Export House
175 Mauldeth Road
Fallowfield
Manchester
M14 6SG
United Kingdom
Tel: +44 (0)161 257 2541
•
Fax: +44 (0)161 225 8817
Email: xportsales@xportsales.com
•
Web: www.xportsales.com
Certificate No 717a-(cl-1) to EN 54-3: 2001 + A1: 2002 + A2: 2006
Certificate No 546a-(cl-6) to EN 54-3:2001 + A1:2002 + A2:2006
Certificate No 176e-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-17:2005
Certificate No 010ak-(cl-6) to EN 54-3:2001 + A1:2002 + A2:2006
Audible Warning Devices
Product | Description | LPCB Ref. No. |
---|---|---|
CP-500IMC | Conventional Sounder with LED Strobe (Red Head / Red Base) (SB-400IMC & DB-450IMC bases) Notes: 1. The above sounder is Type A when used the with the shallow base & Type B when used with the deep base only 2. Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 3. Certification excludes the strobe function |
717a/01 |
CP-400IMC | Conventional Sounder (Red) (SB-400IMC & DB-450IMC bases) Notes: 1. The above sounder is Type A when used the with the shallow base & Type B when used with the deep base only 2. Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 |
717a/05 |
CP-600IMC | Conventional Sounder with LED Strobe Common Operation (Red Head / Red Base) (SB-400IMC & DB-450IMC bases) Notes: 1. The above sounder is Type A when used with the shallow base & Type B when used with the deep base only 2. Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 3. Certification excludes the strobe function |
717a/10 |
CP550SB | Conventional Indoor Type A Sounder Notes: 1. The sounder is approved in red and white colours (-R and -W suffixes) 2. Certified to EN 54-3: 2001 with the following selectable tones: 1 - LF Sweep frequency (800-1000Hz in 0.5sec) 25 - German DIN tone Sweep (1200-500Hz @ 1Hz) 27 - French tone AFNOR (554Hz for 100ms and 440Hz for 400ms) 2ndStage tone for all above (800Hz continuous tone) 11 - 2ndStage, Dutch sweep tone (500-1200Hz for 3.5s on, 0.5s off) |
546a/01 |
CP550DB | Conventional Outdoor Type B Sounder Notes: 1. The sounder is approved in red and white colours (-R and -W suffixes) 2. Certified to EN 54-3: 2001 with the following selectable tones: 1 - LF Sweep frequency (800-1000Hz in 0.5sec) 25 - German DIN tone Sweep (1200-500Hz @ 1Hz) 27 - French tone AFNOR (554Hz for 100ms and 440Hz for 400ms) 2ndStage tone for all above (800Hz continuous tone) 11 - 2ndStage, Dutch sweep tone (500-1200Hz for 3.5s on, 0.5s off) |
546a/01 |
CP850BSW | Conventional Indoor Type A Sounder Base Notes: 1. Also approved in Off-white, Ivory and Alternative white (-O, -I, and -A suffixes) 2. Meets the requirements of EN 54-3 at the following tone settings on low, medium and high volume settings: 1 - LF Sweep (800-1000Hz @ 0.5 Sec) 3 - Warble Tone BS (800-1000Hz @ 0.5 Sec) 11 - 1st Stage, Dutch Sweep Tone (970Hz Cont) 11 - 2nd Stage, Dutch Sweep Tone (500-1200Hz for 3.5s on, 0.5s off) 25 - German DIN Tone (Sweep 1200-500Hz @ 1 Hz) 27 - French Tone AFNOR (554 Hz 100ms and 440Hz for 400ms) 3. Cover Plate (white) - Part no. 116-099 Cover Plate (ivory) - Part no. 116-119 |
546a/04 |
CON430A/CX/DR | Hi-Output Addressable Type B (outdoor) Wall Sounder with Short Circuit Isolator, Deep Base (Red) (Apollo Discovery) Note: 1. Meets the requirements of EN 54-3 at the following tones: - Evacuate, 572Hz for 0.5s, 720Hz for 0.5s - Alternating, 962Hz for 0.25s, 572Hz for 0.25s - Dutch slow sweep, 500Hz to 1200Hz for 3.5s on, 0.5s off |
176e/02 |
CON431A/CX/W | Addressable Type A (indoor) Ceiling Sounder Base with Short Circuit Isolator (Apollo Discovery) Notes: 1. Meets the requirements of EN 54-3 at the following tones: - Evacuate, 550Hz for 0.5s, 825Hz for 0.5s - Alternating, 925Hz for 0.25s, 626Hz for 0.25s - Dutch slow sweep, 500Hz to 1200Hz for 3.5s on, 0.5s off 2. Can be used as : - A stacked sounder base combination with detectors from the Apollo Discovery range |
176e/03 |
55000-005IMC | Intelligent Open-Area Sounder Visual Indicator Red with Red Lens (45681-518IML Enhanced Deep Isolating Base) Notes: 1. Meets the requirements of EN 54-3:2001 at the following tones: Apollo standard-840Hz,0.5s/558Hz,0.5s Dutch (slow whoop)- 500-1200Hz in 3.5s, 0.5s off German DIN-1200-500Hz over 1s 2. The Beacon function is not approved to EN 54-23 |
010ak/03 |
Bases
To read the Red Book section introduction click here.