Search by Certificate Number

Johnson Controls International Plc

8902 North Interstate 27
Lubbock
Texas 79403
USA

Tel: +1 806 472 2400 • Fax: +1 806 806 8902
Email: bob.bandura@tycofp.com

Additional Addresses

Sales Enquiries

Tel: +44 (0)161 875 0400 • Fax: +44 (0)161 875 0491
Email: info-uk@tyco-bspd.com • Web: www.tycobuilding.com


Certificate No 094a
Certificate No 094b to A technical approval based upon BS EN 12259-1:1999 (A1, A2 A3 & C1)
Certificate No 094c to A technical approval based upon BS EN 12259-1:1999 (+A3:2006) & CEA4023


Sprinkler Heads

Product

Nominal

Orifice

Size

(mm)

Type

Temperature Rating (oC)

LPCB
Ref. No.
†G1036

15

SU

260

094a/01
†G1040

15

SP

260

094a/01
TY3221 (Nickel Link) (6),(7)

15

SP

74 (quick response)

094a/03
TY3121 (Nickel Link) (6),(7)

15

SU

74 (quick response)

094a/03
TY3111 (1)

15

SU

74, 100, 138

094a/03
TY3211 (1)

15

SP

74, 100, 138

094a/03
TY3211 (3),(4),(9)

15

SR

74, 100

094a/03
TY4111 (1)

15

SU

74, 100, 138

094a/03
TY4811 (1)

20 (1/2" PT)

SU

74, 100, 138

094a/03
TY4911 (1)

20 (1/2" PT)

SP

74, 100, 138

094a/03
†TY3251 (1),(8)

15

SP

57, 68, 79, 93, 141, 182, 260  (5mm bulb)

094a/05
†TY3151 (1),(8)

15

SU

57, 68, 79, 93, 141, 182, 260 (5mm bulb)

094a/05
†TY3651 (1),(8)

15

CU/P

57, 68, 79, 93, 141, 182 (5mm bulb)

094a/05
†TY3451 (1),(8)

15

WU/P

57, 68, 79, 93, 141, 182 (5mm bulb)

094a/05
†TY3351 (1)

15

WH

57, 68, 79, 93, 141, 182 (5mm bulb)

094a/05
†TY4251 (1),(8)

20

SP

57, 68, 79, 93, 141, 182, 260 (5mm bulb)

094a/05
†TY4151 (1),(8)

20

SU

57, 68, 79, 93, 141, 182, 260 (5mm bulb)

094a/05
†TY4651 (1),(8)

20

CU/P

57, 68, 79, 93, 141, 182 (5mm bulb)

094a/05
†TY3631 (1),(6),(8)

15

CU/P

57, 68, 79, 93, 141 (quick response)

094a/06
†TY3131 (1),(6),(8)

15

SU

57, 68, 79, 93, 141 (quick response)

094a/06
†TY3231 (1),(6),(8)

15

SP

57, 68, 79, 93, 141 (quick response)

094a/06
†TY3431 (1),(6),(8)

15

WU/P

57, 68, 79, 93, 141 (quick response)

094a/06
†TY3331 (1)

15

WH

57, 68, 79, 93, 141

094a/06
†TY4631 (1),(6),(8)

20

CU/P

57, 68, 79, 93, 141 (quick response)

094a/06
†TY4131 (1),(6),(8)

20

SU

57, 68, 79, 93, 141 (quick response)

094a/06
†TY4231 (1),(6),(8)

20

SP

57, 68, 79, 93, 141 (quick response)

094a/06
TY3551(10)

15

CCP

(adjustable) 68 sprinkler with 59 ceiling plate (5mm bulb)

094a/09
TY3551(10)

15

CCP

(adjustable) 93 sprinkler with 74 ceiling plate (5mm bulb)

094a/09
TY3531(10)

15

CCP

(adjustable) 68 sprinkler with 59 ceiling plate (3mm bulb)

094a/10
TY3531(10)

15

CCP

(adjustable) 93 sprinkler with 74 ceiling plate (3mm bulb)

094a/10
TY3155 (1)(8)

15

DSU

57, 68, 79, 93, 141

094a/11
TY3255 (1)(8)

15

DSP

57, 68, 79, 93, 141

094a/11
TY3355 (1)(8)

15

DWH

57, 68, 79, 93, 141

094a/11
† TY3250 (13)

15mm

SP

68, 93, 141, (5mm bulb)

094a/12
TY6226 / ESFR-1 (2)

N/A

SP

74, 100

094b/01
TY9226 / ESFR-25 (12)

N/A

SP

74, 100

094b/03
TY8223 / EFSR-22 (15)

N/A

SP

74, 100

094b/04
† ELO 231 (TY5131) (1),(14)

20mm

SU

68, 93, 141, (quick response)

094c/01
† ELO 231 (TY5231) (1),(14)

20mm

SP

68, 93, 141, (quick response)

094c/02

 

Notes:
1 )    Also approved with chromium finish .
  2)    This ESFR sprinkler has a k-factor of 200 l.min-1.bar -1/2  (US k-factor of 14 gal.min-1.psi-1/2).
  3)    Not to be installed in ceilings with a positive pressure in the void above.
4)    Approved with brass, chrome, or coloured recessing cup.
  6 )    The suitability of 'quick response' sprinklers for many risks is not yet proven. Use is therefore limited to where the purchaser authority having jurisdiction and/or insurers consent to  i ts use. Quick response sprinklers must be handled with care due to the fragile nature of the operating element, with packaging and instructions being marked accordingly.
  7)    Every five years, all sprinklers should be visually examined, and representative samples removed and tested to the requirements of the authority and/or insurer.
8 )    Also approved with polyester finish .
  9)    To be installed with specific installation instructions.
10)    Certificated with Chrome, Brass and painted coverplates.
12)    The ESFR-25 sprinkler has a k-factor of 362.9 l.min-1.bar -1/2   (US k-factor of 25.2 gal.min-1.psi -1/2  ).
13)  Approved in grade 316 Stainless steel
  14)  This Extra Large Orifice (ELO) sprinkler has a k-factor of 160 l.min-1.bar -1/2    (US k-factor of 11.2 gal.min-1.psi -1/2.).
15)  The ESFR-22 sprinkler has a k-factor of 320 l.min-1.bar -1/2  (US k-factor of 22.4 gal.min-1.psi -1/2).

 


 

To read the Red Book section introduction click here.

 

< back to results page