Certificate No 176f to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-17:2005, EN 54-23:2010
Certificate No 176r to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-23:2010




Product Description LPCB
Ref. No.
BF433A/CX/SR

Hi-Output Addressable Type A (indoor) Wall Sounder VAD with Short Circuit Isolator, Shallow Base (Red) (Apollo Discovery)

Notes:

1. Meets the requirements of EN 54-23 for the following:

- Category W-2.4-8.2

- Flash rate 0.5Hz

- Synchronization

- Operating voltage range 21-28 VDC

2. Meets the requirements of EN 54-3 for the following:

- Evacuate, 572Hz for 0.5s, 720Hz for 0.5s

- Alternating, 962Hz for 0.25s, 572Hz for 0.25s

- Dutch slow sweep, 500Hz to 1200Hz for 3.5s on, 0.5s off

- Operating voltage range 17-28 VDC

176f/01
BF433A/CX/DR

Hi-Output Addressable Type B (outdoor) Wall Sounder VAD with Short Circuit Isolator, Deep Base (Red) (Apollo Discovery)
Notes:

1. Meets the requirements of EN 54-23 for the following:

- Category W-2.4-8.2

- Flash rate 0.5Hz

- Synchronization

- Operating voltage range 21-28 VDC

2. Meets the requirements of EN 54-3 for the following:

- Evacuate, 572Hz for 0.5s, 720Hz for 0.5s

- Alternating, 962Hz for 0.25s, 572Hz for 0.25s

- Dutch slow sweep, 500Hz to 1200Hz for 3.5s on, 0.5s off
- Operating voltage range 17-28 VDC

176f/02
BF456A/CX/W

Addressable Type A (indoor) Ceiling Sounder VAD Base with Short Circuit Isolator (Apollo Discovery)

Notes:

1.   Meets the requirements of EN 54-23 for the following:

- Category C-3-8

- Flash rate 0.5Hz

- Synchronisation

- Operating voltage range 21-28 VDC

2.   Meets the requirements of EN 54-3 for the following:

- Evacuate, 550Hz for 0.5s, 825Hz for 0.5s

- Alternating, 925Hz for 0.25s, 626Hz for 0.25s

- Dutch slow sweep, 500Hz to 1200Hz for 3.5s on, 0.5s off

- Operating voltage range 17-28 VDC

3.    Can be used as either:

- a stand-alone device with locking white cap (BF330CTLIDW), or red cap (BF330CTLIDR), or

- a stacked sounder/VAD base combination with detectors from the Apollo Discovery range

176f/03
CA451A/SW

Addressable CAST Protocol Type A Compact Sounder VAD with Short Circuit Isolator, Shallow Base, White Body, IP21C (BFIPPLATE/R, BFIPPLATE/W)

Notes:

1.   Meets the requirements of EN 54-23 for the following:

- Category C-3-8, W-3-3.125

- Flash rate 0.5Hz

- Synchronisation

- White LED

- Operating voltage range 27-40 VDC

2. Meets the requirements of EN 54-3 for the following:

- Evacuate, 535Hz for 0.5s, 800Hz for 0.5s

- Fast Warble, 800Hz for 0.25s, 645Hz for 0.25s

- Dutch Slow Whoop, 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- Operating voltage range 24-40 VDC

176f/07
CA451A/SR

Addressable CAST Protocol Type A Compact Sounder VAD with Short Circuit Isolator, Shallow Base, Red Body, IP21C (BFIPPLATE/R, BFIPPLATE/W)

Notes:

1.   Meets the requirements of EN 54-23 for the following:

- Category C-3-8, W-3-3.125

- Flash rate 0.5Hz

- Synchronisation

- White LED

- Operating voltage range 27-40 VDC

2. Meets the requirements of EN 54-3 for the following:

- Evacuate, 535Hz for 0.5s, 800Hz for 0.5s

- Fast Warble, 800Hz for 0.25s, 645Hz for 0.25s

- Dutch Slow Whoop, 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- Operating voltage range 24-40 VDC

