Search by Certificate Number

Hochiki Europe (UK) Limited

Grosvenor Road
Gillingham Business Park
Gillingham
Kent
ME8 0SA
United Kingdom

Tel: +44 (0)1634 260133 • Fax: +44 (0)1634 260132
Email: info@hochikieurope.com • Web: www.hochikieurope.com


Certificate No 164s to EN 54-23: 2010
Certificate No 164t to EN 54-3:2001 + A1:2002 + A2:2006 and EN 54-23:2010




Product Description LPCB
Ref. No.
CHQ-CB(RED)/WL-15

Addressable Ceiling VAD (White LED)

(YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-SB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.2-7.5, O-2.2-5, O-2.54-1.36

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-11.4, O-3.6-11.17, O-3.88-4

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-15.1, O-4.7-15, O-4.89-9.68, O-5-5.4

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.54-5.3, O-1.7-5

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.6-8

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.6-11.3, O-3.7-4.27

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/01
CHQ-CB(WHT)/WL-15

Addressable Ceiling VAD (White LED)

(YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-SB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.2-7.5, O-2.2-5, O-2.54-1.36

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-11.4, O-3.6-11.17, O-3.88-4

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-15.1, O-4.7-15, O-4.89-9.68, O-5-5.4

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.54-5.3, O-1.7-5

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.6-8

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.6-11.3, O-3.7-4.27

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/02
CHQ-CB(RED)/WL

Addressable Ceiling VAD (White LED)

(YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS,YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3 -6.5, O-1.18-7.1, O-3.26-3.76

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.9, O-3.4-7.5, O-3.72-6.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-4.3-10, O-4.6-5.42

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.2-5.2

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-5.9, O-2.75-5.1

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.5, O-3.2-7.5, O-3.5-6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/03
CHQ-CB(WHT)/WL

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3 -6.5, O-1.18-7.1, O-3.26-3.76

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.9, O-3.4-7.5, O-3.72-6.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-4.3-10, O-4.6-5.42

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.2-5.2

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-5.9, O-2.75-5.1

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.5, O-3.2-7.5, O-3.5-6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/04
CHQ-CB(RED)/RL

Addressable Ceiling VAD (Red LED)

(YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-SB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.64-6.85, O-2.79-3.3

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-8.6, O-3.5-6.5, O-3.89-1.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.91-10, O-4.12-7.8, O-4.3-4.5

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.05-3.8

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-6.4, O-2.5-4.99, O-2.7-3

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-5.9, O-2.97-7.6, O-3.26-3.6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/05
CHQ-CB(WHT)/RL

Addressable Ceiling VAD (Red LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.64-6.85, O-2.79-3.3

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-8.6, O-3.5-6.5, O-3.89-1.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.91-10, O-4.12-7.8, O-4.3-4.5

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.05-3.8

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-6.4, O-2.5-4.99, O-2.7-3

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-5.9, O-2.97-7.6, O-3.26-3.6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/06
CHQ-CB/WL-15

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.2-7.5, O-2.2-5, O-2.54-1.36

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-11.4, O-3.6-11.17, O-3.88-4

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-15.1, O-4.7-15, O-4.89-9.68, O-5-5.4

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.54-5.3, O-1.7-5

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.6-8

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.6-11.3, O-3.7-4.27

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/07
CHQ-CB/WL

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3 -6.5, O-1.18-7.1, O-3.26-3.76

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.9, O-3.4-7.5, O-3.72-6.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-4.3-10, O-4.6-5.42

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.2-5.2

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-5.9, O-2.75-5.1

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.5, O-3.2-7.5, O-3.5-6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/08
CHQ-CB/RL

Addressable Ceiling VAD (Red LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.64-6.85, O-2.79-3.3

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-8.6, O-3.5-6.5, O-3.89-1.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.91-10, O-4.12-7.8, O-4.3-4.5

