Search by Certificate Number

Ceasefire Industries Pvt. Ltd

Plot No. 4
Second Floor
Sector - 135
Noida
Uttar Pradesh
201301
India

Tel: +91 120 4255800 • Fax: +91 120 4255801
Email: amit@ceasefire.in • Web: www.ceasefire.in


Certificate No 1329d to LPS 1666: Issue 1.0


Ceasefire Industries Ltd HFC-227ea Direct Low Pressure (DLP) Application Fixed Fire Suppression Systems

Product

Container Size

Description

Detector Tube

Ventilation (Enclosed or Open Vents)

Air Flow (Forced / Natural)

LPCB
Ref. No.
CF-000880

2 kg

2 kg HFC-227ea DLP system

P/N:TI-000010A 6mm o/d

Enclosed & open options 4

Forced & natural 5

1329d/01
CF-000881

4 kg

4 kg HFC-227ea DLP system

P/N:TI-000010A 6mm o/d

Enclosed & open options 4

Forced & natural 5

1329d/02

 

Notes:  
  1)    Ceasefire Industries Ltd HFC-227ea DLP Systems shall be configured, installed, serviced and maintained in accordance with Ceasefire Industries Ltd System Manual CQRS/DIR/MAN/01 Version.01 Rev.04 - 16.04.2018.  
    2)    These systems are intended solely to provide enhanced local fire protection. They are not intended for use as whole room or building fire protection systems.  
3)    The systems use a single method for detection and delivery of the extinguishing agent to the activation point.
         - System operation pressure: 15 bar @ 20°C.
         - System operation temperature range: -20°C to +60°C.
  4)    The above systems may have air vents at low and/or high level (refer note 1).
5)    The above systems may have forced ventilation (refer note 1).
  
  

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page