Search by Certificate Number

Roxspur Measurement & Control

2 Downgate Drive
Sheffield
South Yorkshire
S4 8BT
United Kingdom

Tel: +44 (0)114 244 2521 • Fax: +44 (0)114 243 4838


Certificate No 088a




Product

Pipe Size

(mm)

Flow Range

(dm3/min)

LPCB
Ref. No.
Shunt Gapmeter

80

300 - 1500

088a/01
Shunt Gapmeter

100

500 - 2500

088a/02
Shunt Gapmeter

125

700 - 3500

088a/03
Shunt Gapmeter

150

1000 - 5000

088a/04

 

These meters have been approved for installation with the gauge glass in the vertical position. There must be at least five diameters of straight pipe upstream and downstream of the orifice plate. The isolating valves on the pressure tappings must be kept closed when the  meter is not being used. A spare gauge glass must be provided and located in the cabinet containing the stock of replacement sprinklers. Type Nominal pipe size to Flow range Connection LPCB Ref. No.

 


 