Search by Certificate Number

Victaulic Company

4901 Kesslersville Road
Easton
Pennsylvania 18040
USA

Tel: +1 610 559 3300 • Fax: +1 610 250 8817
Email: victaulic@victaulic.com • Web: www.victaulic.com


Certificate No 104l to LPS 1261


Victaulic VicFlexTM AH2-CC grooved end braided flexible sprinkler drops.

Product

Length (mm)

Nominal Size/Connection Supply

Nominal Size/Connection Outlet

Maximum Working Pressure (bar)

LPCB
Ref. No.
AH2-31

790

1" BSPT (or NPT) External thread

½" or ¾" BSPT  (or  NPT) Internal thread

16

104l/04
AH2-36

910

1" BSPT (or NPT) External thread

½" or ¾" BSPT  (or  NPT) Internal thread

16

104l/04
AH2-48

1220

1" BSPT (or NPT) External thread

½" or ¾" BSPT  (or  NPT) Internal thread

16

104l/04
AH2-60

1525

1" BSPT (or NPT) External thread

½" or ¾" BSPT  (or  NPT) Internal thread

16

104l/04
AH2-72

1830

1" BSPT (or NPT) External thread

½" or ¾" BSPT  (or  NPT) Internal thread

16

104l/04

 

Notes:
These products have been approved as a Type 2 hose of moderate flexibility in accordance with LPS 1261.  
These may be used in applications where little or no differential movement between the two ends is expected after installation (e.g. supply to single sprinklers in suspended ceilings)

 1.     Victaulic  flexible sprinkler connections are approved for use in the following applications:



       All pipework supplying Victaulic flexible sprinkler connection assemblies in pre-calculated systems shall be sized as distribution mains.
      The above applications apply to Victaulic flexible drops with;
       *up to 2 x 90° bends, with or without, a 90° sprinkler reducer,
      ** up to 3 x 90° bends,  with or without, a 90° sprinkler reducer.

  2.  In a suspended ceiling Victaulic flexible sprinkler connections must be installed using AB1 bracket assemblies in Accordance with the Victaulic Installation Iinstructions, I-VicFlex.AB1/AB2/AB10 REV O.

  3.   In suspended ceilings, the outlet ferrule must be secured to the ceiling support system with brackets supplied. For other applications the installer must supply brackets to ensure sprinkler is secure.
  
  

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page