Certificate No 104-1a to LPS 1219: Issue 3.1


Installation Ready Fittings

Product

Model No.

Pipe Outside Diameter (mm)

Gasket Type

Maximum Working Pressure (bar)

LPCB
Ref. No.
90° Elbow

101

42.4(1), 48.3(1), 60.3(2), 73.0(2), 76.1(2)

EPDM

25

104-1a/38
Tee

102

42.4(1), 48.3(1), 60.3(2), 73.0(2), 76.1(2)

EPDM

25

104-1a/38
45° Elbow

103

42.4(1), 48.3(1), 60.3(2), 73.0(2), 76.1(2)

EPDM

25

104-1a/38

 

Above items to be installed in accordance with Victaulic Instructions I-102_1  REV_B
(1)    A bolt torque of 60 ft lbf (81 Nm) is required for this size
(2)   A bolt torque of 70 ft lbf (95 Nm) is required for this size

 


 