Search by Certificate Number

Project Fire Products Limited

Pasturefields Lane Industrial Estate
Pasturefields Lane
Hixon
Staffordshire
ST18 0PH
United Kingdom

Tel: +44 (0)01889 271271 • Fax: +44 (0)845 2800116
Email: info@projectfire.co.uk • Web: www.projectfireproducts.co.uk


Certificate No 060c


Product

Nominal Size (mm)

Pipe Ends

Gasket Type

Maximum Working Pressure (bar)

LPCB
Ref. No.
Model ZC-R-25 (Zonecheck Residential)

25.4 x 25.4

T        

EPDM

12

060c/07
Model ZC-R-32 (Zonecheck Residential)

32 x 25.4

T

EPDM

12

060c/07
Model ZC-R-40 (Zonecheck Residential)

40 x 25.4

T

EPDM

12

060c/07
Model LT-ZCL-65-002 (Zonecheck Live) (Note 2)

65 x 25.4

T        

EPDM

12

060c/04
Model LT-ZCL-80-002 (Zonecheck Live) (Note 2)

80 x 25.4

T

EPDM

12

060c/04
Model LT-ZCL-100-002 (Zonecheck Live) (Note 2)

100 x 25.4

T

EPDM

12

060c/04
Model LT-ZCL-150-002 (Zonecheck Live) (Note 2)

150 x 25.4

T

EPDM

12

060c/04
Model LT-ZCL-SA-002 (Zonecheck Special) (Note 2)

65 x 25.4

T

EPDM

12

060c/05
Model LT-ZCL-SA-002 (Zonecheck Special) (Note 2)

80 x 25.4

T

EPDM

12

060c/05
Model LT-ZCL-SA-002 (Zonecheck Special) (Note 2)

100 x 25.4

T

EPDM

12

060c/05
Model LT-ZCL-SA-002 (Zonecheck Special) (Note 2)

150 x 25.4

T

EPDM

12

060c/05

 

Guidance and approval conditions.
Zonecheck shall be installed in accordance with Project Fire Products Limited 'Instruction Booklet', but subject to guidance below  taking precedence.
1)    The Zonecheck system circulates, but does not draw-off water from the sprinkler system and consequently does not test any zone or control valves.
2)    System approval based on use with LPCB approved and listed flow switch.
3)    Effective operation of the Zonecheck system should be monitored.
4)    In the event of any servicing being warranted on this system, it shall be ensured that this does not impair effective sprinkler protection.
5)    Provision to test flow switches in the normal way (LPC Sprinkler Rules) should also be incorporated.
6)    It shall be ensured that the associated pipework is adequately vented and charged hydraulically.
7)    The automatic means of operation and recording does not form part of this approval.

  

 


 