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.05-3.8

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-6.4, O-2.5-4.99, O-2.7-3

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-5.9, O-2.97-7.6, O-3.26-3.6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/09
CHQ-CB(RED)/WL-15-HFP

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.2-7.5, O-2.2-5, O-2.54-1.36

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-11.4, O-3.6-11.17, O-3.88-4

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-15.1, O-4.7-15, O-4.89-9.68, O-5-5.4

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.54-5.3, O-1.7-5

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.6-8

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.6-11.3, O-3.7-4.27

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/01
CHQ-CB(WHT)/WL-15-HFP

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

        1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.2-7.5, O-2.2-5, O-2.54-1.36

        - LOL 0
- Flash rate 0.5Hz

        - Synchronization

        2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-11.4, O-3.6-11.17, O-3.88-4

        - LOL 1
- Flash rate 0.5Hz

        - Synchronization

        3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-15.1, O-4.7-15, O-4.89-9.68, O-5-5.4

        - LOL 2
- Flash rate 0.5Hz

        - Synchronization

        4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-1.54-5.3, O-1.7-5

        - LOL 0
- Flash rate 1Hz

        - Synchronization

        5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.6-8

        - LOL 1
- Flash rate 1Hz

        - Synchronization

        6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.6-11.3, O-3.7-4.27

        - LOL 2
- Flash rate 1Hz

        - Synchronization

        7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/02
CHQ-CB(RED)/WL-HFP

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3 -6.5, O-1.18-7.1, O-3.26-3.76

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.9, O-3.4-7.5, O-3.72-6.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-4.3-10, O-4.6-5.42

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.2-5.2

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-5.9, O-2.75-5.1

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of
EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.5, O-3.2-7.5, O-3.5-6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/03
CHQ-CB(WHT)/WL-HFP

Addressable Ceiling VAD (White LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3 -6.5, O-1.18-7.1, O-3.26-3.76

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.9, O-3.4-7.5, O-3.72-6.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-4.3-10, O-4.6-5.42

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.2-5.2

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-5.9, O-2.75-5.1

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-7.5, O-3.2-7.5, O-3.5-6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/04
CHQ-CB(RED)/RL-HFP

Addressable Ceiling VAD (Red LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.64-6.85, O-2.79-3.3

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-8.6, O-3.5-6.5, O-3.89-1.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.91-10, O-4.12-7.8, O-4.3-4.5

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.05-3.8

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-6.4, O-2.5-4.99, O-2.7-3

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-5.9, O-2.97-7.6, O-3.26-3.6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/05
CHQ-CB(WHT)/RL-HFP

Addressable Ceiling VAD (Red LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-1.5, O-2.64-6.85, O-2.79-3.3

- LOL 0
- Flash rate 0.5Hz

- Synchronization

2. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-8.6, O-3.5-6.5, O-3.89-1.9

- LOL 1
- Flash rate 0.5Hz

- Synchronization

3. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-10, O-3.91-10, O-4.12-7.8, O-4.3-4.5

- LOL 2
- Flash rate 0.5Hz

- Synchronization

4. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following category:
- Light Coverage Distance O-2.05-3.8

- LOL 0
- Flash rate 1Hz

- Synchronization

5. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance O-2.4-6.4, O-2.5-4.99, O-2.7-3

- LOL 1
- Flash rate 1Hz

- Synchronization

6. The ceiling mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
- Light Coverage Distance C-3-5.9, O-2.97-7.6, O-3.26-3.6

- LOL 2
- Flash rate 1Hz

- Synchronization

7. Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit

164s/06
CHQ-WSB2/WL

Addressable Type A/B Wall Sounder (White LED) Beacon      

(YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT) bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/01
CHQ-WSB2/RL

Addressable Type A/B Wall Sounder (Red LED) Beacon      

(YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT) bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/02
CHQ-WSB2(WHT)/WL

Addressable Type A/B Wall Sounder (White LED) Beacon

(YBO-R/3(WHT) and YBN-R/3(WHT)-SCI bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/03
CHQ-WSB2(WHT)/RL

