Certificate No 1213c to EN 54-7:2018 & CEA 4021: 2003
Certificate No 1213p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2: 2006, EN 54-17: 2005 & CEA 4021: 2003
Certificate No 1213s to EN54-5: 2000 + A1: 2002 & EN 54-7:2000 + A1: 2002 + A2: 2006 & CEA 4021: 2003
Certificate No 1213y to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 + A2 2006, EN 54-25: 2008 & CEA4021: 2003


Multi-Sensor/Multi-Criteria Detectors

Product Description LPCB
Ref. No.
200-505

Odyssey Analogue Addressable Multisensor Detector

(200-111 mounting base)

1213c/01
100-2401V

EURV-PHI Intelligent Multi-Criteria Detector with Short Circuit Isolator

(100-3000V Base)

Notes:

1. Meets the requirements of EN 54-5 (Class A1) & EN 54-7 at the following

settings:

Multi Criteria Level 1 (most sensitive) - Thermally enhanced smoke detection with Class A1 heat response

Multi Criteria Level 2 - Thermally enhanced smoke detection with Class A1 heat response

Multi Criteria Level 3 - Thermally enhanced smoke detection with Class A1 heat response

Multi Criteria Level 4 (least sensitive) - Thermally enhanced smoke detection with Class A1 heat response

2. Meets the requirements of EN 54-5 (Class A1R) at the following settings:

Class A1R heat only response

3. Meets the requirements of EN 54-7 at the following sensitivity settings:

Optical only level 1 - High

Optical only level 2

Optical only level 3

Optical only level 4 - Low

1213p/01
100-2400V

EURV-PH Intelligent Multi-Criteria Detector (100-3000V Base)

Notes:        

1. Meets the requirements of EN 54-5 (Class A1) & EN 54-7 at the following settings:

Multi criteria level 1 (most sensitive) - Thermally enhanced smoke detection with Class A1 heat response

Multi criteria level 2 - Thermally enhanced smoke detection with Class A1 heat response

Multi criteria level 3 - Thermally enhanced smoke detection with Class A1 heat response

Multi criteria level 4 (least sensitive) - Thermally enhanced smoke detection with Class A1 heat response

2. Meets the requirements of EN 54-5 (Class A1R) at the following settings:

Class A1R heat only response

3. Meets the requirements of EN 54-7 at the following settings:

Optical only level 1 - High sensitivity

Optical only level 2

Optical only level 3

Optical only level 4 - Low sensitivity

1213s/01
EUW-MA-01

Intelligent Wireless Multi-Criteria Detector (EUW-WAB Base)

Notes:

  1. Meets the requirements of EN 54-5 for Class A1R
  2. Meets the requirements of EN 54-7 in the normal sensitivity setting
  3. The device must be used with the following batteries only
  4. CR123A (3 Vdc) - Main Battery
  5. CR2032A (3 Vdc) - Secondary Battery
1213y/01
EUW-MA-02

Intelligent Wireless Addressable Multi-Criteria Detector (EUW-WAB Base)

Notes:

      1.   Meets the requirements of EN 54-5 for Class A1R

      2.   Meets the requirements of EN 54-7 at the following sensitivity settings:

      Level 1 - High

      Level 2 - Normal

      Level 3 - Low

      3.   The device must be used with the following battery type only:

      CR123A (3 Vdc) - Primary and Secondary Battery

1213y/02

 

Bases:

200-111     Odyssey mounting base
    100-3000V    Low profile adaptor base
    EUW-WAB    Wireless Adaptor Base


 


 