Search by Certificate Number

Bosch Security Systems BV

Torenallee 49
Eindhoven
5617 BA
The Netherlands

Tel: +3140 257 7174
Email: Henk.Goudsmits@nl.bosch.com • Web: www.boschsecurity.com


Certificate No 1054a-(cl-1) to EN 54-16: 2008
Certificate No 1054b-(cl-1) to EN 54-4:1997 + A1:2002 & EN 54-16: 2008
Certificate No 1054b-(cl-2) to EN 54-4:1997 + A1:2002 & EN 54-16: 2008
Certificate No 1054c-(cl-1) to ISO 7240-16:2007
Certificate No 1054c-(cl-2) to ISO 7240-16:2007




Product Description LPCB
Ref. No.
PROMATRIX 8000

Voice Alarm System

Incorporating the following modules:

DPM 8016         Controller

PMX-MM2         Message manager

DPM AO-1         Analog audio output module

DPM UI-1         Universal audio input module

DPA 8150         Power amplifier 1 x 500W

DPA 8225         Power amplifier 2 x 250W

DPA 8412         Power amplifier 4 x 125W

DPC 8015         Call station

DCS 400         DCS 19" Mounting Frame

DCS 801R         Controller Module

DCS 407R         AF Relay Module Ext

DCS 408R         Loudspeaker relay Module

DCS 409R         AF Relay Module

DCS 412R         Logic Input Module

DCS 416R         Analog I/O Module

NRS90231         Key lock switch

EB DPC         Emergency button

DPC 8120         Call station extension

CM-1                 Cobranet Network Module

LT802GBTME        Network switch

PLN-24CH12         Power Supply

Certified with the following options with requirements from EN 54 Part 16:

7.3 Audible Warning

7.5 Phase evacuation

7.6.2 Manual silencing of the voice alarm condition

7.7.2 Manual reset of the voice alarm condition

7.9 Voice alarm condition output

8.3 Indication of faults related to the transmission path to the CIE

8.4 Indication of faults related to voice alarm zones

10 Voice alarm manual control

12 Emergency microphone(s)

13.14 Redundant power amplifier

Notes:

1.        The certificate is conditional upon the PROMATRIX 8000 Voice Alarm System being supplied with power from PLN-24CH12 or a power supply that meets the power specifications detailed in the manual and complies with the requirements of EN54-4.

2.        The VACIE is approved when connected to PLN-1EOL or EOL 8001

3.        The VACIE speaker lines are monitored by use of end line modules namely         PLN-1EOL or EOL 8001.

4.        The following IP30 cabinets have been approved for use with PROMATRIX 8000:-

        - Rittal TS8 based rack, with a lockable glass door, side panels, temperature         controlled top fans and having a fixed frame with a maximum height         of 42 HU (i.e. TS-IT series) or a lockable swing frame with a maximum height of 40 HU (i.e. TS-series).

        - Schroff (20130073 PRAESIDEO)

        - Diamond range of floor standing modular enclosures (Manufacturer E.Lan)

        - Knuerr Miracel 2 configurable rack platforms (manufacturer Knürr GmbH)

5.         The DPC 8015 call station requires the NRS90231 and EB DPC in order to meet option with requirement clause 10 and 12 of EN 54-16.

6.        The DPC 8120 is approved when connected with DPC 8015 call station

7.         This certificate is valid only when the installation has been performed in accordance with the "EN54-16 Installer checklist".

8.     The following SFP Modules have been approved for use with PROMATRIX 8000 when connected to the network switch LT-802GBTME:-

        - AC-SFP-LX-E-10 Single mode 1310nm SFP Module

        - AC-SFP-SX-E Multi-mode 850nm SFP Module

1054a/01
Dynacord / PROMATRIX 6000 VACIE

Voice Alarm Control and Indicating Equipment                                              

Incorporating the following modules:

PMX-4CR12        PROMATRIX 6000 Controller

PMX-4R24        PROMATRIX 6000 Router

PMX-2P500        PROMATRIX 6000 2x500 Watt Amp.

PMX-15CST        PROMATRIX 6000 Call Station

PMX-15ECS        PROMATRIX 6000 Call Station

PMX-20CSE        PROMATRIX 6000 Call Station Extension.

NRS90231        Key Lock Switch

EB DPC        Emergency button DPC 8000 Series

PLN-24CH12        Power Supply Module

OM-1                Network Module

LT-802GBTME        Network Switch

Certified with the following options with requirements from EN54-16:

7.3         Audible Warning

7.5         Phase evacuation

7.6.2         Manual silencing of the voice alarm condition

7.7.2         Manual reset of the voice alarm condition

7.9         Voice alarm condition output

8.3         Indication of faults related to the transmission path to the CIE

8.4         Indication of faults related to voice alarm zones

10         Voice alarm manual control

12         Emergency microphone(s)

13.14         Redundant power amplifier

Notes:

1.         The VACIE is approved when connected to PLN-1EOL or EOL 8001 or with activated impedance measurement.

2.          The VACIE speaker lines are monitored by use of end line modules namely PLN-1EOL End Of Line Board, EOL 8001 PROMATRIX EOL Module or by impedance measurement.

