Search by Certificate Number

Notifier by Honeywell (Pittway Systems Technology Group (Europe) Ltd)

Caburn House
2B Brooks Road
Lewes
East Sussex
BN7 2BY
United Kingdom

Tel: +44 (0)1444 230300 • Fax: +44 (0)1444 230888
Email: sales@notifiersystems.co.uk • Web: www.notifierfiresystems.co.uk

Additional Addresses

Charles Avenue
Burgess Hill
West Sussex
RH15 9UF
United Kingdom

Tel: +44 (0)1444 230230 • Fax: +44 (0)1444 230689
Email: sales@notifierfiresystems.co.uk • Web: www.notifierfiresystems.co.uk


Certificate No 166c to EN 54-3:2001 + A1:2002 + A2:2006
Certificate No 166r-(cl-3) to EN 54-3:2001 + A1:2002 + A2:2006, EN 54-17:2005 & EN 54-23:2010
Certificate No 166t-(cl-3) to EN54-23: 2010
Certificate No 166j-(cl-2) to EN 54-3: 2001 + A1: 2002 + A2: 2006 and EN 54-17: 2005
Certificate No 166m-(cl-3) to EN 54-17:2005 & EN 54-23: 2010
Certificate No 166s-(cl-3) to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-23:2010


Audible Warning Devices

Product Description LPCB
Ref. No.
NFXI-WS-z

Analogue addressableType A/B wall mounted sounder with short circuit isolator

(B501AP-cc, Bcc bases, and Wcc bases)

Notes:

1. z indicates body colour. R=Red, W=Pure White

2  Advanced Protocol (and System Sensor 500 series protocol)

3. Meets the requirements of EN54-3 for all output levels at voltage range 15-29VDC and tones:

        1) 554/440, 2Hz (100ms/400ms); 2) 800/970, 1Hz; 3) 800/970, 2Hz;

        4) 2400/2900, 3Hz; 5) 2500/3100, 2Hz; 6) 988/645, 2Hz;

        7) 660Hz; 8) 970Hz; 9) 1200Hz; 10) 2850Hz;

        11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

        12) 420Hz, 0.625s on, 0.625 sec off; 13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

        14) 660, 3.33Hz, 150ms on, 150ms off; 15) 970, 0.8Hz 0.25s on, 1s off;

        16) 970, 0.5Hz 1s on, 1s off; 17) 2850, 1Hz;

        18) 970, 1Hz 500ms on, 500ms off;

        19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

        20) 800Hz;  21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

        22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off; 23) 2400 - 2850, 7Hz;

        24) 500 - 1200Hz, (0.5s off, 3.5s on);

        25) 800 - 970, 50Hz; 26) 800 - 970, 7Hz;

        27) 800 - 970, 1Hz; 28) 2400 - 2850, 50Hz;

        29) 500 - 1000, 7Hz;

        30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

        31) 800 - 1000, 2Hz; 32) 2400 - 2850, 1Hz.

4.  Approved as Type B only when used with Wcc base.

166j/01
NFXI-WSF-zz

Analogue addressable Type A/B wall mounted sounder/strobe with short circuit isolator

(B501AP-cc, Bcc bases, and Wcc bases)

Notes:

1. zz indicates body/lens colour. RR=Red/Red, WC=Clear/Clear

2. Advanced Protocol (and System Sensor 500 series protocol)

3. Meets the requirements of EN54-3 for all output levels at voltage range 15-29VDC and tones:

        1) 554/440, 2Hz (100ms/400ms); 2) 800/970, 1Hz; 3) 800/970, 2Hz;

        4) 2400/2900, 3Hz; 5) 2500/3100, 2Hz; 6) 988/645, 2Hz;

        7) 660Hz; 8) 970Hz; 9) 1200Hz; 10) 2850Hz;

        11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

        12) 420Hz, 0.625s on, 0.625 sec off;

        13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

        14) 660, 3.33Hz, 150ms on, 150ms off; 15) 970, 0.8Hz 0.25s on, 1s off;

        16) 970, 0.5Hz 1s on, 1s off; 17) 2850, 1Hz;

        18) 970, 1Hz 500ms on, 500ms off;

        19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

        20) 800Hz;  21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

        22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off; 23) 2400 - 2850, 7Hz;

        24) 500 - 1200Hz, (0.5s off, 3.5s on);

        25) 800 - 970, 50Hz; 26) 800 - 970, 7Hz;

        27) 800 - 970, 1Hz; 28) 2400 - 2850, 50Hz;

        29) 500 - 1000, 7Hz;

        30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

        31) 800 - 1000, 2Hz; 32) 2400 - 2850, 1Hz.