176f/07
CA432A/W

Addressable CAST Protocol Type A Ceiling Base Sounder VAD with Short Circuit Isolator, White, IP21C, Open Class (BF431QCP)  

Notes:

1. Meets the requirements of EN 54-3:2001 for the following tones:

- Evacuate, 610 Hz for 0.5 sec, 810 Hz for 0.5 sec

- Fast Warble, 810 Hz for 0.25 sec, 610 Hz for 0.25 sec

- Dutch Slow Whoop (sweep), 500 Hz to 1200 Hz for 3.5 sec on, 0.5 sec off

- German DIN Tone, 1200Hz-500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 440ms

- Operating voltage range 24-40V d.c.

2. The Ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating O-R-3-2.5-18

- Synchronization

- Flash rate 0.5Hz

- White LED

176f/08
CA456A/W

Addressable CAST Protocol Type A Ceiling Base Sounder VAD with Short Circuit Isolator, White, IP21C, Ceiling Class (BF431QCP)

Notes:

1. Meets the requirements of EN 54-3:2001 for the following tones:

- Evacuate, 610 Hz for 0.5 sec, 810 Hz for 0.5 sec

- Fast Warble, 810 Hz for 0.25 sec, 610 Hz for 0.25 sec

- Dutch Slow Whoop (sweep), 500 Hz to 1200 Hz for 3.5 sec on, 0.5 sec off

- German DIN Tone, 1200Hz-500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 440ms

- Operating voltage range 24-40V d.c.

2. The Ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating C-3-8.5

- Synchronization

- Flash rate 0.5Hz

- White LED

176f/09
CA433A/SR

Addressable CAST Protocol Type A High Output Wall Sounder VAD with Short Circuit Isolator, Shallow Base, Red, IP21 (BFIPPLATE/R)

Notes:

1. Meets the requirements of EN 54-3 at the following tones:

- Evacuate, 675Hz for 0.5s, 925Hz for 0.5s

- Fast Warble, 920Hz for 0.25s, 975Hz for 0.25s

- Dutch Slow Whoop (sweep), 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- US Temporal LF (ISO 8201), 3x(970Hz, 0.5s on, 0.5s off), 1s off

- Operating voltage range 24-40V d.c

2. The Wall Mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating W-2.75-9 or W-4-4

- Synchronization

- Flash rate 0.5Hz

- Red LED

176f/04
CA433A/DR

Addressable CAST Protocol Type B High Output Wall Sounder VAD with Short Circuit Isolator, Deep Base, Red, IP33 (BFIPPLATE/R)

Notes:

1. Meets the requirements of EN 54-3 at the following tones:

- Evacuate, 675Hz for 0.5s, 925Hz for 0.5s

- Fast Warble, 920Hz for 0.25s, 975Hz for 0.25s

- Dutch Slow Whoop (sweep), 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- US Temporal LF (ISO 8201), 3x(970Hz, 0.5s on, 0.5s off), 1s off

- Operating voltage range 24-40V d.c

2. The Wall Mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating W-2.75-9 or W-4-4

- Synchronization

- Flash rate 0.5Hz

- Red LED

176f/05
CA433A/DR/65

Addressable CAST Protocol Type B High Output Wall Sounder VAD with Short Circuit Isolator, Red, IP55 (BFIPPLATE/R and IP55 Deep Base)

Notes:

1. Meets the requirements of EN 54-3 at the following tones:

- Evacuate, 675Hz for 0.5s, 925Hz for 0.5s

- Fast Warble, 920Hz for 0.25s, 975Hz for 0.25s

- Dutch Slow Whoop (sweep), 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- US Temporal LF (ISO 8201), 3x(970Hz, 0.5s on, 0.5s off), 1s off  

- Operating voltage range 24-40V d.c

2. The Wall Mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating W-2.75-9 or W-4-4

- Synchronization

- Flash rate 0.5Hz

- Red LED

176f/06
HP433A/DR/65

HP Addressable Protocol Type B High Output Wall Sounder VAD with Short Circuit Isolator, IP55

