Search by Certificate Number

Labor Strauss Sicherungsanlagenbau GmbH

Wiegelestrasse 36
A-1231 Vienna
Austria

Tel: +43 1 52114-44 • Fax: +43 1 52114-27
Email: andreas.schumacher@lst.at • Web: www.lst.at


Certificate No 546a-(cl-3) to EN 54-3: 2001 + A1: 2002 + A2: 2006
Certificate No 928w-(cl-4) to EN 54-3:2001 + A1:2002 + A2:2006

Certificate No 928ah-(cl-4) to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-17:2005 & EN 54-18:2005


Audible Warning Devices

Product Description LPCB
Ref. No.
200/FBRI/SOUW

Conventional indoor Type A sounder base  

Notes:        

1.  Also approved in Off-white, Ivory and Alternative white (-O, -I, and -A suffixes)

2.   Meets the requirements of EN 54-3 at the following tone settings on low, medium and high volume settings:

        1 - LF Sweep (Cranford sweep)  (800-1000Hz @ 0.5 Sec)

        3 - Alternative Warble (800-1000Hz @ 0.5 Sec)

        11 - Dutch Sweep Tone (970Hz Cont)

        25 - German DIN Tone (Sweep 1200-500Hz @ 1Hz)

        27- French Tone AFNOR (554Hz 100ms and 440Hz for 400 ms)

3.  Cover plate (Part No. 116-099) must be used.      

546a/04
F1700/WBRI/MT/SOUW

Conventional Indoor Type A Sounder Base

Notes:

1.  Meets the requirements of EN 54-3 at the following sounder tone settings on low, medium and high volume settings:

     1 - Warble Tone BS (800-1000Hz @ 0.5 Sec)

     3 - Slow Whoop (Dutch) (500-1200Hz for 3.5s on, 0.5s off)

     4 - German DIN Tone (Sweep 1200-500Hz @ 1Hz)

     12 - French Tone AFNOR (554Hz 100ms and 440Hz for 400 ms)

     23 - LF Sweep (800-1000Hz @ 0.5 Sec)

2.  Cover Plate (white) - Part no. 116-125

546a/04
F1750/WBRI/MT/SOUW

Conventional Indoor Type A Sounder Base

Notes:

1.  Meets the requirements of EN 54-3 at the following sounder tone settings on low, medium and high volume settings:

    1 - Warble Tone BS (800-1000Hz @ 0.5 Sec)

    3 - Slow Whoop (Dutch) (500-1200Hz for 3.5s on, 0.5s off)

    4 - German DIN Tone (Sweep 1200-500Hz @ 1Hz)

    12 - French Tone AFNOR (554Hz 100ms and 440Hz for 400 ms)

    23 - LF Sweep (800-1000Hz @ 0.5 Sec)

2.  Cover Plate (white) - Part no. 116-125

546a/04
CWS/SOUR

Conventional Type A (indoor) Wall Sounder

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

928w/07
CWS/SOUR + FI750/M/SST

Altair Addressable Type A (indoor) Wall Sounder with Short Circuit Isolator

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

2.Device is only addressable when used in conjunction with FI750/M/SST

Ancillaries

FI750/M/SST        Addressable module with short circuit isolator

928ah/01
.

 

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page