10 Sanderson Way
Marton
Blackpool
Lancashire
FY4 4NB
United Kingdom
Tel: 01253 699500
•
Fax: 01253 699550
Email: info@firesafe.co.uk
•
Web: www.firesafe.co.uk
Certificate No 928ah-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-17:2005 & EN 54-18:2005
Certificate No 928z-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-18:2005 & EN 54-23:2010
Certificate No 928w-(cl-3) to EN 54-3:2001 + A1:2002 + A2:2006
Certificate No 928y-(cl-4) to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-23:2010
Certificate No 546a-(cl-5) to EN 54-3: 2001 + A1: 2002 + A2: 2006
Visual & Audible Warning Devices
Product | Description | LPCB Ref. No. |
---|---|---|
FSCWS + FSIMSB | G2 Addressable Type A (indoor) Wall Sounder with Short Circuit Isolator Notes: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms Tone 2 - Continuous Tone, 970Hz Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)
2.Device is only addressable when used in conjunction with FSIMSB |
928ah/01 |
FSCWSB + FSIMSB | G2 Addressable Type A (indoor) Wall Sounder and Visual Alarm Device with Short Circuit Isolator Notes: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms Tone 2 - Continuous Tone, 970Hz Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)
2. The wall mounted VAD meets the requirements of EN 54-23 for the following: - Category W-2.5-7 - Flash rate - 0.5Hz - Synchronization
3. Device is only addressable when used in conjunction with FSIMSB |
928z/01 |
FSCWS | G2 Conventional Type A (indoor) Wall Sounder Note: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms Tone 2 - Continuous Tone, 970Hz Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz) |
928w/07 |
FSIPLS | G2 Addressable Type A Sounder Base Notes: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Dual Tone 800Hz and 960Hz, 250ms-250ms Tone 2 - Continuous Tone, 1000Hz, Steady Tone 4 - Slow Whoop, 500-1200Hz, 3500ms Sweep, 500ms OFF Tone 5 - Sweep (DIN) Tone, 1200-500Hz, 1s sweep (1Hz) 2. Cover plate (LID100-AL/W or AL/R) |
928w/05 |
FSIPLSB | G2 Addressable Type A Sounder Beacon Base Notes: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Dual Tone 800Hz and 960Hz, 250ms-250ms Tone 2 - Continuous Tone, 1000Hz, Steady Tone 4 - Slow Whoop, 500-1200Hz, 3500ms Sweep, 500ms OFF Tone 5 - Sweep (DIN) Tone, 1200-500Hz, 1s sweep (1Hz) 2. The beacon function is not included within the scope of this approval 3. Cover plate (LID100-AL/W or AL/R) |
928w/06 |
FSCWSB | G2 Conventional Type A (indoor) Wall Sounder and Visual Alarm Device Notes: 1. Meets the requirements of EN 54-3 at the following tone settings: Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms Tone 2 - Continuous Tone, 970Hz Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms
Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz) 2. The wall mounted VAD meets the requirements of EN 54-23 for the following: - Category W-2.5-7 - Flash rate - 0.5Hz - Synchronization |
928y/01 |
FSIPS | G2 Conventional Slave 32 Tone Platform Sounder Base Notes: 1. Meets the requirements of EN 54-3 at the following tone settings on low, medium and high volume settings: -LF Sweep (Cranford sweep) (800-1000Hz @ 0.5s) -Warble Tone BS (800-1000Hz @ 0.5s) -Slow Woop (Dutch) Sweep Tone (500-1200Hz for 3.5s on, 0.5s off) -German DIN Tone (1200-500Hz @ 1Hz) -French Tone AFNOR (554Hz for 100ms and 440Hz for 400ms) |
546a/04 |
Detectors: