Search by Certificate Number

Carrier Airconditioning & Refrigeration Ltd

Narsinghpur
Kherki Daula Post
Gurgaon 122 004
Haryana
India

Tel: +91-124-4825500 • Fax: +91 124 2372230
Email: customersupport.india@carrier.utc.com • Web: www.bis.utc.com


Certificate No 594Cb to LPS 1230


ARGONITE 150, 200, 300 bar Fixed Gaseous Fire Extinguishing System

Product

Risk

Design Concentration

Comments

LPCB
Ref. No.
ARGONITE

Class A Standard

(Solid fires e.g. Paper, wood, plastics)

40.1%

Design concentration includes 30% safety factor

594Cb/01
ARGONITE

Class A Cables  

(Solid fire risks including Cables)

47.6%

Confirmation that minimum safety factor is adequate

594Cb/01
ARGONITE

Class B

(Liquid Fires e.g. heptane)

47.1%

Design concentration includes 30% safety factor

594Cb/01

 

Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables System test concentration.  Where this value is lower than the Class A Standard value, the Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 206880.
Extinguishing concentrations are as tested in BRE Test Report Numbers 206879 and 216485 (ISO 14520-1 tests).
  
This system uses:

Design, Installation, Maintenance and User Manual:  
General Manual - Argonite System, MA-01-9006-0100, Revision 10 dated February 2008
  
Software Programme: VdS-Version 7.2 (2007)  

a)    This system is suitable for storage in environmental conditions from -20°C to +55°C
    b)    System pressure is specified as 150 bar, 200 bar and 300 bar @ 15°C

 


 

To read the Red Book section introduction click here.

 