Search by Certificate Number

Rockwool Limited

Wern Tarw
Pencoed
Bridgend
Mid Glamorgan
CF35 6NY
United Kingdom

Tel: +44 (0)1656 862621 • Fax: +44 (0)1656 862302
Email: info@rockwool.co.uk • Web: www.rockwool.co.uk


Certificate No 022d to LPS 1107: Issue 1


4 Sided Protection Of Steel Columns Using The Bonded Noggin Or Stud Welded Pins/Glued Joint System (critical failure temperature 550°C)

Product

Board

Thickness

(mm)

Performance

Hp/A

30min

Performance

Hp/A

60min

Performance

Hp/A

90min

Performance

Hp/A

120min

Performance

Hp/A

180min

Performance

Hp/A

240min

LPCB
Ref. No.
Rockwool FirePro™ BeamClad

25

260

260

149

65

-

-

022d/01
Rockwool FirePro™ BeamClad

30

260

260

207

83

-

-

022d/01
Rockwool FirePro™ BeamClad

35

260

260

260

104

45

-

022d/01
Rockwool FirePro™ BeamClad

40

260

260

260

128

54

-

022d/01
Rockwool FirePro™ BeamClad

45

260

260

260

155

62

-

022d/01
Rockwool FirePro™ BeamClad

50

260

260

260

187

72

44

022d/01
Rockwool FirePro™ BeamClad

55

260

260

260

225

82

50

022d/01
Rockwool FirePro™ BeamClad

60

260

260

260

260

92

55

022d/01
Rockwool FirePro™ BeamClad

65

260

260

260

260

104

61

022d/01
Rockwool FirePro™ BeamClad

70

260

260

260

260

116

68

022d/01
Rockwool FirePro™ BeamClad

75

260

260

260

260

129

74

022d/01
Rockwool FirePro™ BeamClad

80

260

260

260

260

143

81

022d/01
Rockwool FirePro™ BeamClad

85

260

260

260

260

159

88

022d/01
Rockwool FirePro™ BeamClad

90

260

260

260

260

176

96

022d/01
Rockwool FirePro™ BeamClad

95

260

260

260

260

194

103

022d/01
Rockwool FirePro™ BeamClad

100

260

260

260

260

214

124

022d/01
Rockwool FirePro™ BeamClad

110

260

260

260

260

260

129

022d/01

 

 


 

To read the Red Book section introduction click here.

 