4. Certification excludes the strobe function.

5.  Approved as Type B only when used with Wcc base.

166j/02
NFXI-BS-zz

Analogue addressable Type A integrated detector base sounder with short circuit isolator

(B501AP-cc, Bcc and Wcc bases)

Notes:

1. zz indicates body colour. W=Pure White, IV=Detector White

2  Advanced Protocol (and System Sensor 500 series protocol)

3. Meets the requirements of EN54-3 for all output levels at voltage range 15-29VDC and tones:

        1) 554/440, 2Hz (100ms/400ms); 2) 800/970, 1Hz; 3) 800/970, 2Hz;

        4) 2400/2900, 3Hz; 5) 2500/3100, 2Hz; 6) 988/645, 2Hz;

        7) 660Hz; 8) 970Hz; 9) 1200Hz; 10) 2850Hz;

        11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

        12) 420Hz, 0.625s on, 0.625 sec off; 13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

        14) 660, 3.33Hz, 150ms on, 150ms off; 15) 970, 0.8Hz 0.25s on, 1s off;

        16) 970, 0.5Hz 1s on, 1s off; 17) 2850, 1Hz;

        18) 970, 1Hz 500ms on, 500ms off;

        19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

        20) 800Hz;  21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

        22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off; 23) 2400 - 2850, 7Hz;

        24) 500 - 1200Hz, (0.5s off, 3.5s on);

        25) 800 - 970, 50Hz; 26) 800 - 970, 7Hz;

        27) 800 - 970, 1Hz; 28) 2400 - 2850, 50Hz;

        29) 500 - 1000, 7Hz;

        30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

        31) 800 - 1000, 2Hz; 32) 2400 - 2850, 1Hz.

166j/03
NFXI-BSF-zzz

Analogue addressable Type A integrated detector base sounder/strobe with short circuit isolator

(B501AP-cc, Bcc and Wcc bases)

Notes:

1. zzz indicates body/lens colour. WC=Pure White/Clear, IVC=Detector White/Clear

2. Advanced Protocol (and System Sensor 500 series protocol)

3.  Meets the requirements of EN54-3 for all output levels at voltage range 15-29VDC and tones:

        1) 554/440, 2Hz (100ms/400ms); 2) 800/970, 1Hz; 3) 800/970, 2Hz;

        4) 2400/2900, 3Hz; 5) 2500/3100, 2Hz; 6) 988/645, 2Hz;

        7) 660Hz; 8) 970Hz; 9) 1200Hz; 10) 2850Hz;

        11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

        12) 420Hz, 0.625s on, 0.625 sec off; 13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

        14) 660, 3.33Hz, 150ms on, 150ms off; 15) 970, 0.8Hz 0.25s on, 1s off;

        16) 970, 0.5Hz 1s on, 1s off; 17) 2850, 1Hz;

        18) 970, 1Hz 500ms on, 500ms off;

        19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

        20) 800Hz;  21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

        22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off; 23) 2400 - 2850, 7Hz;

        24) 500 - 1200Hz, (0.5s off, 3.5s on);

        25) 800 - 970, 50Hz; 26) 800 - 970, 7Hz;

        27) 800 - 970, 1Hz; 28) 2400 - 2850, 50Hz;

        29) 500 - 1000, 7Hz;

        30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

        31) 800 - 1000, 2Hz; 32) 2400 - 2850, 1Hz.

