Search by Certificate Number

Mavili Elektronik Ticaret Ve Sanayi A.S.

Serifali Mah
Kutup Sok, No: 27:
1-2-4 Ümraniye
Istanbul
TR 34775
Turkey

Tel: +90 216 4664 505 • Fax: +90 216 4664 510
Email: mavili@mavili.com.tr • Web: www.mavili.com.tr


Certificate No 926s to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-3:2010
Certificate No 926v to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-23:2010, EN 54-17:2005




Product Description LPCB
Ref. No.
ML-2430

Maxlogic Type A Conventional Wall Sounder and Beacon

Notes:

1.   Type A for Indoor Use only

2.   Meets the requirements of EN 54-3 at the following tones:

        1 - Alternating 800-970Hz

        2 - Continuous 970Hz

        3 - Sweep 800-970Hz, 1000ms On

        4 - Pulse 970 Hz, 1s On / 1s Off

        5 - Sweep 800-970Hz, 140ms On

        6 - Pulse 660Hz, 150ms On / 150ms Off

        7 - Intermittent Sweep 500-1200Hz, 3.5s On / 0.5s Off

        8 -  Sweep 1200-500Hz, 1000ms On

        9 - Pulse 970Hz, 450-500ms On / 450-550ms Off

        10 - Sweep 2400-2900Hz, 330ms On

        11 - Alternating 554-440Hz, 100ms On - 400ms On

        12 - Alternating 800-1000Hz, 500ms On - 500ms On

        13 - Sweep 800-1000Hz, 500ms On

        14 - Alternating 990-650Hz, 250ms On - 250ms On

        15 - Pulse 2810Hz, 500ms On / 500ms Off

        16 - Continuous 660Hz

        17 - Pulse 420Hz, 625ms On / 625ms Off

        18 - Sweep 800-970Hz, 20ms On

        19 - Sweep 2400-2850Hz, 20ms On

        20 - Sweep 2400-2850Hz, 140ms On

        21 - Sweep 2400-2850Hz, 1000ms On

        22 - Continuous 2850Hz

        23 - Sweep 150-1000Hz, 10s On / 4s Off

        24 - Sweep 500-1000Hz, 143ms On

        25 - Sweep 500-1200Hz, 1000ms Off

        26 - Sweep 500-1200Hz, 100ms Off

        27 - Alternating 400-1200Hz, 500ms On, 500ms Off

        28 - Pulse 800Hz, 1s On / 1s Off

        29 - Alternating  840-558Hz, 500ms On

        30 - Pulse 500Hz, 150ms On / 600ms On

        31 - Alternating 510-610Hz, 250ms On - 250ms On

        32 - Sweep 800-950Hz, 333ms On

3.   Meets the requirements of EN 54-23 for the following:

      - Category W-2.4-8.0

      - Flash Rate 1Hz

926s/01
ML-1430

Maxlogic Type A Analogue Addressable System Wall Sounder & Strobe

Notes:

1. Type A for Indoor Use only

2. Meets the requirements of EN 54-3 at the following tones:

1 - Alternating 800-970Hz, 250 - 250ms On

2 - Continuous 970Hz

3 - Sweep 800-970Hz, 1000ms On

4 - Pulse 970 Hz, 1000ms ON / 1000ms OFF        

5 - Sweep 800-970Hz, 180ms On

6 - Pulse 660HZ, 160ms On / 160ms Off

7 - Sweep 500-1200Hz, 2500ms On / 500ms Off

8 - Sweep 1200-500Hz, 1000ms On

9 - Pulse 970Hz, 450-550ms On, 450-550ms Off

10 - Sweep 2400-2900Hz, 250ms On

11 - Alternating 554-440Hz, 100ms On - 400ms On

12 - Alternating 800-1000Hz, 500ms On - 500ms On

13 - Sweep 800-1000Hz, 440ms On

14 - Alternating 990-650Hz, 250ms On - 250ms On

15 - Pulse 2810Hz, 500ms On / 500ms Off

16 - Continuous 660Hz

17 - Pulse 420Hz, 625ms On / 625ms Off

18 - Continuous 1200Hz

19 - Continuous 800Hz

20 - Sweep 2400-2850Hz, 200ms On

21 - Sweep 2400-2850Hz, 880ms On

22 - Continuous 2850Hz

23 - Sweep 150-1000Hz, 1100ms On / 4000ms Off

24 - Sweep 500-1000Hz, 190ms On

25 - Sweep 500-1200Hz, 1000ms On / 850ms Off

26 - Sweep 500-1200Hz, 450ms On

27 - Alternating 400-1200Hz, 486ms On / 480ms Off

28 - Pulse 800Hz, 938ms On / 996ms Off

29 - Alternating 840-558Hz, 480ms On - 490ms On

30 - Pulse 500Hz, 580ms On / 144ms Off

31 - Alternating 510-610Hz, 232ms On - 238ms On

32 - Sweep 800-950Hz, 344ms On

3. Meets the requirements of EN 54-23 for the following:

- Category Open Class O-1.4-2.0 (cuboid shape: 1.4-3.0.-2.0)

- Flash Rate 0.5Hz

926s/02
ML-1430.SCI

Maxlogic Type A Analogue Addressable System Wall Sounder & Strobe with Short Circuit Isolator

Notes:

1. Type A for Indoor Use only

2. Meets the requirements of EN 54-3 at the following tones:

1 - Alternating 800-970Hz, 250 - 250ms On

2 - Continuous 970Hz

3 - Sweep 800-970Hz, 1000ms On

4 - Pulse 970 Hz, 1000ms ON / 1000ms OFF

5 - Sweep 800-970Hz, 180ms On

6 - Pulse 660HZ, 160ms On / 160ms Off

7 - Sweep 500-1200Hz, 2500ms On / 500ms Off

8 - Sweep 1200-500Hz, 1000ms On

9 - Pulse 970Hz, 450-550ms On, 450-550ms Off

10 - Sweep 2400-2900Hz, 250ms On

11 - Alternating 554-440Hz, 100ms On - 400ms On

12 - Alternating 800-1000Hz, 500ms On - 500ms On

13 - Sweep 800-1000Hz, 440ms On

14 - Alternating 990-650Hz, 250ms On - 250ms On

15 - Pulse 2810Hz, 500ms On / 500ms Off

16 - Continuous 660Hz

17 - Pulse 420Hz, 625ms On / 625ms Off

18 - Continuous 1200Hz

19 - Continuous 800Hz

20 - Sweep 2400-2850Hz, 200ms On

21 - Sweep 2400-2850Hz, 880ms On

22 - Continuous 2850Hz

23 - Sweep 150-1000Hz, 1100ms On / 4000ms Off

24 - Sweep 500-1000Hz, 190ms On

25 - Sweep 500-1200Hz, 1000ms On / 850ms Off

26 - Sweep 500-1200Hz, 450ms On

27 - Alternating 400-1200Hz, 486ms On / 480ms Off

28 - Pulse 800Hz, 938ms On / 996ms Off

29 - Alternating 840-558Hz, 480ms On - 490ms On

30 - Pulse 500Hz, 580ms On / 144ms Off

31 - Alternating 510-610Hz, 232ms On - 238ms On

32 - Sweep 800-950Hz, 344ms On

3. Meets the requirements of EN 54-23 for the following:

- Category Open Class O-1.4-2.0 (cuboid shape: 1.4-3.0.-2.0)

- Flash Rate 0.5Hz

926v/01

 

 


 

To read the Red Book section introduction click here.

 

< back to results page