Search by Certificate Number

Apollo Fire Detectors Limited

36 Brookside Road
Havant
Hampshire
PO9 1JR
United Kingdom

Tel: +44 (0)2392 492412 • Fax: +44 (0)2392 492754
Email: enquiries@apollo-fire.co.uk


Certificate No 010ay to EN 54-17: 2005 and EN 54-23: 2010
Certificate No 010ba to EN 54-23:2010
Certificate No 010bl to EN 54-3:2001 + A1:2002 + A2:2006 & EN 54-23:2010


Alarm Warning Devices

Product Description LPCB
Ref. No.
45681-709

XP95 Visual Alarm Device Base (White) with Isolator

Notes:        

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator.

5.   The VAD is a Type A device and includes synchronisation.

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010ay/01
55000-740

Loop-Powered Type A VAD 15m (Red)

1. The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

   - Category rating C-3-15

   - Synchronization

   - Flash rate 0.5 Hz

   - White LED

   - Clear lens

2. Approved with XP95/Discovery 45681-210 mounting base and
    45681-284 short circuit isolating base

010ba/01
55000-741

Loop-Powered Type A VAD 6m (Red)

Notes:

1.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

-        Category rating W-2.4-6

-        Synchronization

-        Flash rate 0.5 Hz

-        White LED

-        Clear lens

2.   Approved with XP95/Discovery 45681-210 mounting base and 45681-284 short circuit isolating base

010ba/02
55000-742

Loop-Powered Type A VAD 8.5m (Red)

1. The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

   - Category rating C-3-8.5

   - Synchronization

   - Flash rate 0.5 Hz

   - White LED

   - Clear lens

2. Approved with XP95/Discovery 45681-210 mounting base and
    45681-284 short circuit isolating base

010ba/03
55000-743

Loop-Powered Type A VAD 15m (White)

1. The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

   - Category rating C-3-15  

   - Synchronization

   - Flash rate 0.5 Hz

   - White LED

   - Clear lens

2. Approved with XP95/Discovery 45681-210 mounting base and
    45681-284 short circuit isolating base

010ba/04
55000-744

Loop-Powered Type A VAD 6m (White)

Notes:

1.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

-        Category rating W-2.4-6

-        Synchronization

-        Flash rate 0.5 Hz

-        White LED

-        Clear lens

2.   Approved with XP95/Discovery 45681-210 mounting base and 45681-284 short circuit isolating base

010ba/05
55000-745

Loop-Powered Type A VAD 8.5m (White)

1. The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

   - Category rating C-3-8.5

   - Synchronization

   - Flash rate 0.5 Hz

   - White LED

   - Clear lens

2. Approved with XP95/Discovery 45681-210 mounting base and
    45681-284 short circuit isolating base

010ba/06
55000-070

XP95 VAD C-3-15 (White Flash) (45681-518 base)

Notes:

1.        Approved for Type B Outdoor use

2.        The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: C-3-15

010ba/07
55000-071

XP95 VAD C-3-9 (Red Flash) (45681-518 base)

Notes:

1.        Approved for Type B Outdoor use

2.        The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: C-3-9

010ba/08
55000-072

XP95 VAD W-3.1-11.3 (White Flash) (45681-518 base)

Notes:

1.        Approved for Type B Outdoor use

2.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: W-3.1-11.3

010ba/09
55000-073

XP95 VAD W-2.4-7.49 (Red Flash) (45681-518 base)

Notes:

1.        Approved for Type B Outdoor use

2.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: W-2.4-7.49

010ba/10
55000-074

XP95 Sounder VAD C-3-15 (White Flash) (45681-518 base)

Notes:

1.        Approved for Type A Indoor use only

2.        The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: C-3-15

3.        Meets the requirements of EN 54-3:2001 at the following tones:

- Tone 1, Apollo Standard Tone, 848Hz, 0.5s / 569Hz, 0.5s

- Tone 2, Dutch Slow Whoop, 500 - 1200Hz in 3.5s, 0.5s off

- Tone 3, German DIN Tone, 1200Hz - 500Hz over 1s

- Tone 4, Alert Tone (Pulsed), 848Hz, 1s on, 1s off

- Tone 5: Alert Tone (Continuous), 848Hz, continuous

010bl/01
55000-075

XP95 Sounder VAD C-3-9 (Red Flash) (45681-518 base)

Notes:

1.        Approved for Type A Indoor use only

2.        The ceiling mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: C-3-9

3.        Meets the requirements of EN 54-3:2001 at the following tones:

- Tone 1, Apollo Standard Tone, 848Hz, 0.5s / 569Hz, 0.5s

- Tone 2, Dutch Slow Whoop, 500 - 1200Hz in 3.5s, 0.5s off

- Tone 3, German DIN Tone, 1200Hz - 500Hz over 1s

- Tone 4, Alert Tone (Pulsed), 848Hz, 1s on, 1s off

- Tone 5: Alert Tone (Continuous), 848Hz, continuous

010bl/02
55000-076

XP95 Sounder VAD W-3.1-11.3 (White Flash) (45681-518 base)

Notes:

1.        Approved for Type A Indoor use only

2.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: W-3.1-11.3

3.        Meets the requirements of EN 54-3:2001 at the following tones:

- Tone 1, Apollo Standard Tone, 848Hz, 0.5s / 569Hz, 0.5s

- Tone 2, Dutch Slow Whoop, 500 - 1200Hz in 3.5s, 0.5s off

- Tone 3, German DIN Tone, 1200Hz - 500Hz over 1s

- Tone 4, Alert Tone (Pulsed), 848Hz, 1s on, 1s off

- Tone 5: Alert Tone (Continuous), 848Hz, continuous

010bl/03
55000-077

XP95 Sounder VAD W-2.4-7.49 (Red Flash) (45681-518 base)

Notes:

1.        Approved for Type A Indoor use only

2.        The wall mounted VAD meets the requirements of EN 54-23:2010 for the following:

- Synchronization

- Flash rate 0.5 Hz, 1 Hz

- Category setting: W-2.4-7.49

3.        Meets the requirements of EN 54-3:2001 at the following tones:

- Tone 1, Apollo Standard Tone, 848Hz, 0.5s / 569Hz, 0.5s

- Tone 2, Dutch Slow Whoop, 500 - 1200Hz in 3.5s, 0.5s off

- Tone 3, German DIN Tone, 1200Hz - 500Hz over 1s

- Tone 4, Alert Tone (Pulsed), 848Hz, 1s on, 1s off

- Tone 5: Alert Tone (Continuous), 848Hz, continuous

010bl/04

 

Bases:
45681-210    XP95/Discovery mounting base
45681-284    XP95/Discovery short circuit isolating base
    45681-518    Enhanced Deep Isolating Base (Red)

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page