Certificate No 446a


LPG HFCS Manifolds for HFC23, HFC125 and HFC227ea

Product

Description

LPCB
Ref. No.
3811VCCD

Single Row manifold

446a/12

 

According to the following:
   V denotes container size: '1' means 67L, '2' means 75L and '4' means 100L/120L
CC denotes number of ports
D denotes manifold diameter where '3' means 1 ¼", '4' means 1 ½", '5' means 2", '6' means 2 ½", '7' means 3" and '8' means 4"
    

a)    This range of equipment is suitable for storage from  - 20º to 50ºC
b)    Systems are specified as follows:
  HFC23: System pressure is specified as 41 bar @ 20°C, maximum filling density 0.85 kg/l.
    HFC125: System pressure is specified as 41 bar @ 20ºC, maximum filling density 0.93 kg/l.
    HFC227ea: System pressure is specified as 41 bar @ 20ºC, maximum filling density 1.15 kg/l.
c)    Systems with HFC23 are not superpressurised.
d)    Components listed are appropriate for the gas as indicated.
  

 


 