Addressable Type A/B Wall Sounder (Red LED) Beacon      

(YBO-R/3(WHT) and YBN-R/3(WHT)-SCI bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/04
YBO-BSB2/WL

Analogue Addressable Type A Base Sounder (White LED) Beacon

(YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT) bases)

Notes:        

  1. The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/05
YBO-BSB2/RL

Analogue Addressable Type A Base Sounder (Red LED) Beacon

(YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT) bases)

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under  approved tones

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/06
YBO-BSB2(WHT)/WL

Analogue Addressable Type A Base Sounder (White LED) Beacon

(YBO-R/3(WHT), YBN-R/3(WHT)-SCI Bases)

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under  approved tones

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/07
YBO-BSB2(WHT)/RL

Analogue Addressable Type A Base Sounder (Red LED) Beacon

YBO-R/3(WHT) & YBN-R/3(WHT)-SCI Bases

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under  approved tones

Approved tones:          
                1 - 925 Hz : 250 ms / 628 Hz : 250 ms

          2 - 925 Hz Continuous

          3 - 628 Hz Continuous

          4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

          5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

          6 - 925 Hz : 150 ms / Off : 600 ms

          7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

          8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

          9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

        10 - 970 Hz : 500 ms / Off : 500 ms

        11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

        12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

        13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

        14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

        15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

        16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

        17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

        18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

        19 - 800 Hz : 250 ms / 970 Hz : 250 ms

        20 - 2850 Hz Continuous

        21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

        22 - 800 Hz : 500 ms / 970 Hz : 500 ms

        23 - 2850 Hz : 500 ms / Off : 500 ms

        24 - 925 Hz : 250 ms / Off : 1000 ms

        25 - 970 Hz Continuous

        26 - 660 Hz : 1800 ms / Off: 1800 ms

        27 - 660 Hz : 6500 ms / Off : 13000 ms

        28 - 660 Hz Continuous

        29 - 554 Hz : 500 ms / 440 Hz : 500 ms

        30 - 660 Hz : 500 ms / Off : 500 ms

        31 - 2850 Hz : 150 ms / Off : 100 ms

        32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

        33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

        34 - 988 Hz : 250 ms / 645 Hz : 250 ms

        35 - 510 Hz : 250 ms / 610 Hz : 250 ms

        36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

        37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

        38 - 845 Hz Continuous

        39 - 970 Hz : 1000 ms / Off : 1000 ms

        40 - 800 Hz : 150 ms / 970 Hz : 150 ms

        41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

        42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

        43 - 2850 Hz : 1000 ms / Off : 1000 ms

        44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

        45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

        46 - 440 Hz : 600 ms / Off : 600 ms

        47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

        48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

        49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

        50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

        51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/08
CHQ-WSB2/WL-HFP

Addressable Type A/B Wall Sounder (White LED) Beacon      

(YBO-R/3(RED) and YBO-R/SCI(RED) bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/01
CHQ-WSB2/RL-HFP

Addressable Type A/B Wall Sounder (Red LED) Beacon      

(YBO-R/3(RED) and  YBO-R/SCI(RED) bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/02
CHQ-WSB2(WHT)/WL-HFP

Addressable Type A/B Wall Sounder (White LED) Beacon

(YBO-R/3(WHT) and YBN-R/3(WHT)-SCI bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/03
CHQ-WSB2(WHT)/RL-HFP

Addressable Type A/B Wall Sounder (Red LED) Beacon      

(YBO-R/3(WHT), YBN-R/3(WHT)-SCI Bases)

Notes:        

1.   The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones.

3.   The VAD is Type A when used with any of the above bases and Type B when used with a WS2-WPK weatherproofing kit

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/04
YBO-BSB2(WHT)/WL-HFP

Analogue Addressable Type A Base Sounder (White LED) Beacon

(YBO-R/3(WHT), YBN-R/3(WHT)-SCI Bases)

