Search by Certificate Number

Kingspan Ltd

Carrickmacross Road
Kingscourt
Co. Cavan
Ireland

Tel: +353 42 969 8572 • Fax: +353 42 969 8576/77
Email: info.irl@kingspanpanels.com • Web: www.kingspanpanels.com


Certificate No 186d to LPS 1181 Part 2: Issue 2


Product

Specification Thickness (mm)

Specification Wall Panel Orientation (H/V)

(Note 1)

Kingspan Model Specification Ref

(Note 2)

Fire Resistance Integrity/Insulation (min)

LPS 1181-2 Grade

Core Material

(Note 2)

LPCB
Ref. No.
Kingspan IPN QuadCore KS600-1200CS (wall and ceiling panels)

80 - 200

V

36 Rev 0

-/-

INT-3

Hybrid insulation

279e/01
Kingspan IPN QuadCore KS600-1200CS (wall panel)

100-200

V

36 Rev 0

45/39

INT-2

Hybrid insulation

279e/02
Kingspan IPN QuadCore KS600-1200CS (ceiling panel)

175 - 200

-

36 Rev 0

95/65

INT-2

Hybrid insulation

279e/03
Kingspan IPN QuadCore KS600-1200CS (wall panel)

100 - 200

V

36 Rev 0

128/30

INT-2

Hybrid insulation

279e/04
Kingspan IPN QuadCore KS600-1200CS (ceiling panel)

125 - 200

-

36 Rev 0

57/49

INT-2

Hybrid insualtion

279e/05
Kingspan IPN QuadCore KS600-1200CS (wall panel)

175 - 200

V

36 Rev 0

211/65

INT-2

Hybrid insulation

279e/06

 

Notes;
1.    Wall panel orientation, Horizontal or Vertical (H/V), relates to the long joint orientation
2.    The Kingspan Model Specification documents contain full system details including panel fixing requirement, joint seals and stitching details as applicable. Reference must be made to the appropriate Model Specification to define the specific installation requirements. Copies of Model specifications are available on request please contact the Kingspan Envirocare Department - refer to model specificatio LPCB 36 Rev 0 for full details.

 


 

To read the Red Book section introduction click here.

 