Search by Certificate Number

Kidde Fire Protection

Station Road
High Bentham
Lancaster
LA2 7NA
United Kingdom

Tel: +44 (0)1494 480 410 • Fax: +44 (0)1494 480 449
Email: general.enquiries@kiddeuk.co.uk • Web: www.kfp.co.uk


Certificate No 273q to prEN12094-7 and an LPCB schedule of requirements


Kidde Inert Gas System(400 Series) Nozzles

Product

Description

Orifice Size (mm)

LPCB
Ref. No.
38-4A7100-XXX (1)(2)

½" Nozzle assembly - 360° Holes

3 - 10

273q/01
38-4A7200-XXX (1)(2)

¾" Nozzle assembly - 360° Holes

7 - 13.5

273q/02
38-4A7300-XXX (1)(2)

1" Nozzle assembly - 360° Holes

10 - 17

273q/03
38-4A7400-XXX (1)(2)

1½" Nozzle assembly - 360° Holes

14 - 26

273q/04
38-4A7500-XXX (1)(2)

½" Nozzle assembly - 180° Holes

3 - 10

273q/05
38-4A7600-XXX (1)(2)

¾" Nozzle assembly - 180° Holes

7 - 13.5

273q/06
38-4A7700-XXX (1)(2)

1" Nozzle assembly - 180° Holes

10 - 17

273q/07
38-4A7800-XXX (1)(2)

1½" Nozzle assembly - 180° Holes

14 - 26

273q/08

 

KIDDE INERT GAS SYSTEM (400) SERIES), FIXED FIRE FIGHTING COMPONENTS

  • This range of equipment is suitable for storage temperatures -20°C to +50°C and is approved for use with: Argonite® (IG55), Nitrogen (IG-100), Argon (IG-01) and IG541
  • This range of equipment is approved for use in conjunction with Kidde Fire Protection Design manual reference: 06-237518-001 (Revision AA dated May 2018)
  • System pressure is specified at 200 bar and 300 bar @ 15°C.

    Notes:
  • (1)    Where XXX is Orifice size, e.g. 070 = 7mm, 075 = 7.5mm, 115 = 11.5mm, etc
    (2)    Where A can be 1 for BSP and 0 for NPT connections
        

     


     

    To read the Red Book section introduction click here.

     

    < back to results page

    < back to search page