Search by Certificate Number

Turk Prysmian Kablo ve Sistemleri A.S.

Omerbey Mah
Bursa Asfalti Cad. No: 51
16941 Mudanya
Bursa
Turkey

Tel: 00 90 224 270 3000 • Fax: 0090 224 270 3030
Email: tpks@prysmiangroup.com • Web: www.prysmian.com.tr


Certificate No 1151c to EN 61034-2:2005, EN 50267-2-1:1999, EN 50267-2-2:1999, EN 50267-2-3:1999, IEC 60331-21:1999, EN 60332-1-2:2004, EN 60332-3-24:2009


AFUMEX N2XH FE 180

Product

Nominal csa of conductor (mm2)

Core Construction

(excluding drain wire and earth)

EN 61034-2

EN 50267-2-1

EN 50267-2-3

IEC 60331-21

EN 60332-3-24

LPCB
Ref. No.
AFUMEX N2XH FE 180

16/10

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

25/16

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

35/16

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

50/25

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

70/35

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

95/50

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

120/70

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

150/70

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

185/95

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01
AFUMEX N2XH FE 180

240/120

3

>60%

<0.5% HCI

Complies

Complies(3)

Complies

1151c/01

 

Uo/U 600/1000V
  
Notes:
1.    Solid conductor only.
2.    Stranded conductor only.
3.    The AFUMEX N2XH FE 180 cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 750oC for a duration of 180mins at a voltage rating of 600/1000V.
4.    In achieving a weighted average of pH greater than 4.3 and a weighted average of donductivity less than 10µS/mm on the constituent materials when tested in accordance with EN 50267-2-3:1999, the AFEMEX N2XH FE 180 cables listed also met the requirements of EN 50267-2-2:1999.
5.    The AFUMEX N2XH FE 180 cables listed also met the requirements of EN 60332-1-2:2004.

  

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page