Search by Certificate Number

Alfanar

3rd Industrial Area
New AL Kharj Road
PO Box 564
Riyadh 11383
Kingdom of Saudi Arabia

Tel: +966 92000 6111 • Fax: +966 11275 6699
Email: ahmed.attia@alfanar.com • Web: www.alfanar.com


Certificate No 1343a to BS 6387:2013, IEC 60331-21:1999, IEC 61034-2:2005 + A1:2013, EN 60754-1:2014, EN 60754-2:2014 and EN 60332-3-24:2009


FIREPROOF

Product

Nominal

csa of

conductor

(mm2)

Core Construction

BS 6387

IEC 60331-21

EN 60754-1

EN 60754-2

IEC 61034-2

EN 60332-3-24

LPCB
Ref. No.
Alfanar FIREPROOF Wires

1.5

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

2.5

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

4.0

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

6.0

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

10

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

16

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

25

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

35

One

CWZ

Complies

<0.5% HCI

Complies

>60%

Complies

1343a/01
Alfanar FIREPROOF Wires

50

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

70

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

95

One

CWZ

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

120

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

150

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

185

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

240

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

300

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

400

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

500

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01
Alfanar FIREPROOF Wires

630

One

C

Complies

<0.5% HCI

Complies

>60%

-

1343a/01

 

Uo/U 450/750V                                                                
  Notes:  
1.                                                                 Stranded conductor only
2.                                                                 In achieving a weighted average of pH greater than 4.3 and a weighted average of conductivity less than 10µS/mm on the constituent materials when tested in accordance with EN 60754-1:2014, the FIREPROOF cables listed also met the requirements of EN 60754-2:2014.
3.                                                                 The Alfanar FIREPROOF Wires cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950˚C for a duration of 90mins at a voltage rating of 450V.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page