3.        The PVA-15CST call station requires the NRS90231 and EB DPC in order to meet option with requirement clause 10 and 12 of EN 54-16.

4.        The PMX-20CSE is approved when connected with PMX-15CST call station

5.          The following IP30 cabinets have been approved for use with Dynacord/Promatrix 6000:-

                    - Rittal TS8 based rack, with a lockable glass door, side panels, temperature controlled top fans and having a fixed frame with a maximum height of 42 HU (i.e. TS-IT series) or a lockable swing frame with a maximum height of 40 HU (i.e. TS-series).

             - Schroff (20130073 PRAESIDEO)

        - Diamond 19 Inch Cabinet (Manufacturer: E.Lan)

        - Knuerr Miracel 2 (Manufacturer: Knürr GmbH)

6.          The following SFP Modules have been approved for use with Dynacord/Promatrix 6000 when connected to the network switch

        LT-802GBTME:-
        - AC-SFP-LX-E-10 Single mode 1310nm SFP Module

        - AC-SFP-SX-E Multi-mode 850nm SFP Module

7.         This certificate is valid only when the installation has been performed in accordance with the "EN54-16 Installer checklist".

1054b/01
Bosch / PAVIRO VACIE

Voice Alarm Control and Indicating Equipment

Incorporating the following modules:

PVA-4CR12        PAVIRO Controller

PVA-4R24        PAVIRO Router

PVA-2P500        PAVIRO 2x500 W Amplifier

PVA-15CST        PAVIRO Call Station

PVA-15ECS        PAVIRO Call Station

PVA-20CSE        PAVIRO Call Station Extension

PVA-1KS         PAVIRO CST Key Switch

PVA-1EB         PAVIRO CST Emergency button

PLN-24CH12        Power Supply Module

OM-1                Network Module

LT-802GBTME        Network Switch

Certified with the following options with requirements from EN54-16:

7.3         Audible Warning

7.5         Phase evacuation

7.6.2         Manual silencing of the voice alarm condition

7.7.2         Manual reset of the voice alarm condition

7.9         Voice alarm condition output

8.3         Indication of faults related to the transmission path to the CIE

8.4         Indication of faults related to voice alarm zones

10         Voice alarm manual control

12         Emergency microphone(s)

13.14         Redundant power amplifier

Notes:

1.         The VACIE is approved when connected to PLN-1EOL or PVA-1WEOL end of line board or with activated impedance measurement.

2.        The VACIE speaker lines are monitored by use of end line modules namely PLN-1EOL end of line board, PVA-1WEOL addressable end of line board or impedance measurement.

3.         The PVA-15CST call station requires the PVA-1KS and PVA-1EB in order to meet option with requirement clause 10 and 12 of EN 54-16.

4.        The PVA-20CSE is approved when connected with PVA-15CST call station

5.          The following IP30 cabinets have been approved for use with PAVIRO:-

                    - Rittal TS8 based rack, with a lockable glass door, side panels, temperature controlled top fans and having a fixed frame with a maximum height of 42 HU (i.e. TS-IT series) or a lockable swing frame with a maximum height of 40 HU (i.e. TS-series).

             - Schroff (20130073 PRAESIDEO)

        - Diamond 19 Inch Cabinet (Manufacturer: E.Lan)

        - Knuerr Miracel 2 (Manufacturer: Knürr GmbH)

6.          The following SFP Modules have been approved for use with PAVIRO when connected to the network switch LT-802GBTME:-

        - AC-SFP-LX-E-10 Single mode 1310nm SFP Module

        - AC-SFP-SX-E Multi-mode 850nm SFP Module

7.         This certificate is valid only when the installation has been performed in accordance with the "EN54-16 Installer checklist".

1054b/02
Dynacord / PROMATRIX 6000 VACIE

Voice Alarm Control and Indicating Equipment         

Incorporating the following modules:

PMX-15ECS        PROMATRIX 6000 Emergency Call Station

OM-1                Network Module

LT-802GBTME        Network Switch

PMX-4CR12        PROMATRIX 6000 Controller

PMX-4R24        PROMATRIX 6000 Router

PMX-2P500        PROMATRIX 6000 2x500 Watt Amp.

PMX-15CST        PROMATRIX 6000 Call Station

PMX-20CSE        PROMATRIX 6000 Call Station Extension.