Notes:

1. Meets the requirements of EN 54-3 at the following tones:

- Evacuate, 675Hz for 0.5s, 925Hz for 0.5s

- Fast Warble, 920Hz for 0.25s, 975Hz for 0.25s

- Dutch Slow Whoop (sweep), 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- US Temporal LF (ISO 8201), 3x(970Hz, 0.5s on, 0.5s off), 1s off  

- Operating voltage range 24-40V d.c

2. The Wall Mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating W-2.75-9 or W-4-4

- Synchronization

- Flash rate 0.5Hz

- Red LED

176f/06
HP451A/SW

HP Type A Compact Sounder VAD with Short Circuit Isolator, Shallow Base, White Body, IP21C

Notes:

1.   Meets the requirements of EN 54-23 for the following:

- Category C-3-8, W-3-3.125

- Flash rate 0.5Hz

- Synchronisation

- White LED

- Operating voltage range 27-40 VDC

2. Meets the requirements of EN 54-3 for the following:

- Evacuate, 535Hz for 0.5s, 800Hz for 0.5s

- Fast Warble, 800Hz for 0.25s, 645Hz for 0.25s

- Dutch Slow Whoop, 500Hz to 1200Hz for 3.5s on, 0.5s off

- German DIN Tone, 1200Hz to 500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 400ms

- Operating voltage range 24-40 VDC

176f/07
HP456A/W

HP Ceiling Class Type A Base Sounder VAD with Short Circuit Isolator, White, IP21C

Notes:

1. Meets the requirements of EN 54-3:2001 for the following tones:

- Evacuate, 610 Hz for 0.5 sec, 810 Hz for 0.5 sec

- Fast Warble, 810 Hz for 0.25 sec, 610 Hz for 0.25 sec

- Dutch Slow Whoop (sweep), 500 Hz to 1200 Hz for 3.5 sec on, 0.5 sec off

- German DIN Tone, 1200Hz-500Hz for 1s

- French Fire Tone, 554Hz for 100ms/440Hz for 440ms

- Operating voltage range 24-40V d.c.

2. The Ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Category rating C-3-8.5

- Synchronization

- Flash rate 0.5Hz

- White LED

176f/09
BF432C/CC/W

Conventional Type A Indoor O Class Base Sounder VAD, White LED (White Enclosure) IP21C

Notes:

1)   Approved to EN 54-3 (High volume only) at the following tones:

        - 1 - CTEC Evacuation Tone (610Hz for 0.5s, 810Hz for 0.5s)

        - 3 - CTEC Fast Warble (810Hz for 0.25s, 610Hz for 0.25s)

        - 5 - Dutch Slow Whoop (sweep) (500-1200Hz for 3.5s, 0.5s off)

        - 6 - DIN Tone (1200Hz-500Hz for 1s)

        - 15 - French Fire Tone (554Hz for 100ms / 440Hz for 380ms to 420ms)

        - Operating Voltage 18-30 VDC

2)   Meets the requirements of EN 54-23 for the following:  

                - Category O-R-3-2.5-17

                - Flash rate 0.5Hz synchronised

                - Operating voltage range 18-30 VDC

3)  The device must be used with Quick Connect Plate (BF431/QCP)

     Can be used as either:

        - A stand-alone device with locking white cap (BF330CTLIDW) or red cap (BF330CTLIDR), or,

        - A stacked sounder/VAD combination with detectors from C-TECs range of Activ conventional detectors

- C4408 Activ basic base, shall be used when detector is fitted.