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under  approved tones

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/07
YBO-BSB2(WHT)/RL-HFP

Analogue Addressable Type A Base Sounder (Red LED) Beacon

(YBO-R/3(WHT), YBN-R/3(WHT)-SCI Bases)

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under  approved tones

Approved tones:

1 - 925 Hz : 250 ms / 628 Hz : 250 ms

2 - 925 Hz Continuous

3 - 628 Hz Continuous

4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms

5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms

6 - 925 Hz : 150 ms / Off : 600 ms

7 - 670 Hz : 250 ms  / 845 Hz : 370 ms

8 - Whoop 500 Hz - 1200 Hz :  3000 ms / Off : 500 ms

9 - 1200 Hz : 500 ms / 500 Hz : 500 ms

10 - 970 Hz : 500 ms / Off : 500 ms

11 - Sweep 800 Hz - 970 Hz over 140 ms  (7 Hz)

12 - Sweep 800 Hz - 970 Hz over 1000 ms  (1 Hz)

13 - Sweep 800 Hz - 970 Hz over 20 ms  (50 Hz)

14 - Sweep 2400 Hz - 2850 Hz over 140 ms  (7 Hz)

15 - Sweep 2400 Hz - 2850 Hz over 1000 ms  (1 Hz)

16 - Sweep 300 Hz - 1200 Hz over 1000 ms  (1 Hz)

17 - ISO8201 : 970 Hz : 500 ms / Off : 500 ms

18 - ISO8201 : 2850 Hz : 500 ms / Off : 500 ms

19 - 800 Hz : 250 ms / 970 Hz : 250 ms

20 - 2850 Hz Continuous

21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms

22 - 800 Hz : 500 ms / 970 Hz : 500 ms

23 - 2850 Hz : 500 ms / Off : 500 ms

24 - 925 Hz : 250 ms / Off : 1000 ms

25 - 970 Hz Continuous

26 - 660 Hz : 1800 ms / Off: 1800 ms

27 - 660 Hz : 6500 ms / Off : 13000 ms

28 - 660 Hz Continuous

29 - 554 Hz : 500 ms / 440 Hz : 500 ms

30 - 660 Hz : 500 ms / Off : 500 ms

31 - 2850 Hz : 150 ms / Off : 100 ms

32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz)

33 - Sweep 800 Hz - 970 Hz over 500 ms  (2 Hz)

34 - 988 Hz : 250 ms / 645 Hz : 250 ms

35 - 510 Hz : 250 ms / 610 Hz : 250 ms

36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz)

37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz)

38 - 845 Hz Continuous

39 - 970 Hz : 1000 ms / Off : 1000 ms

40 - 800 Hz : 150 ms / 970 Hz : 150 ms

41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz)

42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz)

43 - 2850 Hz : 1000 ms / Off : 1000 ms

44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms

45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms

46 - 440 Hz : 600 ms / Off : 600 ms

47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms

48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms

49 - ISO8201 : Sweep 300 Hz - 1200 Hz  : 500 ms / Off : 500 ms

50 - ISO8201 : Sweep 1200 Hz - 300 Hz  : 500 ms /  Off : 500 ms

51 - Whoop 500-1200 3500 ms / Off 500 ms

164t/08
CHQ-WB/WL

Intelligent Analogue Addressable Type A Wall VAD (White LED)
(YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-7

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-1

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 1Hz

        - Synchronization
6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/10
CHQ-WB(WHT)/WL

Intelligent Analogue Addressable Type A Wall VAD (White LED)-White Body (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-7

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-1

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 1Hz

        - Synchronization
6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/11
CHQ-WB(RED)/WL

Intelligent Analogue Addressable Type A Wall VAD (White LED)-Red Body (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-7

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-1

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 1Hz

        - Synchronization
6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/12
CHQ-WB/RL