4.  Certification excludes the strobe function.

166j/04
NFXI-WF-WC

Analogue addressable wall mounted LED strobe with short circuit isolator (B501AP base)

Note:

1.  The wall mounted VAD meets the requirements of EN 54-23: 2010

     for the following category (light pattern details):
     - Category O-2.4-2
     - Flash rate 1Hz

     - Synchronization

2.  Type A with Bcc deep back box, Type B with Wcc deep back box

166m/01
NFXI-WCF-WC

Analogue Addressable High Output Beacon with Short Circuit Isolator (B501AP base)

Notes:

1. The ceiling / wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories (light pattern details):

- Category C: C-3-5.1, C-6-5.1, C-9-5.1

- Category W: W-2.4-2.76

- Flash rate 0.5Hz

- Synchronization

2. Type A indoor use with B501AP only, Type B outdoor use with B501AP and WRR or WPW

166m/02
NFX-WCF-WC

Analogue Addressable High Output Beacon (B501AP base)

Notes:

1. The ceiling / wall mounted VAD meets the requirements of EN 54-23: 2010 for the following categories (light pattern details):

- Category C: C-3-5.1, C-6-5.1, C-9-5.1

- Category W: W-2.4-2.76

- Flash rate 0.5Hz

- Synchronization

2. Type A indoor use with B501AP only, Type B outdoor use with B501AP and WRR or WPW

166t/02
NFXI-WSF-WC

Analogue Addressable Wall Mounted Sounder / LED Strobe with Short Circuit Isolator (B501AP base)

Notes:

1. The wall mounted VAD meets the requirements of EN 54-23: 2010 for the following category (light pattern details):

- Category O - Open Class

- Flash rate 1Hz

- Synchronization

2. WC=Pure White/Clear indicates body/lens colour.

3. Type A with Bcc deep back box, Type B with Wcc deep back box

4. Meets the requirements of EN54-3: 2001 at the following tones:

1) Alternating 525/440, 2Hz (100ms/400ms);

2) Alternating 800/922, 1Hz;

3) Alternating 800/922, 2Hz;

4) Alternating 2400/2900, 3Hz;

5) Alternating 2500/3100, 2Hz;

6) Alternating 988/645, 2Hz;

7) Continuous 630Hz;

8) Continuous 922Hz;

9) Continuous 1200Hz;

10) Continuous 2810Hz;

11) Sweep 150-1000Hz, rise 10s, stable 40s, fall 10s, stable 20s, then

repeating;

12) Intermittent 420Hz, 0.625s on, 0.625 sec off;

13) Sweep 500-1200Hz, 0.25 sec off, 3.75 sec on;

14) Intermittent 630, 3.33Hz, 150ms on, 150ms off;

15) Intermittent 922, 0.8Hz 0.25s on, 1s off;

16) Intermittent 922, 0.5Hz 1s on, 1s off;

17) Intermittent 2810, 1Hz;

18) Intermittent 922, 1Hz 500ms on, 500ms off;

19) Intermittent 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

20) Continuous 800Hz;

21) Sweep 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

22) Sweep 1200 - 500Hz, 0.99Hz 1s on, 0.01s off;

23) Sweep 2400 - 2850, 7Hz;

24) Sweep 500 - 1200Hz, (0.5s off, 3.5s on);

25) Sweep 800 - 970, 50Hz;

26) Sweep 800 - 970, 7Hz;

27) Sweep 800 - 970, 1Hz;

28) Sweep 2400 - 2850, 50Hz;

29) Sweep 500 - 1000, 7Hz;

30) Sweep 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

31) Sweep 800 - 1000, 2Hz;

32) Sweep 2400 - 2850, 1Hz

166r/01
NFXI-DSF-WC

Analogue Addressable Type A Integrated Detector Base Sounder/Beacon with Short Circuit Isolator (B501AP base)

Notes:

1. The wall mounted VAD meets the requirements of EN 54-23: 2010 for the following category (light pattern details):

- Category O - Open Class

- Flash rate 1Hz

- Synchronization

2. WC=Pure White/Clear indicates body/lens colour.

3. Advanced Protocol (and System Sensor 500 series protocol)

4. Meets the requirements of EN54-3 for all output levels at voltage range 15-29VDC and tones:

1) 554/440, 2Hz (100ms/400ms);

