Search by Certificate Number

Rockwool Limited

Wern Tarw
Pencoed
Bridgend
Mid Glamorgan
CF35 6NY
United Kingdom

Tel: +44 (0)1656 862621 • Fax: +44 (0)1656 862302
Email: info@rockwool.co.uk • Web: www.rockwool.co.uk


Certificate No 022d to LPS 1107: Issue 1


4 Sided Protection Of Steel Beams Using The Bonded Noggin Or Stud Welded Pins/Glued Joint System (critical failure temperature 550°C)

Product

Board

Thickness

(mm)

Performance

Hp/A

30min

Performance

Hp/A

60min

Performance

Hp/A

90min

Performance

Hp/A

120min

Performance

Hp/A

180min

Performance

Hp/A

240min

LPCB
Ref. No.
Rockwool FirePro™ BeamClad

25

260

260

260

98

40

-

022d/01
Rockwool FirePro™ BeamClad

30

260

260

260

130

50

-

022d/01
Rockwool FirePro™ BeamClad

35

260

260

260

168

61

-

022d/01
Rockwool FirePro™ BeamClad

40

260

260

260

216

73

43

022d/01
Rockwool FirePro™ BeamClad

45

260

260

260

260

85

50

022d/01
Rockwool FirePro™ BeamClad

50

260

260

260

260

99

57

022d/01
Rockwool FirePro™ BeamClad

55

260

260

260

260

114

65

022d/01
Rockwool FirePro™ BeamClad

65

260

260

260

260

131

73

022d/01
Rockwool FirePro™ BeamClad

65

260

260

260

260

150

81

022d/01
Rockwool FirePro™ BeamClad

70

260

260

260

260

170

90

022d/01
Rockwool FirePro™ BeamClad

75

260

260

260

260

193

99

022d/01
Rockwool FirePro™ BeamClad

80

260

260

260

260

219

109

022d/01
Rockwool FirePro™ BeamClad

85

260

260

260

260

248

120

022d/01
Rockwool FirePro™ BeamClad

90

260

260

260

260

260

131

022d/01
Rockwool FirePro™ BeamClad

95

260

260

260

260

260

144

022d/01
Rockwool FirePro™ BeamClad

100

260

260

260

260

260

157

022d/01
Rockwool FirePro™ BeamClad

110

260

260

260

260

260

186

022d/01

 

 


 

To read the Red Book section introduction click here.

 

< back to results page