140 Waterside Road
Hamilton Industrial Park
Leicester
LE5 1TN
United Kingdom
Tel: +44 (0)116 246 2000
•
Fax: +44 (0)116 246 2300
Email: gent_enquiry@gent.co.uk
•
Web: www.gent.co.uk
Certificate No 042bj to EN 54-3: 2001 + A1: 2002 + A2: 2006, EN 54-17: 2005
Certificate No 042bt to EN54-17:2005, EN54-23:2010
Certificate No 042bs to EN 54-3:2001+A1:2002 + A2:2006
Product | Description | LPCB Ref. No. |
---|---|---|
S3EP-VAD-HPW-R | S-Cubed Type A White High Performance VAD Red Body with Short Circuit Isolator (Back Box) Notes:
2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bt/03 |
S3EP-VAD-HPR-R | S-Cubed Type A Red High Performance VAD Red Body with Short Circuit Isolator (Back Box) Notes:
2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bt/04 |
S3EP-V-VAD-HPW-R | S-Cubed Type A White High Performance VAD Red Body Voice Sounder with Short Circuit Isolator (Back Box) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low white output - Medium white output - High white output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/07 |
S3EP-V-VAD-HPR-R | S-Cubed Type A Red High Performance VAD Red Body Voice Sounder with Short Circuit Isolator (Back Box) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low red output - Medium red output - High red output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/10 |
S3EP-S-R | S-Cubed Type A Red Body Sounder with Short Circuit Isolator (Back Box) Note: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz |
042bj/25 |
S3-S-VAD-HPR-R | S-Cubed Type A Red High Performance VAD Red Body Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low red output - Medium red output - High red output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/01 |
S3-S-VAD-HPR-W | S-Cubed Type A Red High Performance VAD White Body Sounder with Short Circuit Isolator (S3-DB-W and S3-SB-W Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low red output - Medium red output - High red output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/02 |
S3-S-VAD-HPW-R | S-Cubed Type A White High Performance VAD Red Body Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low white output - Medium white output - High white output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/03 |
S3-V-VAD-HPW-R | S-Cubed Type A White High Performance VAD Red Body Voice Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low white output - Medium white output - High white output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/04 |
S3-V-VAD-HPR-R | S-Cubed Type A Red High Performance VAD Red Body Voice Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low red output - Medium red output - High red output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/05 |
S3-S-VAD-HPW-W | S-Cubed Type A White High Performance VAD White Body Sounder with Short Circuit Isolator (S3-DB-W and S3-SB-W Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz 2. Meets the requirements of EN 54-23 at the following power settings: - Low white output - Medium white output - High white output 3. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/06 |
S3-S-VAD-LPR-R | S-Cubed Type A Red Standard Performance VAD Red Body Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz 2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/11 |
S3-S-VAD-LPW-R | S-Cubed Type A White Standard Performance VAD Red Body Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz
2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bs/12 |
S3-S-R | S-Cubed Type A Red Body Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Note: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz |
042bj/21 |
S3-V-R | S-Cubed Type A Red Body Voice Sounder with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Note: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz |
042bj/22 |
S3-S-W | S-Cubed Type A White Body Sounder with Short Circuit Isolator (S3-DB-W and S3-SB-W Bases) Note: 1. Meets the requirements of EN 54-3 at the following sounder tone settings: 1. Intermittent tone 970Hz @ 1Hz 2. Alternating tone 730/970Hz @ 2Hz 3. Continuous tone 970Hz |
042bj/23 |
S3-V-W | S-Cubed Type A White Body Voice Sounder with Short Circuit Isolator (S3-DB-W and S3-SB-W Bases) Note: 1. Meets the requirements of EN 54-3 at the following sounder tone and speech settings: 1. Intermittent tone 970Hz @ 1Hz (Speech Message 3) 2. Alternating tone 730/970Hz @ 2Hz (Speech Message 5) 3. Continuous tone 970Hz |
042bj/24 |
S3-VAD-HPR-R | S-Cubed Type A Red High Performance VAD Red Body with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes:
2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-6.7-14) - Medium Performance setting - (Category W: W-6.5-12.5) - Low Performance setting - (Category W: W-5-9.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bt/01 |
S3-VAD-HPW-R | S-Cubed Type A White High Performance VAD Red Body with Short Circuit Isolator (S3-DB-R and S3-SB-R Bases) Notes:
2. The wall mounted Visual Alarm Device (VAD) meets the requirements of EN 54-23 for the following light pattern details: - High Performance setting - (Category W: W-5-12.5) - Medium Performance setting - (Category W: W-4.5-11.3) - Low Performance setting - (Category W: W-3-8.5) - Synchronization - Flash rate 2 seconds (0.5Hz) |
042bt/02 |
Bases: