Search by Certificate Number

LPG Técnicas En Extinción De Incendios, S.L.

Mestre Joan Corrales 107-109
08950 Esplugues de Llobregat
Barcelona
Spain

Tel: +34 93 480 2925 • Fax: +34 93 473 7492
Email: marketing@lpg.es • Web: www.lpg.es


Certificate No 446a


LPG HFCS Discharge Hoses for HFC23, HFC125 and HFC227ea

Product

Description

LPCB
Ref. No.
30508HFC

Rigid telescopic hose 1.5" (1)

446a/06
30508080

Rigid hose 1½" HG/MF (1)

446a/06
30508000

Rigid hose 1½" HG/HG (1)

446a/06
30506HFC

Rigid telescopic hose 1" (1)

446a/06
30502140

R2F hose 400 G 1" HG/HF (1)

446a/06
30506000

R2F hose 320 G 1" HG/HG (1)

446a/06
30506070

R2F hose 400 G ¾ " HG/HF (1)

446a/06

 

(1) Maximum Working Pressure 160 bar

a)    This range of equipment is suitable for storage from  - 20º to 50ºC
b)    Systems are specified as follows:
  HFC23: System pressure is specified as 41 bar @ 20°C, maximum filling density 0.85 kg/l.
    HFC125: System pressure is specified as 41 bar @ 20ºC, maximum filling density 0.93 kg/l.
    HFC227ea: System pressure is specified as 41 bar @ 20ºC, maximum filling density 1.15 kg/l.
c)    Systems with HFC23 are not superpressurised.
d)    Components listed are appropriate for the gas as indicated.

 


 

To read the Red Book section introduction click here.

 