176r/01
BF456C/CC/W

Conventional Type A Indoor C Class Base Sounder VAD, White LED (White Enclosure) IP21C

Notes:

1)   Approved to EN 54-3 (High volume only) at the following tones:

        - 1 - CTEC Evacuation Tone (610Hz for 0.5s, 810Hz for 0.5s)

        - 3 - CTEC Fast Warble (810Hz for 0.25s, 610Hz for 0.25s)

        - 5 - Dutch Slow Whoop (sweep) (500-1200Hz for 3.5s, 0.5s off)

        - 6 - DIN Tone (1200Hz-500Hz for 1s)

        - 15 - French Fire Tone (554Hz for 100ms / 440Hz for 380ms to 420ms)

        - Operating Voltage 18-30 VDC

2)  Meets the requirements of EN 54-23 for the following:  

                - Category C-3-8.5

                - Flash rate 0.5Hz synchronised

               - Operating voltage range 18-30 VDC

3)  The device must be used with Quick Connect Plate (BF431/QCP)

     Can be used as either:

        - A stand-alone device with locking white cap (BF330CTLIDW) or red cap (BF330CTLIDR), or,

        - A stacked sounder/VAD combination with detectors from C-TECs range of Activ conventional detectors

- C4408 Activ basic base, shall be used when detector is fitted.

176r/02
BF433C/CC/SR

Conventional Type A Indoor Hi Op Wall Sounder VAD (Red Enclosure), Shallow Base, IP21C

Notes:

1)   Approved to EN 54-3 at the following tones:

        - 1 - CTEC Evacuation Tone (675Hz for 0.5s, 925Hz for 0.5s)

        - 3 - CTEC Fast Warble (920Hz for 0.25s, 975Hz for 0.25s)

        - 5 - Dutch Slow Whoop (sweep) (500-1200Hz for 3.5s, 0.5s off)

        - 6 - DIN Tone (1200Hz-500Hz for 1s)

        - 15 - French Fire Tone (554Hz for 100ms / 440Hz for 380ms to 420ms)

2)  Meets the requirements of EN 54-23 for the following:  

        - Category W-2.75-9 / W-4-4

        - Flash rate 0.5Hz synchronised

        - Operating voltage range 18-30 VDC

176r/03
BF433C/CC/DR

Conventional Type B Outdoor Hi Op Wall Sounder VAD (Red Enclosure), Deep Base, IP33C

Notes:

1)   Approved to EN 54-3 at the following tones:

        - 1 - CTEC Evacuation Tone (675Hz for 0.5s, 925Hz for 0.5s)

        - 3 - CTEC Fast Warble (920Hz for 0.25s, 975Hz for 0.25s)

        - 5 - Dutch Slow Whoop (sweep) (500-1200Hz for 3.5s, 0.5s off)

        - 6 - DIN Tone (1200Hz-500Hz for 1s)

        - 15 - French Fire Tone (554Hz for 100ms / 440Hz for 380ms to 420ms)

2)  Meets the requirements of EN 54-23 for the following:  

        - Category W-2.75-9 / W-4-4

        - Flash rate 0.5Hz synchronised

        - Operating voltage range 18-30 VDC

176r/04
BF433C/CC/DR/65

Conventional Type B Outdoor Hi Op Wall Sounder VAD (Red Enclosure), Deep Base, IP55C

Notes:

1)   Approved to EN 54-3 at the following tones:

        - 1 - CTEC Evacuation Tone (675Hz for 0.5s, 925Hz for 0.5s)

        - 3 - CTEC Fast Warble (920Hz for 0.25s, 975Hz for 0.25s)

        - 5 - Dutch Slow Whoop (sweep) (500-1200Hz for 3.5s, 0.5s off)

        - 6 - DIN Tone (1200Hz-500Hz for 1s)

        - 15 - French Fire Tone (554Hz for 100ms / 440Hz for 380ms to 420ms)

2)  Meets the requirements of EN 54-23 for the following:  

        - Category W-2.75-9 / W-4-4

        - Flash rate 0.5Hz synchronised

        - Operating voltage range 18-30 VDC

176r/05

 

Deep Base - IP33C
Shallow Base - IP21C
Deep Base - IP55
BFIPPLATE/R    IP Protection Plate for Compact / Hi OP / Sounder VAD - Red
BFIPPLATE/W    IP Protection Plate for Compact / Hi OP / Sounder VAD - White
BF431QCP     Quick Connect Plate
CC408   Activ Base
BF330CTLIDW    White Cap
BF330CTLIDR     Red Cap
  

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page