Search by Certificate Number

Promat UK Ltd

The Sterling Centre
Eastern Road
Bracknell
Berkshire
RG12 2TD
United Kingdom

Tel: +44 (0)1344 381300 • Fax: +44 (0)1344 381301
Web: www.promat.co.uk


Certificate No 545a to LPS 1208: Issue 2




Product

Specification

Thickness

(mm)

Fire

Resistance

(min)

Integrity

Fire

Resistance

(min)

Insulation

Maximum

Unsupported

Length (m)

Grading

Core

Material

LPCB
Ref. No.
Durawall 60

100

60

60

4.50

FR60

Mineral fibre

545a/03
Durawall 90

125

90

90

5.50

FR90

Mineral fibre

545a/01
Durawall 120

150

120

120

5.50

FR120

Mineral fibre

545a/01
Durawall 240

150

240

240

7.50

FR240

Mineral fibre

545a/11

 

Notes:

1.    LPCB Ref. No's 545a/01, 545a/03 and 545a/11 - Wall panels can be installed vertically or horizontally.
2.    LPCB Ref. No's 545a/11 - wall panel joints to be stitched on both internal and external faces using 4.7mm Diameter x 20mm long self-tapping screws at 300mm centres.

 


 