NRS90231        Key Lock Switch

EB DPC        Emergency button DPC 8000 Series

PLN-24CH12        Power Supply Module

OM-1                Network Module

LT-802GBTME        Network Switch

Certified with the following options with requirements from ISO7420-16:

7.2        Alert signal

7.5        Audible warning

7.8.2        Silencing of the voice-alarm condition with a manual control

7.9.2        Reset of the voice-alarm condition with a manual control

7.11        Voice-alarm condition output signal

8.2.6.1        Faults related to the transmission path to the emergency detection system

8.2.6.2        Faults related to emergency loudspeaker zones

11        Manual mode control

11.3        Indication of the emergency loudspeaker zones in the fault-warning condition

13        Emergency microphone

13.2        Microphone priority

13.3        Microphone emergency loudspeaker zone control

14.14        Redundant power amplifiers

Notes:

1.         The VACIE is approved when connected to PLN-1EOL or EOL 8001 or with activated impedance measurement.

2.          The VACIE speaker lines are monitored by use of end line modules namely PLN-1EOL End Of Line Board, EOL 8001 PROMATRIX EOL Module or by impedance measurement.

3.        The PVA-15CST call station requires the NRS90231 and EB DPC in order to meet option with requirement clause 10 and 12 of EN 54-16.

4.        The PMX-20CSE is approved when connected with PMX-15CST call station

5.          The following IP30 cabinets have been approved for use with PROMATRIX 6000:-

            - Rittal TS8 based rack, with a lockable glass door, side panels, temperature controlled top fans and having a fixed frame with a maximum height of 42 HU (i.e. TS-IT series) or a lockable swing frame with a maximum height of 40 HU (i.e. TS-series).

            - Schroff (20130073 PRAESIDEO)

             - Diamond 19 Inch Cabinet (Manufacturer: E.Lan)

        - Knuerr Miracel 2 (Manufacturer: Knürr GmbH)

6.         The following SFP Modules have been approved for use with Dynacord/Promatrix 6000 when connected to the network switch

        LT-802GBTME:-

        - AC-SFP-LX-E-10 Single mode 1310nm SFP Module

        - AC-SFP-SX-E Multi-mode 850nm SFP Module

7.         This certificate is valid only when the installation has been performed in accordance with the "ISO7420-16 Installer checklist".

1054c/01
Bosch / PAVIRO VACIE

Voice Alarm Control and Indicating Equipment

Incorporating the following modules:"

PVA-4CR12        PAVIRO Controller

PVA-4R24        PAVIRO Router

PVA-2P500        PAVIRO 2x500 W Amplifier

PVA-15CST        PAVIRO Call Station

PVA-20CSE        PAVIRO Call Station Extension

PVA-1KS         Call Station Key Switch

PVA-1EB         PAVIRO Call Station Emergency button

PLN-24CH12        Power Supply Module

PVA-15ECS        PAVIRO Emergency Call Station

OM-1                Network Module

LT-802GBTME        Network Switch

Certified with the following options with requirements from ISO7420-16:

7.2        Alert signal

7.5        Audible warning

7.8.2        Silencing of the voice-alarm condition with a manual control

7.9.2        Reset of the voice-alarm condition with a manual control

7.11        Voice-alarm condition output signal

8.2.6.1        Faults related to the transmission path to the emergency detection system

8.2.6.2        Faults related to emergency loudspeaker zones

11        Manual mode control

11.3        Indication of the emergency loudspeaker zones in the fault-warning condition

13        Emergency microphone

13.2        Microphone priority

13.3        Microphone emergency loudspeaker zone control

14.14        Redundant power amplifiers

Notes:

1.         The VACIE is approved when connected to PLN-1EOL or PVA-1WEOL end of line board or with activated impedance measurement.

2.        The VACIE speaker lines are monitored by use of end line modules namely PLN-1EOL end of line board, PVA-1WEOL addressable end of line board or impedance measurement.

3.         The PVA-15CST call station requires the PVA-1KS and PVA-1EB in order to meet option with requirement clause 10 and 12 of ISO7420-16.

4.        The PVA-20CSE is approved when connected with PVA-15CST call station

5.        The following IP30 cabinets have been approved for use with PAVIRO:-

        - Rittal TS8 based rack, with a lockable glass door, side panels, temperature controlled top fans and having a fixed frame with a maximum height of 42 HU (i.e. TS-IT series) or a lockable swing frame with a maximum height of 40 HU (i.e. TS-series).

             - Schroff (20130073 PRAESIDEO)

            - Diamond 19 Inch Cabinet (Manufacturer: E.Lan)

        - Knuerr Miracel 2 (Manufacturer: Knürr GmbH)

6.          The following SFP Modules have been approved for use with PAVIRO when connected to the network switch LT-802GBTME:-

        - AC-SFP-LX-E-10 Single mode 1310nm SFP Module

        - AC-SFP-SX-E Multi-mode 850nm SFP Module.         

7.        This certificate is valid only when the installation has been performed in accordance with the "ISO7420-16 Installer checklist".

1054c/02

 

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page