Ceasefire Fixed Gaseous Fire Extinguishing Systems
Product |
Risk |
Design Concentration |
Comments |
LPCB Ref. No. |
---|---|---|---|---|
Ceasefire HFC227ea 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class A Standard (Solid fires e.g. Paper, wood, plastics) |
7.8 % |
Design concentration includes 30% safety factor |
1329e/01 |
Ceasefire HFC227ea 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class A Cables (Solid fire risks including Cables) |
8.2 % |
Confirmation that minimum safety factor is adequate |
1329e/01 |
Ceasefire HFC227ea 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class B (Liquid Fires e.g. heptane) |
9.2 % |
Design concentration includes 30% safety factor |
1329e/01 |
Ceasefire FK 5-1-12 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class A Standard (Solid fires e.g. Paper, wood, plastics) |
5.3 % |
Design concentration includes 30% safety factor |
1329e/02 |
Ceasefire FK 5-1-12 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class A Cables (Solid fire risks including Cables) |
5.5 % |
Confirmation that minimum safety factor is adequate |
1329e/02 |
Ceasefire FK 5-1-12 25 bar and 42 bar Fixed Gaseous Fire Extinguishing System |
Class B (Liquid Fires e.g. heptane) |
6.0 % |
Design concentration includes 30% safety factor |
1329e/02 |