Search by Certificate Number

Grupo General Cable Sistemas, S.L.U.

Casanova, 150
Barcelona
08036
Barcelona
Spain

Tel: +34 93 227 95 00 • Fax: +34 93 227 95 22
Email: info@generalcable.es • Web: www.generalcable.es


Certificate No 730b to BS 6387:2013 Cat CWZ, EN 50267-2-1:1999, EN 61034-2:2000 and IEC 60331-21:1999




Product

Nominal csa

of conductor

(mm2)

Core Construction

BS 6387

EN 50267-2-1

(Insulation &

Binder tape)

EN 61034-2

IEC 60331-21

LPCB
Ref. No.
GENFIRE FR 950 07Z-R-M

1.0

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

1.5

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

2.5

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

4.0

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

6.0

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

10

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

16

One(1)

CWZ(2, 3)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

25

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

35

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

50

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

70

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

95

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

120

One(1)

CW(2, 4, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

150

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

185

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

240

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

300

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

400

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01
GENFIRE FR 950 07Z-R-M

500

One(1)

C(2, 5)

<0.5% HCI

>60%

Complies(6)

722a/01

 

Uo/U 450/750 V

Notes:
1)    Stranded conductor only.
2)    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
3)    To satisfy the requirement of BS 6387, testing for CWZ categories was conducted using a 20mm stainless steel conduit as the other metallic element.
4)    To satisfy the requirement of BS 6387, testing for W category was conducted using a 38mm stainless steel conduit as the other metallic element.
5)    To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
6)    The GENFIRE FR 950 07Z-R-M cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 750C for a duration of 90 mins + 15 mins cool down, at a voltage rating of 450V

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page