Intelligent Analogue Addressable Type A Wall VAD (Red LED) (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance O-2-3*
        * Light coverage defined as per standard W-rating but with a maximum height of 2m(rectangular)

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.7-1.07

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-4

        - LOL 2
        - Flash rate 1Hz

        - Synchronization

6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/13
CHQ-WB(WHT)/RL

Intelligent Analogue Addressable Type A Wall VAD (Red LED)-White Body (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance O-2-3*
        * Light coverage defined as per standard W-rating but with a maximum height of 2m(rectangular)

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.7-1.07

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-4

        - LOL 2
        - Flash rate 1Hz

        - Synchronization

6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/14
CHQ-WB(RED)/RL

Intelligent Analogue Addressable Type A Wall VAD (Red LED)-Red Body (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance O-2-3*
        * Light coverage defined as per standard W-rating but with a maximum height of 2m(rectangular)

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.7-1.07

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-4

        - LOL 2
        - Flash rate 1Hz

        - Synchronization

6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/15
CHQ-WB(WHT)/WL-HFP

Intelligent Analogue Addressable Type A Wall VAD (White LED) - White Body  (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-7

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-1

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 1Hz

        - Synchronization
6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/11
CHQ-WB(RED)/WL-HFP

Intelligent Analogue Addressable Type A Wall VAD (White LED)-Red Body  (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes:

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-7

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-1

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 1Hz

        - Synchronization
6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/12
CHQ-WB(WHT)/RL-HFP

Intelligent Analogue Addressable Type A Wall VAD (Red LED)-White Body  (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance O-2-3*
        * Light coverage defined as per standard W-rating but with a maximum height of 2m(rectangular)

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.7-1.07

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-4

        - LOL 2
        - Flash rate 1Hz

        - Synchronization

6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/14
CHQ-WB(RED)/RL-HFP

Intelligent Analogue Addressable Type A Wall VAD (Red LED) - Red Body  (YBO-R/SCI, YBN-R/3(SCI), YBN-R/3, YBO-BS, YBO-BSB2(RL&WL) & YBO-BSB Bases)

Notes

1.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance O-2.3*
        * Light coverage defined as per standard W-rating but with a maximum height of 2m(rectangular)

        - LOL 0
        - Flash rate 0.5Hz

        - Synchronization

2.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5

        - LOL 1
        - Flash rate 0.5Hz

        - Synchronization

3.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-5.5

        - LOL 2
        - Flash rate 0.5Hz

        - Synchronization

4.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.7-1.07

        - LOL 1
        - Flash rate 1Hz

        - Synchronization

5.   The Wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories:
        - Light Coverage Distance W-2.4-4

        - LOL 2
        - Flash rate 1Hz

        - Synchronization

6.   The Default factory setting is LOL 1, 0.5Hz

7.   Type B for outdoor use when used in conjunction with a WS2-WPK weatherproofing kit.

164s/15
YBO-BSB2(BLK)/RL

Addressable Type A Base Sounder Beacon (Black Housing, Red LED)

YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT), YBO-R/3(WHT) and YBN-R/3(SCI) Bases

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.    Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones

164t/09
YBO-BSB2(BLK))/WL

Addressable Type A Base Sounder Beacon (Black Housing, White LED)

YBO-R/3(RED), YBO-R/SCI(RED) and YBN-R/3(WHT), YBO-R/3(WHT) and YBN-R/3(SCI) Bases

Notes:        

1.   The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category 0

- Flash rate 0.5Hz

- Synchronization

2.   Meets the requirements of EN 54-3 for all 51 tones as listed under approved tones

164t/10

 

Bases:
YBN-R/3 Analogue mounting base (ivory and white)
YBO-R/SCI Isolator base
YBO-R/3(RED) Standard Base
YBO-R/SCI(RED) Short Circuit Isolator Base
YBN-R/3(WHT) Standard Base
YBO-R/3(WHT) Standard Base
YBN-R/3(SCI) Short Circuit Isolator Base

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page