Search by Certificate Number

Victaulic Company

4901 Kesslersville Road
Easton
Pennsylvania 18040
USA

Tel: +1 610 559 3300 • Fax: +1 610 250 8817
Email: victaulic@victaulic.com • Web: www.victaulic.com


Certificate No 104l to LPS 1261


Victaulic VicFlexTM AH1 braided flexible sprinkler drops

Product

Length (mm)

Nominal Size/Connection Supply

Nominal Size/Connection Outlet

Maximum Working Pressure (bar)

LPCB
Ref. No.
AH1-31

790

1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-36

910

1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-48

1220

1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-60

1525

1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-72

1830

1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-31

790

1¼" x 1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-36

910

1¼" x 1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-48

1220

1¼" x 1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-60

1525

1¼" x 1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02
AH1-72

1830

1¼" x 1"BSPT (or NPT)

External thread

½" or ¾" BSPT  (or  NPT)

Internal thread

16

104l/02

 

These products have been approved as a Type 2 hose of moderate flexibility in accordance with LPS 1261.  
These may be used in applications where little or no differential movement between the two ends is expected
after installation (e.g. supply to single sprinklers in suspended ceilings)

1.    Victaulic  flexible sprinkler connections are approved for use in the following applications:



      All pipework supplying Victaulic flexible sprinkler connection assemblies in pre-calculated systems
      shall be sized as distribution mains.
      The above applications apply to Victaulic flexible drops with;
       *up to 2 x 90° bends, with or without, a 90° sprinkler reducer,
      ** up to 3 x 90° bends,  with or without, a 90° sprinkler reducer.

2.  In a suspended ceiling Victaulic flexible sprinkler connections must be installed using AB1 bracket assemblies in Accordance with either of the Victaulic Installation Iinstructions,  I-VicFlex.AB1/AB2/AB10 REV M; I-VicFlex.AB3 REV D;I-VicFlex.AB4/AB9 REV F; I-VicFlex.AB5 REV C; I-VicFlex.AB7 REV H; I-VicFlex.AB8 REV B.
  

 


 

To read the Red Book section introduction click here.

 