Search by Certificate Number

Fire Eater A/S

Vølundsvej 17
3400 Hillerød
Denmark

Tel: +45 7022 2769 • Fax: +45 7023 2769
Email: go@fire-eater.dk • Web: www.fire-eater.com


Certificate No 1287b to LPS 1230


Fire Eater IG541 200 bar & 300 bar

Product

Risk

Design Concentration

Comments

LPCB
Ref. No.
Fire Eater Control Inert INERGEN

Class A Standard (Solid fires e.g. paper, wood, plastics

37.2%

Design concentration includes 30% safety factor

1287b/01
Fire Eater Control Inert INERGEN

Class A Cables (Solid fires risks including cables)

42.6%

Confirmation that 'minimum safety factor' is adequate

1287b/01
Fire Eater Control Inert INERGEN

Class B (Liquid Fires e.g.heptane)

43.7%

Design concentration includes 30% safety factor

1287b/01

 

Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 291411 (200 bar and 300 bar)
Extinguishing concentrations are as tested in BRE Test Report Number 291410 (EN 15004-1 tests).

This system uses:

Design Manual: ‘Fire Eater Control Inert Extinguishing System - Design, Installation, Maintenance and User Manual’ - Revision 2015-02-23
Software Program: Fire Eater A/S Inergen Program, IMT version 2.2.x.
This system is suitable for storage and environmental conditions from -20ºC to +65ºC.
System pressure is specified as 200 bar and 300 bar at 15ºC.


 


 

To read the Red Book section introduction click here.

 