Search by Company Name

Life Safety Distribution GmbH, System Sensor Europe

Javastrasse 2
CH-8604
Hegnau
Switzerland

Tel: +41 44 943 4424 • Fax: +41 44 943 4399
Email: sse.marketing@systemsensor.com • Web: www.systemsensoreurope.com


Certificate No 199ad-(cl-1) to EN 54-20:2006
Certificate No 199ae-(cl-2) to EN 54-17:2005 & EN 54-20:2006


Aspirating Smoke Detectors

Product Description LPCB
Ref. No.
FL0111E-HS

Stand Alone Single Channel Aspirating Detector (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

The 3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ad/01
FL0112E-HS

Stand Alone Single Channel Unit Common Chamber Aspirating Detector (F-INF-25 In line filter)

Notes:

1. This device has single channel capability with two high sensitivity smoke sensors in a common chamber.

2. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

3. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

4. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ad/02
FL0122E-HS

Stand Alone Dual Channel Aspirating Detector (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ad/03
FL2011EI-HS

Analogue Addressable Single Channel Loop-Based Aspirating Detector (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/01
FL2012EI-HS

Analogue Addressable Loop-Based Single Channel Unit Common Chamber Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1. This device has single channel capability with two high sensitivity smoke sensors in a common chamber.

2. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

3. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

4. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/02
FL2022EI-HS

Analogue Addressable Dual Channel Loop-Based Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/03

 

Accessories
    F-INF-25    In line filter
    

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page