Search by Certificate Number

Apollo Fire Detectors Limited

36 Brookside Road
Havant
Hampshire
PO9 1JR
United Kingdom

Tel: +44 (0)2392 492412 • Fax: +44 (0)2392 492754
Email: enquiries@apollo-fire.co.uk


Certificate No 010aw to EN54-23: 2010, EN54-3: 2001 + A1:2002 + A2: 2006 and EN54-17: 2005


Alarm Warning Devices

Product Description LPCB
Ref. No.
45681-700

Discovery Sounder Visual Alarm Device Base (White) with Isolator (45681-292 and 45681-293 Caps)

Notes:

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator.

5.   The VAD is a Type A device and includes synchronisation

6.   Meets the requirements of EN 54-3: 2001 at the following tone settings:

        Tone 1 Apollo Evacuation Tone - 567Hz for 0.5s, 850Hz for 0.5s

        Tone 12 Alternating - (Hochiki & Fulleon) - 925Hz for 0.25s,

        626Hz for 0.25s

        Tone 14 Medium Sweep - 800Hz to 970Hz at 1 Hz

        Tone 3 Dutch Slow Whoop (sweep) - 500Hz - 1200Hz for 3.5s,

        off for 0.5s

        Tone 4 DIN Tone (sweep) - 1200Hz - 500Hz for 1s

        Tone 18 Swedish Fire Tone - 660 Hz, 150ms on, 150ms off

        Tone 0 Apollo Alert Tone - 1s off, 1s 850Hz

        Tone 11 Continuous (Hochiki & Fulleon) - 925Hz

        Tone 13 Continuous - 970Hz

        Tone 2 Continuous - 850Hz

        Tone 17 Swedish all clear signal - Continuous - 660Hz

7.    Approved for sounder volumes 2-7 only

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010aw/01
45681-701

Discovery Marine Sounder Visual Alarm Device Base (White) with Isolator (45681-292 and 45681-293 Caps)

Notes:

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator.

5.   The VAD is a Type A device and includes synchronisation.

6.   Meets the requirements of EN 54-3: 2001 at the following tone settings:

        Tone 1 Apollo Evacuation Tone - 567Hz for 0.5s, 850Hz for 0.5s

        Tone 12 Alternating - (Hochiki & Fulleon) - 925Hz for 0.25s,626Hz for 0.25s

        Tone 14 Medium Sweep - 800Hz to 970Hz at 1 Hz

        Tone 3 Dutch Slow Whoop (sweep) - 500Hz - 1200Hz for 3.5s,off for 0.5s

        Tone 4 DIN Tone (sweep) - 1200Hz - 500Hz for 1s

        Tone 18 Swedish Fire Tone - 660 Hz, 150ms on, 150ms off

        Tone 0 Apollo Alert Tone - 1s off, 1s 850Hz

        Tone 11 Continuous (Hochiki & Fulleon) - 925Hz

        Tone 13 Continuous - 970Hz

        Tone 2 Continuous - 850Hz

        Tone 17 Swedish all clear signal - Continuous - 660Hz

7.    Approved for sounder volumes 2-7 only

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010aw/02
45681-705

XP95 Sounder Visual Alarm Device Base (white) with Isolator

(45681-292 and 45681-293 Caps)

Notes:

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator.

5.   The VAD is a Type A device and includes synchronisation.

6.   Meets the requirements of EN 54-3: 2001 at the following tone settings:

        Tone 1 Apollo Evacuation Tone - 567Hz for 0.5s, 850Hz off for 0.5s

        Tone 0 Apollo Alert Tone - 1s off, 1s 850Hz

7.    Approved for sounder volumes 2-7 only.

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010aw/03
45681-706

XP95 Sounder Visual Alarm Device Base (white) Slow Whoop with Isolator

(45681-292 and 45681-293 Caps)

Notes:

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator.

5.   The VAD is a Type A device and includes synchronisation.

6.   Meets the requirements of EN 54-3: 2001 at the following tone settings:

        Tone 2 Continuous - 850Hz

        Tone 3 Dutch Slow Whoop (sweep) - 500 Hz - 1200Hz for 3.5s/0Hz,

        off for 0.5s

7.   Approved for sounder volumes 2-7 only.

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010aw/04
45681-707

XP95 Sounder Visual Alarm Device Base (white) DIN with Isolator

   (45681-292 and 45681-293 Caps)

Notes:

1.   The VAD is rated as open class: (Refer to installation guide).

2.   The VAD operating voltage range 17-28V DC (24V nominal).

3.   The VAD Light mode (light pattern details): 0.5Hz mode only.

4.   The VAD includes a short circuit isolator function

5.   The VAD is a Type A device and includes synchronisation.

6.   Meets the requirements of EN 54-3: 2001 at the following tone settings:

        Tone 4 DIN Tone (sweep) - 1200Hz - 500Hz for 1s

        Tone 2 Continuous - 850Hz

7.   Approved for sounder volumes 2-7 only.

Accessories:

45681-292        White Cap (Lockable)

45681-293        Red Cap (Lockable)

010aw/05

 

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page