Search by Certificate Number

Morley-IAS Fire Systems by Honeywell (Pittway Systems Technology Group (Europe) Ltd)

Caburn House
2B Brooks Road
Lewes
East Sussex
BN7 2BY
United Kingdom

Tel: +44 (0)1444 230300 • Fax: +44 (0)1444 230888
Email: sales@morleyias.co.uk • Web: www.morley-ias.co.uk


Certificate No 199ae-(cl-1) to EN54-17: 2005 & EN54-20: 2006


Aspirating Smoke Detectors

Product Description LPCB
Ref. No.
MI-FL2011EI-HS

Analogue Addressable Single Channel Loop-Based Aspirating Detector (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/01
MI-FL2012EI-HS

Analogue Addressable Loop-Based Single Channel Unit Common Chamber Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1.        This device has single channel capability with two high sensitivity smoke sensors in a common chamber.

2.        For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

3.        The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

4. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/02
MI-FL2022EI-HS

Analogue Addressable Dual Channel Loop-Based Aspirating Detector, Dual Sensors (F-INF-25 In line filter)

Notes:

1. For compliance with Clause 5.10 of EN54-20: 2006, the detector must be supplied by a power supply complying with EN54-4.

2. The devices are only approved at the following levels:

·        Alarm Level 1 meets class A, B and C

·        Alarm Levels 2-3 meets class B and C

·        Alarm Levels 4-5 meet class C only

With Filter, part number F-INF-25

·        Alarm Levels 1-2 meet class B and C

·        Alarm Level 3 meets class C only

3. The class of any pipe / hole configuration and detector sensitivity must be determined using PipelQ software (version 2.9 or higher), with the EN54 option selected.

199ae/03

 

Accessories
F-INF-25    In line filter
    

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page