Sokerilinnantie 11C
02600
Espoo
Finland
Tel: +358 10 446 511
•
Fax: +358 10 446 5103
Email: FI-FireSecurity-Info@schneider-electric.com
•
Web: www.schneider-electric.com
Certificate No 199p to EN54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003
Certificate No 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003
Certificate No 010aq-(cl-2) to LPS 1274: 2005 EN 54-5: 2000 + A1: 2002 LPS 1265: 2004
Certificate No 010h to EN 54-7:2000 + A1:2002 + A2:2006, EN 54-5:2000 + A1:2002, CEA 4021:2003
Certificate No 010bb-(cl-2) to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002 + A2:2006, EN 54-17:2005 & CEA 4021:2003
Multi Criteria Detectors
Product | Description | LPCB Ref. No. |
---|---|---|
ED2351TEM | Conventional optical/thermal smoke & heat detector (B401, B401DG, B401R, B401SD and B401RSD bases) Note: 1. Meets the requirements of EN 54-5: 2000 at class A1R and EN 54-7: 2000 at High, Medium and Low. |
199p/03 |
ESMI2251CTLE | Analogue addressable multi-criteria fire detector and incorporating CO, photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: - Normal Mode: Alarm Levels 1 to 5 (Multi-criteria) EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R
Nuisance Environment Applications: Application 0, Alarm Level 4 EN54-7, LPS1279 & CEA 4021 Application 1, Alarm Level 5 EN54-5 Class A1R, EN54-7 & CEA 4021 Application 2, Alarm Level 4 or 5 EN54-5 Class A1R, EN54-7 & CEA 4021 Application 3, Alarm Level 5 EN54-5 Class A1R, EN54-7 & CEA 4021 Application 4, Alarm Level 5 EN54-5 Class A1R, EN54-7 & CEA 4021 Application 5, Alarm Level 5 EN54-7 & CEA 4021 Application 6, Alarm Level 5 EN54-5 Class A1R, EN54-7 & CEA 4021 |
199t/01 |
EDI-30 | ESMI Intellia Multisensor Smoke Detector (EBI-10 and EBI-12 bases) Note: 1. Certified at the following settings: Mode 1 - High sensitivity smoke detector with standard heat enhancement Mode 2 - Smoke detection only Mode 3 - Medium sensitivity smoke detector with standard heat enhancement Mode 4 - Low sensitivity smoke detector with high heat enhancement Mode 5 - Class A1 heat detector Also approved in conventional alarm modes 1, 2, 3, 4 and 5 2. Approved with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery multisensor detector in accordance with manufacturer's instructions. |
010h/01 |
EDE223-I | ESMI Essentia Smoke/Heat Detector with Multi-Criteria Detector (EBE200-N base)
Certified at the following settings: Mode 1: High sensitivity smoke detector with high heat enhancement Mode 2: Standard smoke sensitivity only Mode 3: Medium sensitivity smoke detector with medium heat enhancement Mode 4: Low sensitivity smoke detector with high heat enhancement Mode 5: Class A1R heat detector |
010bb/01 |
Bases:
To read the Red Book section introduction click here.