Search by Company Name

Draka (Malaysia) Sdn. Bhd.

Lot 48, Jalan Industri 13
Alor Gajah Industrial Estate
78000 Alor Gajah
Malacca
Malaysia

Tel: +606 556 3833 • Fax: +606 556 3282
Email: scmm@draka.com • Web: www.draka.com.my


Certificate No 994a to BS 6387: 1994, IEC 60331-21: 1999, BS EN 50267-2-1: 1999 and BS EN 61034-2: 2005


FIRETUF Classic MI SIFER (s)

Product

Nominal csa of conductor (mm2)

Core construction

(See note 1)

BS 6387

(See notes 2 - 4)

BS EN 50267-2-1

BS EN 61034-2

IEC 60331-21

(See note 9)

LPCB
Ref. No.
FIRETUF Classic MI SIFER (s)

1.5

One

C, W, Z(5)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

2.5

One

C, W, Z(5)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

4.0

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

6.0

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

10

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

16

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

25

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

35

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

50

One

C, W, Z(6, 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

70

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

95

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

120

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

150

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

185

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

240

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

300

One

C( 7)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

400

One

Complies(8)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

500

One

Complies(8)

<0.5% HCI

>60%

Complies

994a/01
FIRETUF Classic MI SIFER (s)

630

One

Complies(8)

<0.5% HCI

>60%

Complies

994a/01

 

Uo/U 600/1000V

Notes:

1)    Stranded conductor only.
2)    Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the calbe having only one core.
3)    These cables also met category C, W, Z when tested for voltage rating 600/1000V which is not recognised by BS 6387.
4)    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
5)    To satisfy the requirement of BS 6387, testing for C, W & Z.categories were conducted using a 20mm stainless steel conduit as the other metallic element.
6)    To satisfy the requirement of BS 6387, testing for W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element.
7)    To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
8)    Only Clause 10 of BS 6387 was conducted.
9)    These cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 750oC and at a voltage rating of 600V.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page