.200.651)

Incorporating the following modules:

PFI801-FC        Field Interface

CUI                       Colour User Interface

BAQ140T24         5 A PSU

Incorporating the following optional modules:

PNI800        Profile Network Interface

FB800                 Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/02
FC602S Lite Scandanavian

1-2 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        FireClass Scandinavian (557.200.652)

Incorporating the following modules:

PFI801-FC             Field Interface

CUI                       Colour User Interface

BAW75T24            2.5 A PSU

Incorporating the following optional units:

PNI800                 Panel Network Interface

FB800                  Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3            Dependencies on more than one alarm signal -Type C

7.13               Alarm counter

8.3                 Fault signals from points

8.9                 Output to fault warning routing equipment

9.5                 Disablement of each address point

10                  Test condition

11                  Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/06
FC604S Lite Scandanavian

2-4 Loop Analogue Addressable Control and Indicating Equipment, Shallow Housing

        FireClass Scandinavian (557.200.653)

Incorporating the following Modules:

PFI800-FC        Field Interface

CUI        Colour User Interface

BAQ140T24        5 A PSU

Incorporating the following optional units:

PNI800        Panel Network Interface

FB800        Fuse Board

Certified with the following options with requirements from EN54-2:

7.8           Output to fire alarm device(s)

7.9.1        Output to fire alarm routing equipment

7.9.2        Alarm confirmation input from fire alarm routing equipment

7.10.1      Output to fire protection equipment- Output type A

7.10.2      Output to fire protection equipment- Output type B

7.10.3      Output to fire protection equipment- Output type C

7.10.4      Fault monitoring of fire protection equipment  

7.11         Delays to outputs

7.12.1      Dependencies on more than one alarm signal- Type A

7.12.2      Dependencies on more than one alarm signal -Type B

7.12.3      Dependencies on more than one alarm signal -Type C

7.13         Alarm counter

8.3           Fault signals from points

8.9           Output to fault warning routing equipment

9.5           Disablement of each address point

10            Test condition

11            Output to standardised input/output interface

Notes:

1. Scope of approval does not include the operation of the network functionality

2. This product approval does not constitute compliance with the fire detection and alarm system requirements of EN54-13.

681bb/07
FC32AR

32 Zone AC Repeater, FireClass 557.202.914

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

PMM800        Power Monitor Module

BAW75T24        Power Supply Unit, 2.5 A

Note: Approved for use with the FC602S, FC604S, FC602S Lite Scandinavian and FC604S Lite Scandinavian

681bb/R01
FC32DR

32 Zone DC Repeater, FireClass 557.202.915

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

Note: Approved for use with the FC602S, FC604S, FC602S Lite Scandinavian and

FC604S Lite Scandinavian

681bb/R02
FC32AR-S

32 Zone AC Repeater, FireClass Scandinavian (557.200.656)

Incorporating the following modules:

CUI-R        Repeater Colour User Interface

PMM800        Power Monitor Module

BAW75T24        Power Supply Unit, 2.5 A

Note: Approved for use with the FC602S Lite Scandinavian and FC604S Lite Scandinavian

681bb/R05
FC32DR-S

32 Zone DC Repeater, FireClass Scandinavian (557.200.657)


Incorporating the following modules:

CUI-R        Repeater Colour User Interface

Note: Approved for use with the FC602S Lite Scandinavian and FC604S Lite Scandinavian

681bb/R06

 

 


 

To read the Red Book section introduction click here.

 