2) 800/970, 1Hz;

3) 800/970, 2Hz;

4) 2400/2900, 3Hz;

5) 2500/3100, 2Hz;

6) 988/645, 2Hz;

7) 660Hz;

8) 970Hz;

9) 1200Hz;

10) 2850Hz;

11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

12) 420Hz, 0.625s on, 0.625 sec off;

13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

14) 660, 3.33Hz, 150ms on, 150ms off;

15) 970, 0.8Hz 0.25s on, 1s off;

16) 970, 0.5Hz 1s on, 1s off;

17) 2850, 1Hz;

18) 970, 1Hz 500ms on, 500ms off;

19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

20) 800Hz;

21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off;

23) 2400 - 2850, 7Hz;

24) 500 - 1200Hz, (0.5s off, 3.5s on);

25) 800 - 970, 50Hz;

26) 800 - 970, 7Hz;

27) 800 - 970, 1Hz;

28) 2400 - 2850, 50Hz;

29) 500 - 1000, 7Hz;

30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

31) 800 - 1000, 2Hz;

32) 2400 - 2850, 1Hz

166r/02
NFX-DSF-WC

Analogue Addressable Type A Integrated Detector Base Sounder/Beacon (B501AP base)

Notes:

1. The wall mounted VAD meets the requirements of EN 54-23: 2010 for the following category (light pattern details):

- Category O - Open Class

- Flash rate 1Hz

- Synchronization

2. PC=Pure White/Clear indicates body/lens colour.

3. Advanced Protocol (and System Sensor 500 series protocol)

4. Meets the requirements of EN54-3 for all output levels at voltage range 15-32VDC and tones:

1) 554/440, 2Hz (100ms/400ms);

2) 800/970, 1Hz;

3) 800/970, 2Hz;

4) 2400/2900, 3Hz;

5) 2500/3100, 2Hz;

6) 988/645, 2Hz;

7) 660Hz;

8) 970Hz;

9) 1200Hz;

10) 2850Hz;

11) 150-1000, rise 10s, stable 40s, fall 10s, stable 20s, then repeating;

12) 420Hz, 0.625s on, 0.625 sec off;

13) 500-1200Hz, 0.25 sec off, 3.75 sec on;

14) 660, 3.33Hz, 150ms on, 150ms off;

15) 970, 0.8Hz 0.25s on, 1s off;

16) 970, 0.5Hz 1s on, 1s off;

17) 2850, 1Hz;

18) 970, 1Hz 500ms on, 500ms off;

19) 950, 0.22Hz (0.5s on, 0.5s off) x 3, 1.5s off;

20) 800Hz;

21) 400-1200Hz, (0.5s on, 0.5s off) x 3, 1.5s off;

22) 1200 - 500Hz, 0.99Hz 1s on, 0.01s off;

23) 2400 - 2850, 7Hz;

24) 500 - 1200Hz, (0.5s off, 3.5s on);

25) 800 - 970, 50Hz;

26) 800 - 970, 7Hz;

27) 800 - 970, 1Hz;

28) 2400 - 2850, 50Hz;

29) 500 - 1000, 7Hz;

30) 500 - 1200 - 500, 0.166Hz rise 1s, stable 4s, fall 1s;

31) 800 - 1000, 2Hz;

32) 2400 - 2850, 1Hz

166s/02
NBS3D

4 Tone Type A conventional ceiling mounting sounder, white

Note:

        Meets the requirements of EN 54-3 at all output levels, and voltage

         ranges of 10-14 VDC and 19.5-28 VDC for the following tones:

         1 - Falling 1200Hz-500Hz over 3.5s followed by 0.5s silence

         2 - 800Hz continuous

         3 - 500Hz-1200Hz slow whoop

         4 - Falling 1200Hz-500Hz over 3.5s followed by 0.5s silence

166c/40

 

Ancillaries
B501AP Mounting base - Low profile base IP21C
WPW Deep back box for outdoor (White)
WRR Deep back box for outdoor (Red)

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page